Power Consumption
4W Max
Operating Temperature
0 to
C
0
0
55
Storage Temperature
- 0 to 8 C
3
0
0
0
Humidity
95% RH
Certification
CE, UL (Pending)
Dimensions(WxHxD)mm
99 x 99 x 62.85
Panel Cutout(WxH)mm
92 x 92
Weight
275gms
selec
SP3-GT35
Operating Instructions
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
3.5" LCD with Touch
Built in Buzzer
10 password levels
Modbus protocol
Alarms
Recipe Management
Serial Printing
Data Logging
FEATURES
OP404-V01
Resolution
Backlight
320 x 240 pixels
LED backlight
SPECIFICATIONS
Display Type
Display Size(WxH)mm
3.5" TFT LCD (256 color), Resistive Touch Screen
70.08 x 52.56
selec
SP3-GT35
Font
16 MB (System Memory)
4 MB
BMP
Total
Application
4 MB
512 KB
Slave Port
Master Port
RS232 (MODBUS RTU)
RS485 (MODBUS RTU)
Brightness Adjustment
Yes (Via Internal MMI)
Keys
System key X 1, Function keys X 5
Operation Voltage
18 - 30VDC
Backup Battery
Battery Life
Buzzer
Type
Sound Output
Operation
Replaceable 3V CR2032
1 year at 25 C
0
Electro Magnetic Buzzer
85 dB at 10cm
Software Programmable
Printer Port
RS232 (LX300 Protocol)
LCDMODULE
COMMUNICA
TION
Doc. Name : OP INST SP3-GT35 OP404-V01(Page 1 of 2)B-B
Accuracy
+/- 10 min per Year
RealT
ime
Clock(RTC)
Upload
5.5 MB
External
Micro SD upto 2 GB (User Memory)
System Reserved
2 MB
MEMOR
Y
This manual is meant for personnel involved in wiring,
installation, operation and routine maintenance of the
equipment.
All safety related conditions, symbols and instructions
that appear in this operating manual or on the equipment
must be strictly followed to ensure operator and
instrument safety. Any misuse may impair the protection
provided by the equipment.
Read complete instructions prior to
installation and operation of the unit.
CAUTION :
SAFETY PRECAUTIONS
1. This equipment, being built-in-type, normally becomes
a part of the main control panel and the terminals do not
remain accessible to the user after installation.
2. Conductors must not come in contact with the internal
circuitry of the equipment else it may lead to a safety
hazard that may endanger life or cause electrical shock
to the operator.
3. Circuit breaker or mains switch must be installed
between the power source and supply terminals to
facilitate power 'ON' or ‘OFF' function.
4. The equipment shall not be installed in environmental
conditions other than those specified in this manual.
5. Since this equipment forms part of the main control
panel, its output terminals get connected to the host
equipment. Such equipment shall also comply to EMI /
EMC and safety requirements like CE standard
procedure.
6. Thermal dissipation of equipment is met through
ventilation holes provided on housing of equipment.
Obstruction of these ventilation holes may lead to a
safety hazard.
7. The output terminals shall be loaded strictly as per the
values / range specified by the manufacturer.
INSTALLATION INSTRUCTIONS
CAUTION
92
92
99
90.5
99
9
53
Side view
Front bezel
For installing the controller
1. Prepare the panel cutout with proper dimensions as
shown above.
2. Remove the clamp from the SMI.
3. Fix the unit into the cutout. Insert the clamp from both
sides and tighten the screws.
The equipment in its installed state must not come in
close proximity to any heating sources, caustic vapors,
oils, steam, or other unwanted process by products.
1. Use proper input power cables with shortest
connections and twisted type.
2. Layout of connecting cables shall be away from any
internal EMI source.
1. To avoid blockage of ventilation holes, clean the
equipment regularly using a soft cloth.
2. Do not use Isopropyl alcohol or any other organic
Solvents for cleaning.
EMC Guidelines :
MAINTENANCE
CAUTION
MECHANICAL INSTALLATION
Outline Dimensions
(in mm)
Panel Cutout
(in mm)
1. Wiring shall be done strictly according to the terminal
layout provided in the operating manual.
2. To eliminate electromagnetic interference use short
wire with adequate ratings and twists of equal size.
3. The power supply connection cable must have a cross
section of 1sq.mm or greater and insulation capacity of
at least 1.5KV.
WIRING INSTRUCTIONS
CAUTION
Internal