 CURRENT TRANSMITTER

 

5

  AAC

 or 10 A

AC full scale

 current input 

0

-

20 mA or 4

-

20 mA output with active or passive connection; 

0

-10 VDC, 

2

-

10

 VDC,

 0

-5 VDC, or 

1

-

VDC

 

S

ettable by internal jumper and 

DIP

-switch

High precision: 0.3

% FS

Power supply presence indication on front panel
3-

way isolation

: 4000 V

AC

 between power supply / input and output

GENERAL SPECIFICATIONS

The    Z201-H  current  converter  measures  the  simple  harmonic 
alternating current applied at the input and generates a standard mA or 
V signal directly proportional to the current measured.

BLOCK DIAGRAM

INPUT

OUTPUT

CAT III 300 V

TECHNICAL SPECIFICATIONS

Power Supply:

Consumption:

Current Input:

85

-

265 V

DC

 or 

VAC

 from 50 to 400

 

Hz; 

I

solation:

 input / output : 4000 V

AC

 

< 2 W at full load; < 20 mA @ 230 V

AC

Power Supply Specifications

Input Specifications 

Alternat

ing

 Current:   0

-

5  A

AC

  or   0

-10

 

AAC

,

S

electable  by terminal

 wiring

.

EN

9

8

7

1

3

Power supply

4

5

6

0 V

20 V

mA 

output

output

+

+

mA 

output

+

ext. supply

max 28 V

85

-

265 V

AC/DC

 50

 to 

400

 

Hz

Summary of Contents for Z201-H

Page 1: ...ent converter measures the simple harmonic alternating current applied at the input and generates a standard mA or V signal directly proportional to the current measured BLOCK DIAGRAM INPUT OUTPUT CAT III 300 V TECHNICAL SPECIFICATIONS Power Supply Consumption Current Input 85 265 VDC or VAC from 50 to 400 Hz Isolation input output 4000 VAC 2 W at full load 20 mA 230 VAC Power Supply Specification...

Page 2: ... variation max 100 ms from 10 to 90 Temperature 10 to 65 C humidy 30 95 40 C not condensing Group III Storage Temperature 20 to 85 C Altitude up to 2000 meters a s l Presence of power supply green IP20 140 g 100 x 112 x 17 5 mm 1 These acronyms apply om of measurement ots of the scale 2 Error caused by electromagnetic disturbances EMI 3 The precision values are indicated for a sinusoidal signal wi...

Page 3: ...NAL JUMPER POSITION OUTPUT SIGNAL SETTINGS The Z201 H instrument transmits a voltage or a current signal The output type voltage or current is set using the internal jumper accessible under the rear side of the the case The signal range is set using the double DIP switch SW1 Current or Voltage Output Selection Current Output F Voltage Output SW1 SW1 J1 J1 Output Range Settings Switch 1 Position Sc...

Page 4: ...tecollectionprograms Thissymbol foundonyour product oron itspackaging indicatesthat thisproductshould notbetreatedas household waste when you wish to dispose of it Instead it should be handed over to an applicable collection point for the recycling of electrical and electronic equipment By ensuring this product is disposed of correctly you will help prevent potential negative consequences to the e...

Reviews: