background image

INSTALLATION  

MANUAL

MIM-D00

DMS

  

(Data Management Server)

DB98-29919A(1)

E

K

C

CHINESE

ENGLISH

MIM-D00_IM_E_29919-1.indd   29

2008-09-10   ソタネト 1:27:35

Summary of Contents for MIM-D00

Page 1: ...INSTALLATION MANUAL MIM D00 DMS Data Management Server DB98 29919A 1 E K C CHINESE ENGLISH ...

Page 2: ...horized installation center WARNING CAUTION Do not use inflammable gases near the DMS Do not install the DMS in a location where it will come into contact with combustible gases machine oil sulphide gas etc Avoid locations where acid alkali solution or special spray is used Choose a location that is dry and sunny but not exposed to direct sunlight Suitable temperature is between 0 C 32 F and 39 C ...

Page 3: ... PRECAUTIONS 2 BEFORE INSTALLING THE DMS 4 ACCESSORIES 5 PRODUCT DESIGN 5 PRODUCT DIMENSIONS 6 SYSTEM ARCHITECTURE 7 COMPATIBLE DEVICES 8 INSTALLING THE DMS 9 DMSEXTERNAL DISPLAY 14 SETTING THE COMPUTER ENVIRONMENT 15 APPENDIX 22 ...

Page 4: ...to page 23 24 for explanation on technical terms DMS IP A public IP is needed to access the DMS over the internet One public IP is needed for each DMS A private IP may be used if the DMS need not be accessed over the internet The DMS does not support DHCP Note DHCP Dynamic Host Configuration Protocol An Internet protocol for automating the configuration of computers that use TCP IP DHCP is used to...

Page 5: ...alled by a trained installer Ensure the main power is turned off before installing the DMS The power cable and the communication cable must be installed according to the national electrical wiring regulations VCTF 2C x 0 75mm2 must be used for the communication and power cables Ensure the cables are out of user s reach Caution Product Design ...

Page 6: ... mm Installation Method Fix the provided screws to the wall and use the four holes on the back of the DMS to hang the DMS on the wall 219 150 101010 37 135 135 20 30 60 28 8 8 130 60 Serial Port LAN Port Reset Button Power Input ...

Page 7: ...equipments to be purchased separately Centralized Controller Centralized Controller SIM I M Transmitter Transmitter Transmitter Power meter Power related equipments to be purchased separately Connect one power meter to N number of outdoor units Make sure the power meter capacity is greater than the total capacity of the outdoor units DMS ...

Page 8: ...eded for power distribution 5 Watt hour Meter RS485 comm type Needed for power distribution Please consult Samsung for compatible power meters Note Products with are not Samsung products and must be purchased separately Only selected power meters may be used for protocol compatibility issues Maximum Devices attachable The maximum number of devices attachable to the DMS is as follow Devices Max Not...

Page 9: ... from the centralized controller to the J1 terminal of the DMS Communication will fail if the cable is not connected properly 5 Connect the LAN cable to the J6 terminal of the DMS 6 Close the case cover after making sure the power cable is not pressed 7 Assemble the cover as shown in the picture to avoid exposure of the stripped wires Maximum 16 centralized controllers can be connected to one DMS ...

Page 10: ... on the bottom of the DMS front cover 2 Hold the bottom two sides of the DMS and push upwards to slide open the cover Sliding type cover 3 Connect the provided power cable to the power terminal 4 Connect the C1 C2 communication cable from the SIM I M to the J1 terminal of the DMS Communication will fail if the cable is notconnected properly ...

Page 11: ...ing sure the power cable is not pressed 7 Assemble the cover as shown in the picture to avoid exposure of the stripped wires Maximum 8 SIM I Ms can be connected to one DMS Maximum8powermeterscanbeconnectedtooneSIMI M Separate the power cable and the communication cable when installing the DMS The DMS may malfunction due to electrical disturbance Caution ...

Page 12: ...perating Pressing the reset switch will delete all current data The switch must only be operated by the installer 2 DIP Switch SW3 Used for setting the DI mode Operate only when the DI port is used Factory Default Settings SW03 Note Refer to the appendix page 22 23 for how to install the DI external signal control ...

Page 13: ... status previous to ON signal when the external input signal changes to OFF Pattern 3 OFF ON OFF OFF Responds when there is an input signal on DI 1 and DI 2 Operation Changes the on off status of all the indoor units depending on the ON OFF status of the DI 1 input Enables disables the remote controllers depending on the ON OFF status of the DI 2 input ON enable OFF disable The schedules will run ...

