Overcurrent Elements 

Page 1 of 7 

20120723 

Hands-On Relay Testing Session 

Overcurrent Elements 

Exercise Objectives 

After completing this exercise, you should be able to do the following: 

 

Identify overcurrent element settings. 

 

Determine effective overcurrent protection settings. 

 

Validate relay settings. 

In this exercise, the instructor will introduce the SEL-387A Current Differential and Overcurrent Relay 
overcurrent elements, determine how to set the elements for transformer backup protection, and 
demonstrate how to enter the settings. 

You will then enter the overcurrent settings into 

AC

SEL

ERATOR

 QuickSet

®

 SEL-5030 Software. After 

sending your settings to the relay, you will validate the settings and verify the protection scheme. 

SEL-387A Time-Overcurrent Elements 

The SEL-387A provides numerous overcurrent elements, as many as 11 per winding and 5 per neutral 
input. Four levels of phase instantaneous or definite-time elements are available for overcurrent 
protection, breaker failure protection, overcurrent phase selection for targeting, transformer backup 
protection, and so on. Two levels of negative-sequence and residual instantaneous elements provide 
protection against unbalanced conditions and ground faults. Phase, negative-sequence, and residual time-
overcurrent elements are available for system backup protection. The SEL-387A also has neutral 
instantaneous or definite-time elements available. 

For a more detailed description of each of the overcurrent elements, refer to the SEL-387A Instruction 
Manual (available at http://www.selinc.com). 

Hands-On Activity 1: Enable Overcurrent Elements 

In this hands-on activity, you will enable the element for a particular winding and enter settings for 
backup overcurrent protection. Write your answers in the space provided. 

Transformer Data 

Rated 50 MVA 

Rated high side 161 kV (DAB) 

Rated low side 14.4 kV (wye) 

High-side bushing current transformer (CT) ratio (wye connected) 

Low-side bushing CT ratio (wye connected) 

Neutral bushing CT ratio 

Summary of Contents for SEL-387A

Page 1: ...instantaneous or definite time elements are available for overcurrent protection breaker failure protection overcurrent phase selection for targeting transformer backup protection and so on Two levels...

Page 2: ...Element Settings Step 2 Determine the Winding 1 Max Phase Time Overcurrent Trip Level setting 51P1P ________________ The transformer maximum expected load equals MVA 1000 kV 3 Set the 51P1 pickup to...

Page 3: ...5 Verify that the Neutral Inst Overcurrent Trip Delay 50NN1D is set at minimum value of 0 50 Step 6 Select Group 1 Set 1 Winding 2 Elements Figure 3 Phase Time Overcurrent Element Settings Step 7 Det...

Page 4: ...default values 51P2RS Y 51P2TC 1 Step 11 Save your settings and then send them to the relay Hands On Activity 2 Validate Overcurrent Elements In this hands on activity you will validate the phase and...

Page 5: ...le Relay Word bit asserts Step 1 Reset relay targets by pushing the TARGET RESET pushbutton located on the relay front panel Step 2 Clear the Sequential Events Recorder SER entries You can perform thi...

Page 6: ...minals to simulate faults as indicated in Table 1 Step 1 Calculate the expected operate time using the equations from Figure 5 and record your answers in Table 2 Figure 5 Time Overcurrent Operation Eq...

Page 7: ...rt command or the ACSELERATOR QuickSet HMI Step 3 After the instructor applies the fault current use the TARn serial port command n the Relay Word bit for the element under test or the ACSELERATOR Qui...