1

LASER SCANNER 

FOR BUILDING AUTOMATION 

AND SECURITY

EN

User’s Guide

 

for product version 0600 and more

Summary of Contents for LZR-S25

Page 1: ...1 LZR S25 LASER SCANNER FOR BUILDING AUTOMATION AND SECURITY EN User s Guide for product version 0600 and more ...

Page 2: ...er wavelength 650nm max output CW power 3mW Class 3R according to IEC 60825 1 The visible laser beams are inactive during normal functioning The installer can activate the visible lasers if needed CAUTION Use of controls adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure Do not look into the laser emitter or the visible red laser b...

Page 3: ...connect white red and white blue wires to ground left right MOUNTING SIDE Stay outside of the detection field to avoid disturbances Select the corresponding mounting side The sensor then learns its environment and automatically determines the detection field s Both red LEDs flash slowly and the 3 visible laser beams automatically light up during 30 seconds WITH BACKGROUND WITHOUT BACKGROUND The se...

Page 4: ...ntrol use the following sequence no field 0 1 m 25 0 m 0 1 m 25 0 m 0 1 m 25 0 m REMOTE CONTROL ADJUSTMENTS OPTIONAL FACTORY VALUES IMMUNITY FILTER MIN OBJECT SIZE OUTPUT CONFIGURATION DETECTION FIELD REDIRECTION approximate values A active P passive NO normally open NC normally closed UNCOVERED ZONE field 1 field 2 field 2 field 1 or field 2 off indoor outdoor low outdoor med outdoor high indoor ...

Page 5: ...rol the sensor locks the access to the remote control session The batteries in the remote control are not installed properly or dead The remote control is badly pointed A reflective object is in close proximity to the sensor You have to enter a code or the wrong code was entered The object size is too small The polarity of the power supply is inverted Check cable and connexion Check wiring The red...

Page 6: ... free 35 V DC 24 V AC 80 mA resistive tON 5 ms tOFF 5 ms typ 30 Ω 0 7 V 20 mA 10 µA 2 optocouplers galvanic isolated polarity free 30 V DC over voltage protected Log H 8 V DC Log L 3 V DC 5 ms 1 blue LED power on status 1 orange LED error status 2 bi coloured LEDs detection output status green no detection red detection 125 mm D x 93 mm W x 70 mm H mounting bracket 14 mm PC ASA black or white 45 0...