Page 14: ...omplete RS485 Rx Green Flickers during data transmission from the centralized controller to the DMS DI 1 Status Green Lights on when using the external contact signal control Refer to page 23 DI 2 Status Green Lights on when using the external contact signal control Refer to page 23 A C Running Green DMS status indicator Running status of indoor unit indicator You may setup A C Running LED to indi...

Page 15: ... be downloaded from http java sun com j2se or automatically by connecting to the DMS through the internet 3 Connection Method Choose one of the two methods list below Connecting the DMS directly to the computer Connecting the DMS using a HUB Note Cross Cable A cross cable is used when connecting two PCs directly A direct cable is used to connect the PC to a HUB and a cross cable is used to connect...

Page 16: ...he DMS as follow Click on the My Network icon on the desktop to access the above screen Right click and press properties Right click on the Local Area Network icon and press properties Select Internet protocol TCP IP and press properties 2 Run the route command Start Run Type in the following command Enter Route add 192 168 0 0 mask 255 255 255 0 Computer_IP The computer IP refers to the IP addres...

Page 17: ...92 168 0 2 If the connection is successful the following front page will load The DMS will prompt for a user ID and a password as shown above The factory default user setting is as follow Type in the ID and the password and click on LOGIN Change the user setting if needed for security reasons admin 1234 ...

Page 18: ...E 18 Setting the Computer Environment Continued The following screen is displayed if the login is successful Click on SYSTEM ENVIRONMENT ...

Page 19: ...e for accurate error time logs and schedule controls Click on the Edit button to change the Operation mode of A C Running When you click Edit button it will change to Save button Select the mode you wish to set DMS status Green light will flicker every 5 seconds when DMS operates normally Running status of indoor unit Solid green light will turn on when the indoor units operate normally at least 1...

Page 20: ...oom mode tracking Control the indoor units according to the MAIN address of the indoor units Indoor unit MAIN address and the RMC address will be displayed The message Tracking Please wait will be displayed while tracking Tracking will take at least a few seconds to at most three minutes Tracking Click on the tracking button once the environment is set The above screen will be displayed ...

Page 21: ...and the centralized controllers The basic settings for the internet control is set Please refer to the user manual for detailed information on internet control The following screen is display if tracking is successful Note For detail instructions onTracking refer to user s manual ...

Page 22: ...ings on the Operation mode of A C Running LED DMS status Green light will flicker every 5 seconds when DMS operates normally Running status of indoor unit Solid green light will turn on when the indoor units operate normally at least 1 indoor unit DO 2 Digital Output Outputs 12V if there is an error on the indoor or outdoor unit or if communication error occurs External circuit may be built for di...

Page 23: ...ume Operation No Connection Pattern 2 May be used for connection with a fire sensor Run Stop A C Enable Disable remote control Pattern 3 Run Stop Pattern 4 Pulse signal control Note Refer to page 12 13 for PCB DIP s w settings when using the DI external signal control ...

Page 24: ...rnal control over the internet 2 Please consult the network administrator when deciding the DMS IP address Must consult for firewall issues DMS Computer HUB Direct Cable Public IP SNET i Cross Cable Private IP 192 168 0 2 Private IP 192 168 0 1 DMS Computer Cross Cable Private IP 192 168 0 2 Private IP 192 168 0 1 AseparateLANCardisneededifthe userwantstousethecomputerto accessboththeinternetandth...

Page 25: ... IP address assigned by the internet service provider that changes every time the computer connects to the internet Private IP The internet cannot be accessed using a private IP unless a HUB or an internet sharing program is used However if a private IP is used the computer or the DMS cannot be accessed from the internet There are three blocks of private IP addresses 10 0 0 0 through 10 255 255 25...

Page 26: ...e and when they are connected on the same network the IP address of the DMS will collide Please set the network environment of the DMS one at a time and connect all the DMS once all the IP addresses are set differently Computer The computer will not know which DMS has the IP address 192 168 0 2 DMS 1 Initial IP 192 168 0 2 DMS 2 Initial IP 192 168 0 2 DMS 3 Initial IP 192 168 0 2 DMS 4 Initial IP ...

Page 27: ... on the right side of the 7 segment display Only d is displayed on the right side of the 7 Segment display The 7 Segment display of the transmitter is as follow Left The main address of the indoor units are displayed if the communication is normal Right The RMC address of the indoor units are displayed followed by the following alphabets d Displayed when waiting for communication with the centrali...

Page 28: ......

Reviews: