background image

MI000692-E

ENGLISH - 1/4

EN

SELF POWERED CURRENT LOOP ISOLATOR

Z110S - 1 Channel
Z110D - 2 Channel

4 - 20 mA current input.
Retransmission of input as an isolated  4 - 20 mA  output.
Input / output isolation  1500Vac.
Channel to channel isolation  1500Vac  (2 channel model Z110D 
only).

GENERAL SPECIFICATION

TECHNICAL SPECIFICATION

Self Powered from the input (primary) loop.

Power supply:

Input:

Output:

Operating Conditions:

Input measurement
error:

Response Time:

Input Protection:

Output Protection:

Standards:

Current: 4 - 20 mA
Minimum Volt Drop at 20mA: 7V (all loads up to 160ohm)
Maximum Volt Drop at 20mA 3.8V + (Load Resistance)*0.02V.

4 - 20 mA (active), max load resistance 500 ohm.

Temperature: 0~50°C, Humidity min:30%, max 90% @ 40°C, 
non condensing.

Calibration
Error

0,1% off f.s.

0,1% off f.s. 0,1% off f.s.

Thermal
Coefficient

0,02% off f.s./°C

Linearity 
error

Load variation
effect

<100 mS to reach 90% of final value.

Protected up to 35Vdc Max.

Protected up to 35Vdc Max.

This instrument meets or exceeds the requirements of
EN50081-2 (electromagnetic emissions, industrial 
environment)
EN50082-2 (electromagnetic susceptibility, industrial 
environment)
EN61010-1 (safety)

Reviews: