background image

 

SINGLE MULTIPLE STATION PHOTOELETRIC 

SMOKE DETECTOR      SD-218 SERIES 

USER’S MANUAL 

 
TABLE OF CONTENTS

 

INTRODUCT ION………………………………..……………………………1 
LOCATIONS  TO INSTALL YOUR SMOKE DETECTOR  …………………...1 
LOCATIONS TO INSTALL YOUR SMOKE DETECTORS IN MOBILE 
HOMES  AND  RVs………………………………………………………………..3 
LOCATIONS NOT TO INSTALL YOUR SMOKE DETECTOR…..………….3 
INSTALLING  YOUR  SMOKE  DETECTOR  ………………………...…..  .  .  ..4 
HOW TO INTERCONNECT MODEL SD-218*-I DETECTORS 
TOGETHER………………………………………………………………………..5 
RED  LED  INDICATOR………………………………………………..………..7 
TESTING  YOUR  SMOKE  DETECTOR………………………………………7 
TAKING  CARE OF YOUR SMOKE  DETECTOR ………………...…………..7 
HEAT  SENSOR  TESTING………………………………………………………8 
FIVE  YEAR  LIMITED  WARRANTY  ……………………………….………..…8 

 

INTRODUCTION 

SENT EK’s  single  station  photoelectric  smoke  detector  is  designed 
to  sense  smoke  that  comes  into  the  detector  chamber.  It  does  not 
sense  gas,  heat,  or  flame.  T his  smoke  detector  is  designed  to  give 
early warning of developing fires by giving of f the  alarm  sounds from 
its  built-in alarm horn.  It  can  provide  precious  time  f or  you  and  your 
family to escape before  a  fire  spreads.  However, the smoke detector 
makes  such  pre-warning  of  f ire  accident  possible,  only  if  the 
detector  is  located,  installed,  and  maintained  properly  as  described 
in this User's Manual. 

WARNING:

 

This smoke detector is designed for use in a single residential 

unit only, which means that it  should be used  inside  a single family  home or 
apartment.  It  is  not  meant  to  be  used  in  lobbies,  hallways,  basements,  or 
another  apartment in multi-family  buildings,  unless there are already  working 
detectors  in  each  family  unit.  Smoke  detectors,  placed  in  common  areas 
outside of the individual living unit, such as on porches or in hallways, may not 
provide early warning to residents. In multi-family buildings, each family living 
unit should set up its own                                      detectors. 

WARNING:

 

This  detector  is  not  meant  to  be  used  in  non-residential 

buildings.  Warehouses,  industrial  or  commercial  buildings,  and  special 
purpose  non-residential  buildings  require  special  fire  detection  and  alarm 
systems.  This  detector  alone  is  not  a  suitable  substitute  for  complete  fire 
detection systems for places where many people live or work, such as hotels 
or motels. The same is true of dormitories, hospitals, nursing homes or group 
homes of any kind, even if they were once single  family homes. Please refer 
NFPA 101, the Life Safety Code, NFPA71, 72A, 72B, 72C, 72D, and 72E for 
smoke  detector  requirements  for  fire  protection  in  buildings  not  defined  as 
“households”. 

LOCATIONS TO INSTALL YOUR SMOKE DETECTOR 

Smoke detectors should be installed  in accordance  with  the NFPA Standard 
74  (National  Fire  Protection  Association,  Batterymarch  Park,  Quincy,  MA 
02169).  For  complete  coverage  in  residential  units,  smoke  detectors  should 
be installed in all  rooms, halls,  storage  areas,  basements, and attics in  each 
family living unit. Minimum coverage is one detector on each floor and one in 
each sleeping area. and attics in each family living unit. Minimum coverage is 
one detector on each floor and one in each sleeping area. 
 
Here, we have useful tips for you: 

˙

 Install  a  smoke  detector  in  the  hallway  outside  every  separate  bedroom 

area, as shown in Figure 1. Two detectors are required in homes with two 
bedroom areas, as shown in Figure 2. 

˙

 Install a smoke  detector on every floor  of a  multi-floor home or  apartment, 

as shown in Figure 3. 

 

˙

 Install a smoke  detector on every floor  of a  multi-floor home or  apartment, 

as shown in Figure 3. 

˙

 Install a minimum of two detectors in any household. 

˙

 Install a smoke detector inside every bedroom. 

˙

 Install smoke detectors at both ends of a bedroom hallway if    the    hallway 

is more than 40 feet (12 meters) long. 

˙

 Install a    smoke detector inside every room where one sleeps with the door 

partly  or  completely  closed,  since  smoke  could  be  blocked  by  the  closed 
door  and  a    hallway  alarm    may  not    wake  up  the  sleeper  if  the  door  is 
closed. 

 

Figure 1:LOCATIONS FOR PLACING 

SMOKE DETECTORS FOR 
SINGLE RESIDENCE WITH 
ONLY ONE SLEEPING AREA 

   
   

 

 

Figure 2: LOCATIONS FOR 

PLACING SMOKE 
DETECTORS FOR 
SINGLE-FLOOR RESIDENCE 
WITH MORE THAN ONE 
SLEEPING AREA 

 

 

 

Figure 3: LOCATION FOR PLACING 

SMOKE DETECTORS FOR 
A MULTI-FLOOR 
RESIDENCE       

                                 

 

˙

 Install  basement  detectors  at  the 

bottom of the basement stairwell. 

˙

 Install second-floor detectors at the top of the first-to-second floor stairwell. 

 
Be sure no door or other obstruction blocks the path of smoke to the detector. 

˙

 Install additional detectors in your living room, dining    room, family room, 

attic, utility and storage rooms. 

˙

 Install smoke detectors as close to the center of  the ceiling as possible. If 

this is not practical, put the detector on the ceiling, no closer than 4 inches 
(10 cm) from any wall or corner, as shown in Figure 4. 

˙

 If ceiling mounting is not  possible and  wall  mounting  is  permitted  by  your 

local and state codes, put wall-mounted detectors between 4 and 6 inches 
(10 ~ 15 cm) from the ceiling, also see Figure 4. 

˙

 If some of your rooms have sloped, peaked, or gabled ceilings, try to mount 

detectors 3 feet (0.9 meter) measured horizontally from the highest point of 
the ceiling as shown in Figure 5. 

   

Figure 4: RECOMMENDED 

BEST AND 
ACCEPTABLE 
LOCATIONS TO MOUNT 
SMOKE DETECTORS   

 

 
 

Figure 5: 

RECOMMENDED 

LOCATION TO MOUNT 

SMOKE DETECTORS 
IN ROOMS WITH 
SLOPED, GABLED, OR 
PEAKEDCEILING 

 

 

CAUTION

 

(As required by State Fire Marshall) 

“Early  warning  fire  detection  is  best  achieved  by  the  installation  of  fire 
detection equipment in all rooms and areas of the household as follows: (1) A 

 

 

 

 

 

Summary of Contents for SD-218-A Series

Page 1: ...al units smoke detectors should be installed in all rooms halls storage areas basements and attics in each family living unit Minimum coverage is one detector on each floor and one in each sleeping area and attics in each family living unit Minimum coverage is one detector on each floor and one in each sleeping area Here we have useful tips for you Install a smoke detector in the hallway outside e...

Page 2: ...ding unheated buildings or outdoor rooms If the temperature goes above or below the operating range of smoke detector it will not work properly The temperature range for your smoke detector is 32 o F to 120 o F 0 o C to 50 o C In very dusty or dirty areas dirt and dust can build up on the detector s sensing chamber to make it overly sensitive Additionally dust or dirt can block openings to the sen...

Page 3: ...series with I mark smoke detectors may be interconnected with as many as 38 other detectors 3 The total length of wire interconnecting the detectors should be no more than 1000 feet The interconnecting wire should be 18 AWG or larger and be rated at least 300V 4 The installation of such detector must be in accordance with the requirements of Article 760 of the National Electrical Code and any loca...

Page 4: ...ature between 132ºF and 180 ºF This requirement can be met by some domestic hair dryers Proceed as follows 1 Switch on the warm air flow and check that temperature is correct and stable 7 2 From a distance of inches direct the airflow at the guard protecting the thermistor The detector should alarm within 30 seconds 3 On alarm immediately remove the heat source check that the detector s red LED is...

Reviews: