SNAPAK

®

MAGNETIC CIRCUIT PROTECTORS

Introduction

The SNAPAK® series is a snap-acting hydraulic-magnetic circuit protector that combines power switching and accurate, reliable circuit protection in 

one aesthetically pleasing package.  The SNAPAK® combines the functions of three separate components: power switch, fuse and fuse holder. To the 

OEM, this means that only one item has to be mounted instead of three. Less assembly is required, inventory is cut by two-thirds and greater panel 

density is obtainable with less clutter. In addition, the SNAPAK® can be operated at either DC or 50/60Hz, eliminating the need to specify, order and 

stock separate units. 400Hz units are also available.

To enhance front-panel aesthetics, SNAPAK® is offered with paddle and rocker handles in six attractive colors and push-pull and push-to-reset 

actuators. Also offered is a variety of optional mounting hardware. The push-pull version is supplied with a black button with a white indicating band.

Orientation of the button when marked with an amperage notation must be specified when using the fourth decision table. Push-to-reset is supplied 

with a contrasting color indicating shaft. In addition, SNAPAK® is offered in SPST and DPST configurations. The single pole satisfies most applications. 

The two-pole version is often used for extra safety in products that utilize high voltage or where current sensing and breaking of both sides of the line is 

required.  Quick connect terminals are standard, UNC 8-32 or M4 screw 

terminals are available as additional termination options.

Since the SNAPAK® is snap-acting, it assures immediate opening and 

closing of the contacts. Its design also prevents operator “teasing” of 

the contacts and minimizes arcing.SNAPAK® circuit protectors are 

UL Recognized as supplementary protectors per UL STD. 1077, CSA 

Certified as supplementary protectors per CSA STD. C22.2 No. 235, TUV 

Approved as circuit breakers for equipment per STD. EN 60934, CCC 

Approved (customer must request product be manufactured in China) 

and CE Compliant. In addition, most versions are certified by UL to meet 

spacing requirements of IEC 950 for basic and functional insulation for 

front panel mounting.  

Consult factory for details and exceptions. Typical applications include 

office appliances, electronic data processing, medical equipment, 

business machines, vending and amusement machines. Push-pull 

versions are particularly well suited for medical instrumentation, 

automotive production transfer lines and other applications where 

accidental turn off is unacceptable. For those applications which do not 

require circuit protection, SNAPAK® is offered in a power-switch-only 

configuration.

TOGGLE ACTUATORS

Mounting Tolerance ± .005 [.13] unless noted angles: ±5°. Dimensions in 

Brackets [ ] are millimeters

[12.70 ±       ]

.025

.000

.500 ±     

.010

.000

.355

[9.02]

.125

[3.18]

Mounting Details with Locking Ring

[12.70 ±       ]

.025

.000

.500 ±     

.010

.000

.222 ± 0.002

[5.64 ± 0.05]

PANEL CUTOUT SHOWN ABOVE

MAY BE MADE WITH GREENLEE

RADIO CHASSIS PUNCH #733 x 1/2” DIA.

without Locking Ring

The SNAPAK® is available with paddle handles 

in six attractive colors. Engineered for safe, sure 

operation, the paddle handles may be specified in

Summary of Contents for AIRPAX SNAPAK

Page 1: ...ck connect terminals are standard UNC 8 32 or M4 screw terminals are available as additional termination options Since the SNAPAK is snap acting it assures immediate opening and closing of the contacts Its design also prevents operator teasing of the contacts and minimizes arcing SNAPAK circuit protectors are UL Recognized as supplementary protectors per UL STD 1077 CSA Certified as supplementary ...

Page 2: ...030 12 70 0 76 1 2 32 THD 680 0 010 17 27 0 25 031 0 79 250 6 35 1 375 0 010 34 93 0 25 1 LINE 2 Single Pole Toggle 2 4 1 LINE LINE 3 POLE 1 POLE 2 15º 15º ON OFF FLAT 1 715 0 030 43 56 0 76 375 0 010 9 53 0 25 1 125 0 030 28 58 0 76 125 0 010 3 17 0 25 468 0 010 11 89 0 25 0 500 0 030 12 70 0 76 1 2 32 THD 625 0 010 15 88 0 25 031 0 79 250 6 35 1 375 0 010 34 93 0 25 1 304 0 010 33 12 0 25 Two Po...

Page 3: ...5 0 305 0 010 7 75 0 25 Handle Guards Single Pole Handle Guards Two Pole 1 047 0 010 26 60 0 25 0 305 0 010 7 75 0 25 0 093 0 010 2 36 0 25 0 625 0 010 15 88 0 25 0 125 0 010 3 18 0 25 0 030 0 325 8 26 0 76 1 304 0 010 33 12 0 25 0 031 0 79 0 250 6 35 1 840 0 030 46 74 0 76 0 375 0 010 9 53 0 25 1 125 0 030 28 58 0 76 1 375 0 010 34 93 0 25 0 972 0 010 24 69 0 25 1 560 0 010 39 62 0 25 0 400 0 010...

