background image

Instruction Manual 

120V Model 

2kVA, 3kVA

 

Uninterruptible Power Supply

 

 
 

 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

M0008068 

Summary of Contents for A11H

Page 1: ...Instruction Manual 120V Model 2kVA 3kVA Uninterruptible Power Supply M0008068...

Page 2: ...ons 7 4 Checking the Contents of the Package 8 5 External Dimensions and Part Names 9 5 1 Front and Back Panels of UPS 9 5 2 Control Panel and Indicators 10 5 3 External Interfaces 11 6 Wiring 15 6 1...

Page 3: ...Remote Switch 51 18 2 Linked Operation Cable 52 18 2 1 Wiring and Settings for Linked Operation 53 18 2 2 Linked Operation ON Procedure 54 18 2 3 Linked Operation OFF Procedure 54 18 2 4 Linked Operat...

Page 4: ...ct the load devices page 25 Start up the UPS page 29 Turn the load device power on page 30 Charge the UPS page 22 Check the UPS daily by user page 37 UPS is malfunctioning battery needs to be replaced...

Page 5: ...lanation DANGER Denotes immediate hazards which WILL probably cause severe bodily injury or death as a result incorrect operation CAUTION Denotes hazards which COULD cause bodily injury and product or...

Page 6: ...l temperature of the UPS rises which could cause battery deterioration resulting in a fire For maintenance the UPS requires at least 1 m 40 inches space at the front and 50 cm 20 inches at the back Th...

Page 7: ...ne other than qualified service personnel All such repairs and modifications will void the warranty CAUTION The following table shows the UPS states resulting from operation of the MAIN MCCB breaker a...

Page 8: ...g Contact with any part of a grounded battery can result in electric shock Do not attempt to open or disassemble batteries The electrolyte is harmful to the skin and eyes The battery contains diluted...

Page 9: ...eaker A11H202U011TW A11H202U111TW 1 8kVA 20A A11H302U011TW A11H302U111TW 2 7kVA 30A UL standard 2 2 Protect branch circuits by using the breaker of the specified capacity on distribution panels To mee...

Page 10: ...environment subject to long and frequent power outages more than once a week the batteries may not receive sufficient charge which could result in foreshortened battery life and premature battery fai...

Page 11: ...s s o of f t th he e P Pa ac ck ka ag ge e After opening the package carton check to be sure that it contains all of the following items Are UPS and all accessories in Is there no visible damage on th...

Page 12: ...r control software Card interface CARD I F Connector for the Optional interface card 2 Option card slot OPTION CARD Optional interface card 2 slot External control terminals AUX OUTPUT Connect an opti...

Page 13: ...1 LOAD O L Overload display Load 105 or more Load under 105 ALARM Alarm Failure detected No failure ON OFF Operation status Output power supply OFF Power supply bypassing During ON OFF delay operation...

Page 14: ...on For more information about the power management software see 16 How to Use Power Management Software or the User Guide on the supplied CD ROM 2 Interface setting Standalone Select this setting when...

Page 15: ...fault occurs in the UPS main unit Active transistor conduction state External transmission signal electrical characteristics Interface Transistor open collector output Maximum rating DC 35V 100mA Nor...

Page 16: ...in the User Settings Guide for details on the setting procedure REMOTE connector terminal names External view There are 2 REMOTE connectors each with the same functions For remote control of one UPS u...

Page 17: ...cy Power Off of UPS output When the switch is pressed in an emergency the EPO terminals are shorted and UPS output stops For details see 18 7 Connecting the Emergency Power Off EPO Terminals The switc...

Page 18: ...try to force it Doing so can damage the connector and result in electric shock Be careful not to get your hands caught when securing the cover Proceed as follows to connect the battery connectors insi...

Page 19: ...into the slots and press it down until you hear a click sound Secure with the screws Place the front cover over the battery cover and press it down The connector cannot be inserted in the wrong orien...

Page 20: ...ions in 16 How to Use Power Management Software and 18 Using Optional Equipment and the instruction manual supplied with the optional equipment Contact your supplier or a SANYO DENKI representative fo...

Page 21: ...ace where the UPS input power plug cannot be grounded Proceed as follows to connect the input power plug of the UPS Check that MAIN MCCB is in the OFF position Connect the input power plug of the UPS...

Page 22: ...es wiring of A11H302U 11TW To 3 prong grounded utility power outlet Connect as shown below Model Plug shape Note A11H302U011 A11H302U111 NEMA TYPE L5 30P seen from prong side When the AC input power i...

Page 23: ...e simulation test page 23 Start up the UPS page 29 The backup function is available during power outage Test result OK Test result NG See If power outage simulation test does not finish properly check...

Page 24: ...nu List to check the setting value The factory default settings of the UPS are indicated by the mark in the Default Setting column in the Setup Menu List When the load specification requirement or you...

Page 25: ...r at least 24 hours 2 The UPS should be charged for at least 24 or 36 hours to ensure backup in the event of a power outage but load devices can be connected for use when the UPS is first activated ev...

Page 26: ...d in steps and MCCB Hold for 1 second Set MAIN MCCB on the back panel of the UPS to ON Set MAIN MCCB to OFF Step and are not necessary if the procedure in 8 2 UPS Charge was performed beforehand Tip P...

Page 27: ...tion Green OUTPUT does not light Press and hold for 1 second See the step in 8 3 Outage Simulation Test Red ALARM lights Contact your supplier Contact your supplier or SANYO DENKI when the Red ALARM l...

Page 28: ...ed 3 0 kVA 2 1 kW If the load devices are a single wire grounded connection always connect the ground phase to the W terminal V phase side Never connect the following types of load devices to the UPS...

Page 29: ...installation environment Ambient temperature 0 to 40 C 32 to 104 F Relative humidity 20 to 90 Do not install the UPS in the following locations Where the ambient temperature exceeds 40 C 104 F Where...

Page 30: ...Check that the input breaker MAIN MCCB is set to OFF Check that load devices are connected correctly Rear View Rear View MCCB BATT MCCB is ON Attach the cover using two screws BYPASS OC is set to ON O...

Page 31: ...ht when installing the stand Proceed as follows to fix the UPS on the floor Prepare two floor fixation plates supplied Prepare four suitable anchor bolts to fix the UPS on the floor The anchor bolts a...

Page 32: ...e battery charge level MCCB Hold for 1 second Set MAIN MCCB on the back panel of the UPS to ON Press and hold for at least 1 second Buzzer Musical trill LEDs Green ON OFF Lit Green OUTPUT Lit Green IN...

Page 33: ...devices if needed See 3 3 Setting Output Frequency in the User Settings Guide for details However the setting cannot be changed if MAIN MCCB is not set to ON so preset this setting when there is a no...

Page 34: ...d devices prior to shutting down the UPS Operation varies depending on the user setting of Shutdown operation See 3 8 Setting UPS Shutdown Operation in the User Settings Guide for details Hold for 1 s...

Page 35: ...n operation See 3 8 Setting UPS Shutdown Operation in the User Settings Guide for details MCCB Hold for 1 second If input power is shut off while the UPS is operating the batteries are discharged as i...

Page 36: ...etting Remarks 1 4 3 1 Output voltage 120V 1 3 2 5 3 2 Frequency sync range RESTART 5 When you change the setting of the menus indicated by RESTART in the Menu column its changes do not take effect un...

Page 37: ...the UPS power supply Auto return Auto recovery when a certain period of time has elapsed 9 12 3 9 Overload recovery operation Bypass Fixed as bypass power supply on overload Set the UPS operation afte...

Page 38: ...nutes 23 26 3 23 Outlet box OUTPUT2 OFF delay time 5 minutes Set the OFF delay times for the OUTPUT1 and OUTPUT2 terminals of the outlet box The delay times are not enabled unless item 3 19 Enabling a...

Page 39: ...not replaced at the end of the service life the UPS may not function properly There are routine checks to be performed by the user and maintenance to be performed by service personnel Some maintenanc...

Page 40: ...back of the UPS If the air intake or exhaust vent is blocked the internal temperature of the UPS rises which could result in a damage of the UPS See 10 1 2 Installation Space Check Remove any dust or...

Page 41: ...g the battery early is recommended Contact SANYO DENKI The Green BATT TEST indicator goes off and returns to its normal indication Hold for 2 seconds Press and hold it for at least 2 seconds After the...

Page 42: ...ere are neither a problem nor a trouble in the equipment of the load Set BYPASS OC to ON Set MAIN MCCB to ON and then start the UPS by pressing and holding it for 1 second For details about UPS startu...

Page 43: ...ible because the UPS will be unable to provide backup power in the event of a power outage CAUTION The battery pack weighs about 12kg 26 46lbs A11H202U 18kg 39 68lbs A11H302U Be careful not to drop it...

Page 44: ...them in their original cartons and send them to your supplier An extra charge is required Note on the used battery Forced Bypass switch should be inverter position Place the front cover over the batt...

Page 45: ...check Wait for the battery check to end You can stop the battery check by pressing and holding it for at least 2 seconds Continuous beeps Red BATT LOW lit The battery voltage is low Verify that the i...

Page 46: ...and input frequency are within the rated range See 19 4 Specifications No output power is supplied from the output terminals of the UPS Red ALARM lit The bypass breaker may be tripped See 13 3 Bypass...

Page 47: ...ive Input voltage or input frequency is out of range Shutdown under remote control is in progress UPS is defective When using the power management software serial communication fails Check that Interf...

Page 48: ...TWARE STANDALONE from the Windows Start menu to set up The following is the minimum system configuration required for the setup and operation of the SANUPS SOFTWARE STANDALONE Computer AT compatible C...

Page 49: ...nector correctly If the UPS is operated without the batteries Charge might show a value lower than the actual charge rate Moreover even if the battery connector is reconnected and operates the UPS the...

Page 50: ...he UPS Characteristics section D Remote UPS Shutdown When this check box is checked the UPS shuts down 2 minutes after commencement of the OS shutdown A Registry setting change is required to change t...

Page 51: ...then click Finish Select the Positive option before clearing the check from the UPS Shutdown check box No Item Description A Power Fail On Battery Specifies that a warning message should be displayed...

Page 52: ...number of minutes that should elapse after a power failure until the OS shutdown begins The minimum time is 2 minutes The OS shutdown begins after the specified time or after the battery power becomes...

Page 53: ...completely stopped If you need to connect optional equipment after operating the UPS completely stop the UPS and connected loads and disconnect their input power plugs from utility power sockets Fail...

Page 54: ...setting for the function you want to use See 3 4 Setting PC Interface in the User Settings Guide for details on the setting procedure 1 To perform UPS remote ON OFF Set the Interface to Standalone 2 T...

Page 55: ...wer ON and OFF for all load systems connected to the UPS units in one operation You can also set the ON OFF times for each UPS separately allowing you to start and stop them in sequence The following...

Page 56: ...panels to ON Set the Interface item in the user setting menu according to the procedure in 3 4 Setting PC Interface in the User Settings Guide The following two functions are available depending on th...

Page 57: ...ation OFF delay sequence Be sure to keep the remote switch button pressed for at least 2 seconds Note Linked operation starts or stops on an ON OFF operation on the remote switch It does not start or...

Page 58: ...s ON 2 You can use user setting 3 10 UPS Operation at OFF in the User Settings Guide to select whether UPS power supply after the UPS stops is OFF or Bypass When you select Bypass UPS output after the...

Page 59: ...led by output line control and OUTPUT0 which is direct output from the UPS The user settings menu allows you to set separate ON OFF delay times for OUTPUT1 and OUTPUT2 This makes it possible to start...

Page 60: ...ol items 3 20 to 3 26 in the User Settings Guide Set MAIN MCCB to OFF check that the UPS is completely stopped and then set MAIN MCCB to ON again to restart the UPS The setting of 3 19 Enabling and Di...

Page 61: ...OFTWARE allows the delay times of OUTPUT1 and OUTPUT2 to be set to user specified values When using an outlet box and the SANUPS SOFTWARE power management software user setting menu items 3 20 to 3 26...

Page 62: ...ply may continue when OUTPUT1 and 2 are OFF because of power management software control or another reason In this state when the ON button is pressed on a remote switch linked operation ON delay time...

Page 63: ...lot on the back panel of the UPS Using the LAN interface card communications cable connect the CARD I F connector of the UPS to the UPS connector of the LAN interface card Set the Interface setting to...

Page 64: ...Supplied with contact interface card The following signals are output Signal name Description AC input error This signal is output on a utility power outage or voltage error a contact b contact Batte...

Page 65: ...or similar tool insert the wire into the terminal Pull the inserted wire to make sure it does not come out Depress lever with flat blade screwdriver to insert or remove wire Circuit voltage DC 5 V Cur...

Page 66: ...he battery voltage reaches the final discharge level a protective circuit shuts off the inverter to prevent over discharging of the batteries When normal utility power recovers after the inverter has...

Page 67: ...l switch to bypass supply Input over voltage Battery operation Input over voltage prolonged Battery operation 3 Power outage Battery operation Power outage prolonged Battery operation 3 Input error fr...

Page 68: ...Output Overload capability Bypass 800 2 cycles Type Small sealed lead battery Number 8 12 10 15 12V per battery Rated capacity 136W 2 parallel 136W 3 parallel 170W 2 parallel 170W 3 parallel 15 minut...

Page 69: ...es not apply to failures due to accidents improper use or use for other than the product s intended use 9 This warranty does not apply to defects or damages arising from fire earthquake storm or flood...

Page 70: ...Blank page...

Page 71: ...Blank page...

Page 72: ......