Lithium-ion Battery UPS

Ver. 

3

Summary of Contents for S-A11KL102B0013SSN00

Page 1: ...Lithium ion Battery UPS Ver 3 ...

Page 2: ...TSN00 2 500 min 550 min S A11KL152B0500TSN00 p 13 p 15 600 min 660 min S A11KL152B0600TSN00 2 1 6 15 min 16 min Outlet terminal block S A11KL202B0015SS 00 1 p 5 p 8 3 2 4 9 min 10 min Outlet terminal block S A11KL302B0009SS 00 1 p 7 p 9 19 min 20 min S A11KL302B0019SS 00 1 50 min 55 min S A11KL302B0050TS 00 1 p 13 pp 16 18 100 min 110 min S A11KL302B0100TS 00 2 150 min 165 min S A11KL302B0150TS 00...

Page 3: ...th a backup time of 19 minutes or less Wide Input Range Easy Maintenance Wide OperatingTemperature Range Compatible with High Power Factor Loads Reduced Maintenance Work Space Saving Easy and Reliable Sequential System Start and Stop 1 Conventional UPS A11K with lead acid batteries 2 At 30 C ambient temperature Settings can be done with an outlet box it comes built in for 1 and 1 5 kVA models and ...

Page 4: ...1 8 m Output Outlet NEMA L5 30 Output Outlet Breaker For NEMA 5 15 Output Outlet NEMA 5 15 Optional Card Slot Menu Operation Buttons Inverter ON STANDBY Button LCD Panel Warning LED Output LED Backup Time LED Input Power LED LCD Screen Sliding Button Cover Opened slides up down 1 1 5 2 kVA Front View LCD Panel Battery backup time Battery backup time 8to 19min Note The photos above may look differe...

Page 5: ... Operation using a dedicated connection cable Auxiliary port Output Line Control contact 6 Dry contact Optional dry contact interface card is required Network support Optional LAN interface card is required Acoustic noise During normal operation 41 dB 45 dB 45 dB During battery operation or at a temperature above 40 C 51 dB 51 dB 51 dB Heat dissipation At rated operation after battery charging com...

Page 6: ...lides up down Note The photos above may look different from the actual products in the printed text etc 3 kVA Front View LCD Panel 5 kVA Rear View 5 kVA Front View PC Port RS 232C Main Breaker Bypass Breaker Output Line Control and Remote Ports Maintenance Bypass Breaker Output Outlet Breaker For NEMA 5 15 Optional Card Slot Optional Card Interface Output Outlet NEMA 5 15 I O Terminal Block LCD Pa...

Page 7: ...liary port Output Line Control contact 6 Dry contact Optional dry contact interface card is required Network support Optional LAN interface card is required Acoustic noise During normal operation 46 dB 46 dB During battery operation or at a temperature above 40 C 55 dB 55 dB Heat dissipation At rated operation after battery charging completed 254 W 421 W Input leakage current 3 5 mA 3 5 mA Operati...

Page 8: ...ated operation after battery charging completed 82 W 127 W 127 W 153 W Input leakage current 3 mA 3 mA 3 mA 3 mA Operating environment Ambient temperature 20 to 55 C 3 humidity 10 to 90 RH non condensing Dimensions 4 Unit mm Drawing Fig 1 Fig 1 Fig 1 Fig 1 W 435 435 435 435 H 86 2U 86 2U 86 2U 86 2U D 440 488 625 625 Mass 17 kg 18 kg 27 kg 27 kg 1 Vertical rack mount convertible 2 At a 25 C ambien...

Page 9: ... outlet NEMA L5 30R 1 or M5 terminal NEMA 5 15R 2 15 A each NEMA L5 30R 1 or M5 terminal NEMA 5 15R 2 15 A each M5 terminal NEMA 5 15R 2 15 A each Acoustic noise During normal operation 46 dB 46 dB 46 dB During battery operation or at a temperature above 40 C 55 dB 55 dB 55 dB Heat dissipation At rated operation after battery charging completed 254 W 254 W 421 W Input leakage current 3 5 mA 3 5 mA...

Page 10: ... min 15 min 8 min 10 min After 10 years 5 11 min 12 min 6 min 8 min Battery self test Can be enabled Factory setting disabled Interface PC port RS 232C Remote port Remote ON OFF switch can control up to 5 UPS units in Linked Operation using a dedicated connection cable Dry contact Optional dry contact interface card is required Network support Optional LAN interface card is required Acoustic noise...

Page 11: ...dB 51 dB Heat dissipation At rated operation after battery charging completed 82 W 127 W Input leakage current 3 mA 3 mA Operating environment Ambient temperature 20 to 55 C 3 humidity 10 to 90 RH non condensing Dimensions 4 Unit mm Drawing Fig 1 Fig 1 W 435 435 H 86 2U 86 2U D 440 488 Mass 16 kg 17 kg 1 Vertical rack mount convertible 2 At 25 C ambient temperature and load power factor of 0 8 usi...

Page 12: ...it Battery Unit Optional Card Slot 3 kVATerminal BlockType Rear View Same as above model except for the part shown below UPS Unit Maintenance Bypass Breaker Main Breaker Bypass Breaker Optional Card Slot Output Outlet Breaker For NEMA 5 15 Output Outlet NEMA 5 15 I O Terminal Block Note The photos above may look different from the actual products in the printed text etc 5 kVA Rear View I O Termina...

Page 13: ...as the input rated frequency Frequency regulation During grid operation Within 1 3 5 or 7 of the rated frequency User selectable Factory setting 3 During battery operation Within 0 5 of rated frequency Output waveform Pure sine wave Voltage harmonic distortion At linear load 3 or less At rated output At rectifier load 7 or less At rated output Load power factor Rated 0 8 lagging Variation range 0 ...

Page 14: ...ype UPS unit dimensions 4 Unit mm Drawing Fig 2 W 435 H1 86 2U D 488 Mass 14 kg Rack mount type Battery unit dimensions 4 Unit mm Drawing Fig 3 1 Fig 3 2 Fig 3 3 Fig 3 4 W 435 435 435 435 H2 175 4U 175 2 8U 175 3 12U 175 4 16U D 520 520 520 520 Mass 52 kg 52 kg 2 52 kg 3 52 kg 4 1 Vertical rack mount convertible 2 At 25 C ambient temperature and load power factor of 0 8 using new fully charged bat...

Page 15: ...ation after battery charging completed 127 W Input leakage current 3 mA or less Operating environment Ambient temperature 20 to 55 C 2 humidity 10 to 90 RH non condensing Free standing type Dimensions 3 Unit mm Drawing Fig 7 Fig 8 W 435 435 435 65 H 1066 716 D 520 520 Mass 286 kg 184 170 kg Rack mount type UPS unit dimensions 3 Unit mm Drawing W H1 D Mass Rack mount type Battery unit dimensions 3 ...

Page 16: ... type UPS unit dimensions 4 Unit mm Drawing Fig 2 W 435 H1 131 3U D 520 Mass 22 kg Rack mount type Battery unit dimensions 4 Unit mm Drawing Fig 3 1 Fig 3 2 Fig 3 3 Fig 3 4 W 435 435 435 435 H2 175 4U 175 2 8U 175 3 12U 175 4 16U D 520 520 520 520 Mass 52 kg 52 kg 2 52 kg 3 52 kg 4 1 Vertical rack mount convertible 2 At 25 C ambient temperature and load power factor of 0 8 using new fully charged ...

Page 17: ...dissipation At rated operation after battery charging completed 254 W Input leakage current 3 5 mA or less Operating environment Ambient temperature 20 to 55 C 2 humidity 10 to 90 RH non condensing Free standing type Dimensions 3 Unit mm Drawing Fig 7 Fig 8 W 435 435 435 65 H 1111 761 D 520 520 Mass 294 kg 192 170 kg Rack mount type UPS unit dimensions 3 Unit mm Drawing W H1 D Mass Rack mount type...

Page 18: ...5 435 435 435 H 435 586 761 936 D 520 520 520 520 Mass 74 kg 132 kg 184 kg 236 kg Rack mount type UPS unit dimensions 4 Unit mm Drawing Fig 2 W 435 H1 131 3U D 520 Mass 22 kg Rack mount type Battery unit dimensions 4 Unit mm Drawing Fig 3 1 Fig 3 2 Fig 3 3 Fig 3 4 W 435 435 435 435 H2 175 4U 175 2 8U 175 3 12U 175 4 16U D 520 520 520 520 Mass 52 kg 52 kg 2 52 kg 3 52 kg 4 1 Vertical rack mount con...

Page 19: ...t rated operation after battery charging completed 254 W Input leakage current 3 5 mA or less Operating environment Ambient temperature 20 to 55 C 2 humidity 10 to 90 RH non condensing Free standing type Dimensions 3 Unit mm Drawing Fig 7 Fig 8 W 435 435 435 65 H 1111 761 D 520 520 Mass 294 kg 192 170 kg Rack mount type UPS unit dimensions 3 Unit mm Drawing W H1 D Mass Rack mount type Battery unit...

Page 20: ... W 175 175 435 435 H 435 630 805 D 520 520 520 Mass 82 kg 140 kg 192 kg Rack mount type UPS unit dimensions 4 Unit mm Drawing Fig 2 W 435 H1 175 4U D 520 Mass 30 kg Rack mount type Battery unit dimensions 4 Unit mm Drawing Fig 3 1 Fig 3 2 Fig 3 3 W 435 435 435 H2 175 4U 175 2 8U 175 3 12U D 520 520 520 Mass 52 kg 52 kg 2 52 kg 3 1 Vertical rack mount convertible 2 At 25 C ambient temperature and l...

Page 21: ... mm Drawing Fig 1 Fig 4 Fig 5 W 435 435 435 435 65 H 980 1155 805 D 520 520 520 Mass 244 kg 302 kg 200 170 kg Rack mount type UPS unit dimensions 4 Unit mm Drawing Fig 2 W 435 H1 175 4U D 520 Mass 30 kg Rack mount type Battery unit dimensions 4 Unit mm Drawing Fig 3 4 W 435 H2 175 4 16U D 520 Mass 52 kg 4 1 Vertical rack mount convertible 2 At 25 C ambient temperature and load power factor of 0 8 ...

Page 22: ... min model 3 kVA 50 min model 5 kVA 30 min model 1 5 kVA 200 min model 3 kVA 100 min model 5 kVA 60 min model Load level Battery backup time min 100 80 60 40 20 10 40 30 20 10 80 90 70 100 110 0 60 50 1 5 kVA 8 min model 2 kVA 15 min model 1 kVA 13 min model 5 kVA 11 min model 3 kVA 9 min model 10 20 40 60 80 100 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 Load level Battery backu...

Page 23: ...ets via wired connection It can control up to 5 UPS units in Linked Operation requires optional Linked Operation cable Linked Operation cable P10911 For branching terminal connection between relay connector and lead wire P10912 Cable length 1 m between relay connector and lead wire P10913 Cable length 3 m between relay connector and lead wire A unit to unit cable for performing on off switching of...

Page 24: ...el Please contact us concerning the disposal of used storage batteries supplied by SANYO DENKI The products listed in this catalog fall into the category 16 of Appended Table 1 of the Export Trade Control Order To export the products as an individual part or to export a device into which the prod ucts are assembled the Inform Requirements and Objective Requirements that the Ministry of Economy Tra...