September 2016
INM RTK RT-AD rev 4

Instruction manual

MTL process alarm equipment

RTK RT-AD range 

Dual redundant power supply

Summary of Contents for CROUSE-HINDS RT-AD Series

Page 1: ...September 2016 INM RTK RT AD rev 4 Instruction manual MTL process alarm equipment RTK RT AD range Dual redundant power supply...

Page 2: ...ARATION OF CONFORMITY A printed version of the Declaration of Conformity has been provided separately within the original shipment of goods However you can find a copy of the latest version at http ww...

Page 3: ...ailable Models 1 2 2 INSTALLATION 2 2 1 Mounting Details 2 3 2 2 Connections 4 2 2 1 GND 4 2 2 2 Supply 4 2 2 3 Outputs 5 2 2 4 Relay 1 and 2 5 2 2 5 Allowable wires 5 3 TECHNICAL SPECIFICATION 6 3 1...

Page 4: ...d in this manual to alert the user to important information WARNING Warnings are provided to ensure operator safety and MUST be followed CAUTION Cautions are provided to prevent damage to the instrume...

Page 5: ...88 264V AC 47 63Hz 120 270V DC 1 3 Available Models Only those combinations listed in the table below are available Model Input Range Supply 1 Input Range Supply 2 RT AD LH 25 24 36 72VDC 88 264VAC o...

Page 6: ...Details There are two sizes of enclosure used for the RT AD range of power supply The smaller of the two sizes houses all supplies up to and including 150 Watt output power whilst the larger is used f...

Page 7: ...INM RTK RT AD rev 4 3 Figure 2 Dimensions for 200 320W Supplies 165 320 150 134 5 5 67 5 15 154 15 15 Connections this end...

Page 8: ...protective safety earth connection to the GND terminal 2 2 2 SUPPLY Connect the correct supply inputs to SUPPLY 1 and SUPPLY 2 as defined on the product label which is located on the opposite end of t...

Page 9: ...n the supply input or the internal supply fail the contacts become de energised with the NO contact open and the NC contact closed 2 2 5 Allowable wires The connections can be made using the following...

Page 10: ...35 of output voltage Hold up time Typically 20ms at 240V AC Output isolation 500V AC Withstand voltage output to Earth GND or relay contacts Output Derating Some models need to be derated for operatin...

Page 11: ...2 heavy industrial level criteria A LVD All variants EN61010 1 2010 and IEC61010 2 201 Environment Operating temperature 10 to 60 C Note Some models need to be derated for operating temperature For m...

Page 12: ...full power at 45 C and 0 at 60 C 100 M 100 full power 0 35 C Reducing to 80 full power at 45 C and 0 at 60 C 100 H 100 full power 0 40 C Reducing to 60 full power at 55 C and 0 at 60 C 80 Full power...

Page 13: ...er supply must only be performed by competent service personnel WARNING Hazardous voltages may exist on the connections of the power supply Remove all power before removing any cover or connection Ens...

Page 14: ...10 INM RTK RT AD rev 4 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 15: ...INM RTK RT AD rev 4 11 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 16: ...INDIA MTL India No 36 Nehru Street Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia sr...