MI000692-E
ENGLISH - 1/4
EN
SELF POWERED CURRENT LOOP ISOLATOR
Z110S - 1 Channel
Z110D - 2 Channel
4 - 20 mA current input.
Retransmission of input as an isolated 4 - 20 mA output.
Input / output isolation 1500Vac.
Channel to channel isolation 1500Vac (2 channel model Z110D
only).
GENERAL SPECIFICATION
TECHNICAL SPECIFICATION
Self Powered from the input (primary) loop.
Power supply:
Input:
Output:
Operating Conditions:
Input measurement
error:
Response Time:
Input Protection:
Output Protection:
Standards:
Current: 4 - 20 mA
Minimum Volt Drop at 20mA: 7V (all loads up to 160ohm)
Maximum Volt Drop at 20mA 3.8V + (Load Resistance)*0.02V.
4 - 20 mA (active), max load resistance 500 ohm.
Temperature: 0~50°C, Humidity min:30%, max 90% @ 40°C,
non condensing.
Calibration
Error
0,1% off f.s.
0,1% off f.s. 0,1% off f.s.
Thermal
Coefficient
0,02% off f.s./°C
Linearity
error
Load variation
effect
<100 mS to reach 90% of final value.
Protected up to 35Vdc Max.
Protected up to 35Vdc Max.
This instrument meets or exceeds the requirements of
EN50081-2 (electromagnetic emissions, industrial
environment)
EN50082-2 (electromagnetic susceptibility, industrial
environment)
EN61010-1 (safety)