Page 4: ...010 33 12 0 25 9 53 025 000 375 010 000 162 0 002 4 11 0 05 0 76 0 030 OFF 6 35 0 25 FLUSH 0 030 ON FLUSH 0 25 Mounting Detail Single Pole and Two Pole Push to Reset Actuation Single and Two Pole Push Pull Single Pole 1 960 0 030 49 78 0 76 375 0 010 9 53 0 25 400 0 010 10 16 0 25 0 500 0 030 12 70 0 76 OFF SHOWN 0 250 0 030 6 35 0 76 ON WHITE BAND VISIBLE IN OFF POSITION ONLY 3 8 32 THD FLAT Push...

Page 5: ... protection for the critical load When the current through this load becomes excessive and reaches the trip point the protector will open and remove power from both loads simultaneously The current rating of both loads must not exceed the maximum contact rating Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the contacts The coil may ...

Page 6: ...rations Power Switch In the event that over current protection is not desired the coil mechanism can be deleted providing an excellent low cost single or double pole power switch Maximum current rating is 20 amps 2 4 1 LINE LINE 3 C N C N O 0 093 2 36 0 040 1 02 DIA HOLE FOR SOLDER ATTACHMENT 560 0 030 1 4 22 0 76 LOAD LINE BREAKER SHOW N IN OFF POSITION C NC NO LOAD LIN E BREAKER SHO WN IN OFF PO...

Page 7: ...RENT VS TRIP TIME IN SECONDS AT 25 C VERTICAL MOUNT Delay 100 135 150 200 400 600 800 Instant No Trip May Trip 100 Max 100 Max 100 Max 100 Max 100 Max Fast No Trip 3 to 7 2 to 5 1 to 2 03 to 50 015 to 30 010 to 150 Slow No Trip 3 to 70 2 to 40 1 to 15 10 to 4 0 015 to 2 0 010 to 800 PULSE TOLERANCE Delay Pulse Tolerance 1 2 61 62 9 Times Rated Current 3 4 61F 62F 13 Times Rated Current 400 Hz DC 5...

Page 8: ...between 40 C and 85 C Insulation Resistance Not less than 100 megohms at 500Vdc Dielectric Strength Withstands 1500 volts 60Hz for 60 seconds or 1800Vac for one second between all electrically isolated terminals Endurance Mechanical life in excess of 50 000 operations In manyapplications however contact wear due to the electrical load determines unit life At maximum electrical ratings the SNAPAK c...

Page 9: ...dress nuts are also available in a matte black finish Every SNAPAK comes with a hex nut but you may order the front panel nuts which will best enhance your design Miscellaneous Hardware SNAPAK circuit protectors with 1 2 32 thread may also be equipped with optional locking rings to prevent rotation of the unit after it is installed 3 8 32 Hex Nut and Panel Nuts The hardware will be supplied with e...

Page 10: ...ector S Screw Terminals Single pole 1 and series only 5th decision group V screw terminal option is required when 1st decision S is specified PR Push To Reset 2 Two Pole 3 Shunt Circuit Protector R Rocker 5 Two Pole 4 Relay Circuit Protector CR Rocker 5 Series w Silver Aux Switch CPP Push Pull 6 Series w Gold Aux Switch CPR Push to Reset 9 Mixed Construction 2 Pole Only UL CSA Construction Non UL ...

Page 11: ... number are now complete except if you require S screwterminal option from the 5th Decision Table Paddle T Handle Color 01 Black 02 Red 03 Yellow 04 Green 05 Blue 06 White If you have chosen a handle from this table your 4th Decision is now complete except for hardware options in 5th Decision Table Push Pull PP CPP and CPR XX XX No button markings desired not available for CPP CPR OA LINE 5 Marked...

Page 12: ...000 U1 1000 P R only 65 DC 1 10 10 7 5 U 2 500 U1 500 65 DC 2 10 10 15 U1 1000 65 DC 2 10 10 20 10 20 U2 500 U1 5005 00 65 2 D C 11 0 10 30 10 30 U2 120 120R PP PR only 65 2 D C 2 only 10 10 25 U1 100 R only 65 2 D C 21 0 10 25 U2 500 R only 125 50 60 11 10 10 20 7 6 20 U1 10005 00 125 50 60 11 10 10 30 3 U1 1000 T only 125 2 50 60 11 10 10 30 U2 1000 R PP PR only 125 2 50 60 11 11 10 30 20 1 30 U...

Page 13: ...IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL REGULATORY AND SAFETY RELATED REQUIREMENTS CONCERNING ITS PRODUCTS AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS NOTWITHSTANDING ANY APPLICATIONS RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA Mailing Address Sensata Technologies Inc 529 Pleasant Street Attleboro MA 02703 USA Revised 01 17 20 Notes A A neon bulb is provide...

Reviews: