background image

1 of 2

Acuity Brands | One Lithonia Way Conyers, GA 30012  Phone: 800.535.2465   www.acuitybrands.com   © 2020-2021 Acuity Brands Lighting, Inc.   All rights reserved.   Rev. 0

4

/

18

/202

2

 

912-00148-00

3

SPODMRA JOT

 

Dimming Switchpod

Installation Instructions

PROVISSIONING JOT SYSTEM APP-LESS

After JOT enabled luminaries and wall stations are installed and powered, locate 
the “pin hole” as shown below.

 

For app-free pairing, fixtures must be placed 

downstream from the wall switch.

Insert JOT tool then press / hold any front button for 6 seconds. Once LED begin 
blinking rapidly, remove tool from device. All branch circuit luminaries will power cycle 
and begin to self-pair one at a time indicated by a 10% dim state. Once all luminaries 
are paired, light level will transition from 10% to 100%.

WARNING

Only use pre-packaged JOT tool to start pairing process.

DO NOT INSERT METAL INTO PIN HOLE!

CONVERSION FROM GROUND ONLY

This product is pre-configured for wiring without a neutral; however, if connection to 
neutral is required by code, the unit easily converts in seconds

 by removing green sleeve

3-Way or (Multi-Way Application); similarly applies to neutral wiring

1

SPODMRA JOT

SPODMRA JOT

2

OPERATIONAL SETTINGS

JOT Tool must be inserted to perform any of the below operations. Press any button on 
the front of the switch to enter mode.

2 = Occupancy Time Delay 

The length of time an occupancy sensor will keep the lights on after it last detects 
occupancy.

1 - Test Mode**

6 - 10.0 min*

11 - 22.5 min

**Test mode sets Occupancy Time 

Delay to 30 seconds and increases 

photocell transition rate in addition 

to disabling the microphone on units 

with Dual Technology

2 - 30 sec

7 - 12.5 min

12 - 25.0 min

3 - 2.5 min

8 - 15.0 min

13 - 27.5 min 

4 - 5.0 min

9 - 17.5 min

14 - 30.0 min

5 - 7.5 min

10 - 20.0 min

Level of light output when occupancy 
is initially detected. Not applicable in 
Automatic Dimming Control (ADH) mode.

1 - 10%

4 - 40%  7 - 70%

10 - 100%*

2 - 20%

5 - 50%

8 - 80%

* DEFAULT 
SETTING

3 - 30%

6 - 60%

9 - 90%

3 = Start Level

OUTPUT RATING

 

120VAC, 800W, 6.7A

277VAC, 1200W, 4.3A 

347VAC, 1500W, 4.3A 

 

  SETTING CODE 6 (Join a Group)

   

  

SETTING CODE 7 (Accept New Device)

 

      

1

2

1 - 1%

4 - 30% 

7 - 60%

10 - 90%

2 - 10%

5 - 40%

8 - 70%

11 - 100% 

3 - 20%

6 - 50%

9 - 80%

9

 = Re

set Pin

Un-paired device send request to join a group.

10

10 = Remove Local Device Only

1 - Do not remove  2 - Remove * and **
* If device is the configurator, the group will “Restore” all devices in the group back to 
factory default. This action will un-pair all devices in the group.
** If device is not the configurator, the device will send a “Delete Node” message to the 
configurator for itself and restore itself back to factory defaults and will no longer be 
able to communicate with the group.

11 = Restore all Group Devices to Factory Default 

1 - Do not remove 2 - Remove

12 = LOW TRIM SETTING (LOWEST DIM VALUE)

4 = On Mode 

1 - Automatic On
Sensor automatically turns the light on when it detects occupancy.
2 - Manual On
Sensor requires pressing the button to turn the light on. 

5 = HIGH TRIM SETTING (MAXIMAUM BRIGHTNESS LEVEL) 

6 = Join Group (used in 3-way / multi-way applications) 

Places an unpaired device into “Join Group” mode. This will allow the device to join an 
existing group. Do this on the device that is new or an addition to the group, this needs 
to be completed prior to putting the Configurator Device in “Accept New Device” mode. 

7 = Accept New Device (used in 3-way / multi-way applications)

Places the new configurator device into "Accept New Device" mode. This is done after 
setting up a new /additional device to be added in join group mode.

8 = Add Mobile Device (Clairity Pro) 

Allow user to use mobile application of a pre-configured group. 

1 - 1%

4 - 30% 

7 - 60%

10 - 90%

2 - 10%

5 - 40%

8 - 70%

11 - 100% 

3 - 20%

6 - 50%

9 - 80%

Reviews: