background image

 

 

M0009239 

 

 

 
 
 
 
 
 
 
 
 
 

TYPE

 

S2  

5, 10, 15, 20 kVA

 

Instruction

 

Manual

 

 

Summary of Contents for A11J S2

Page 1: ...M0009239 TYPE S2 5 10 15 20 kVA Instruction Manual...

Page 2: ...emperature 0 to 40 C 32 to 104 F 1 UPS is an abbreviation for Uninterruptible Power Supply Table of Contents 1 Before Use 1 2 Safety Precautions 2 3 For Proper Operation 6 3 1 UPS Input Power Supply 6...

Page 3: ...sing UPS Unit Control Panel 30 9 Inspection and Maintenance 31 9 1 Routine Checks by Customer 32 9 2 Battery Test 32 9 3 Resetting Main Breaker 33 10 Buzzer Sounds 34 11 Troubleshooting 35 12 UPS Char...

Page 4: ...page 8 Install the UPS pages 15 to 16 Check and set the settings of the LCD panel setting menu page 23 LCD Panel Operating Manual Start the UPS page 27 Turn on the power of the load devices page 28 C...

Page 5: ...ily injury and product or property damage as a result of incorrect operation Additionally even those hazards denoted by CAUTION could lead to a serious accident so the instructions should be strictly...

Page 6: ...ion resulting in a fire For maintenance the UPS requires at least 1 m 40 inches of space at the front and at least 50 cm 20 inches at the back The space around the UPS must be ventilated The table on...

Page 7: ...result in electric shock or other accidents when performed by anyone other than qualified service personnel All such repairs and modifications will void the warranty CAUTION Check the load side safet...

Page 8: ...of grounding Contact with any part of a grounded battery can result in electric shock Do not attempt to open or disassemble batteries The electrolyte is harmful to the skin and eyes The battery contai...

Page 9: ...set to automatically detect the AC input frequency 50 or 60 Hz 3 The input branch circuit breaker should be compliant with UL489 of the branch circuit protection 2 The UPS input should be connected t...

Page 10: ...ult in foreshortened battery life and premature battery failure 4 If the UPS is stored without being operated for a long period the batteries may require recharging If the batteries in the UPS are lef...

Page 11: ...maged or unusual Check and place a mark in If any item is missing or unusual contact your supplier or SANYO DENKI Note on transferring or selling the UPS This is an image The actual shapes of the UPS...

Page 12: ...ut power ground and load devices External interfaces See 5 4 Interfaces for connecting external devices Extension battery connector EXT BATTERY For connecting extension Battery 2 Option card slot OPTI...

Page 13: ...ept LCD display items or contents ITEM key ITEM Switches LCD display items or contents BACK key BACK Cancels the selection and returns to previous LCD display menu level HOME key BUZZER STOP HOME Retu...

Page 14: ...5 3 3 U UP PS S U Un ni it t C Co on nt tr ro ol l P Pa an ne el l No Name Label Color Function Lit When input power is normal Input LED INPUT Green Blinking When input power is abnormal Lit When sup...

Page 15: ...O DENKI 2 Interface setting Standalone standalone Use the standard UPS service function of the operating system NetWare Windows NT etc to shut down the UPS automatically Signal Names External Appearan...

Page 16: ...a power outage Current flows at approximately 5 mA when the power is on This is enabled when the interface is set to Standalone For the setting procedure see 3 5 Setting PC Interface in the LCD Panel...

Page 17: ...Also the remote ON function cannot be enabled in the event of an emergency stop when the EPO terminals are in a short circuited state To resume operation of the UPS release the emergency output stop...

Page 18: ...not drop it Failure to do so may result in bodily injury or damage to the UPS 6 6 1 1 1 1 C Ch he ec ck ki in ng g I In ns st ta al ll la at ti io on n E En nv vi ir ro on nm me en nt t Suitable insta...

Page 19: ...The LCD panel is secured by magnets but also secure it with the screws A in two places if there is the risk of it falling off Insert one end of the LCD panel connection cable into the connector at th...

Page 20: ...U IF of the power distribution unit and the UPS unit on the very bottom with the PDU interface cable Connect INPUT of the UPS units and INPUT of the power distribution unit INPUT INPUT OUTPUT INPUT EX...

Page 21: ...that all of the cables are connected securely Attach the cable covers to all of the UPS units and the power distribution unit Insert the tabs Insert the tabs at the bottom and secure the top in the t...

Page 22: ...pper cover of the terminal block cover as shown below Install a conduit in the hole of the terminal block cover Prepare the conduit by customer s self Attach the terminal block cover using four screws...

Page 23: ...he ground phase to N phase side Notes on wiring terminal block Do not connect the following types of load device to the UPS Load Devices Reason Laser printers plain paper fax machines copy machines ov...

Page 24: ...ard REMOTE EPO Terminal Connection Method Connect and use for example a switch or a contact of the customer s system that matches the terminal specifications For details on the functions of the termin...

Page 25: ...Installation and Wiring 22 Blank page...

Page 26: ...n the LCD panel Set MAIN MCCB on all UPS units to OFF Set MAIN MCCB to OFF When MAIN MCCB is set to ON Total Unit Err is displayed on the LCD screen and the buzzer makes a beep sound continuous tone T...

Page 27: ...the extension battery See the instruction manual of the extension battery Check that Green Input has changed from blinking to always on Set MAIN MCCB on the front of all UPS units to ON Operate the U...

Page 28: ...ck Cancel ONLINE The screen changes after approx 1 sec INV ON Control OK 3 2 STANDBY Green Lit Green Lit Red Off Green Lit Green Off Red Off ONLINE Green Blinking Lit Green Off Red Off SANYO DENKI SAN...

Page 29: ...ables properly 6 3 Connection Between Units Is Green OUTPUT off Perform the ON operation properly Steps 2 and 3 of 7 3 Power Outage Simulation Test Are Red ALARM and Red WARNING light Contact your sup...

Page 30: ...PS A11J STANDBY Vi Fi After approx 5 sec Green Off Set MAIN MCCB on all UPS units to ON The state of the LEDs of all UPS units becomes the same Breakers are displayed enclosed in like MAIN MCCB and LE...

Page 31: ...devices connected to the UPS exceed the rated capacity of the UPS Reduce the number of connected load devices If this state persists even after reducing the load devices to the rated capacity or less...

Page 32: ...OFF If MAIN MCCB is set to OFF while the UPS is operating the batteries are discharged as if a power outage occurred Be aware that when the input supply is restored the full capacity of the backup fun...

Page 33: ...U Un ni it t C Co on nt tr ro ol l P Pa an ne el l You can use the UPS unit control panel on the right side of the front of the UPS unit to start up and shut down the UPS The UPS unit control panel c...

Page 34: ...e checks to be performed by the user and maintenance to be performed by a service technician Some maintenance items are not able to be performed by the user so be sure to submit a request for such wor...

Page 35: ...When the UPS is shipped from the factory it is set up to perform an automatic battery test once every 180 days If you changed the setting for the schedule of the automatic battery test in 3 14 of the...

Page 36: ...ed the power supply may stop Follow the procedure below to reset the breaker Check that there is no abnormality with the connected load devices and reduce the load capacity Set the tripped MAIN MCCB o...

Page 37: ...ions Are all MAIN MCCB set to OFF If they are set to OFF set them to ON 2 seconds 2 beeps 2 beeps Test Condition Testing The UPS is performing a battery test Wait for the battery test to end To stop t...

Page 38: ...input frequency are within the rated ranges See 12 4 Specifications Was the startup operation performed in accordance with the correct procedure See 8 1 UPS Startup and check the correct operating pr...

Page 39: ...city of the batteries may be low Sufficiently charge the UPS The buzzer sounded The alarm buzzer sounds when a state change warning or error occurs in the UPS See 10 Buzzer Sounds The buzzer does not...

Page 40: ...management software option serial communication fails Is Interface in the LCD panel setting menu set to WS workstation See 3 5 Setting PC Interface in the LCD Panel Operating Manual The default setti...

Page 41: ...tion Upon Power Recovery in the LCD panel setting menu is set to STOP inverter output remains stopped 1 12 2 2 2 P Pr ro ot te ec ct ti iv ve e F Fu un nc ct ti io on ns s 1 Overload protection If the...

Page 42: ...Prolonged battery voltage drop BATTERY Power Outage BATTERY Power Outage Prolonged battery voltage drop BATTERY Input Error Frequency BATTERY Input Error Prolonged battery voltage drop BATTERY Stop r...

Page 43: ...actor 0 9 At 25 C 77 F ambient temperature initial value 6 Batteries Expected service life 5 years At 25 C 77 F ambient temperature Generated heat 350 W 730 W 1100 W 1500 W During rated output Input l...

Page 44: ...es not apply to failures due to accidents improper use or use for other than the product s intended use 9 This warranty does not apply to defects or damages arising from fire earthquake storm or flood...