background image

Sentry :

 Solutions for the Data Center Equipment Cabinet

Sentry :

 CDU Technical Specifications

Sentry Switched CDU

Input Current Monitoring

 

Exclusive True RMS current monitoring is critical to 
preventing overloads in high-density computing  
environments.  LED digital displays on the CDU enclosure 
report the input current of each phase or branch circuit.

              

Temperature and Humidity 

   

 

 

The Switched CDU supports two external 10’ (3m) probes. 
Each of these probes measure both temperature and 
humidity.  Receive SNMP-based alerts or email notifications 
when conditions exceed defined thresholds.

              

CW-24V4

High Density Power Distribution

The Switched CDU’s combine remote configuration and management 
with power distribution and power and environmental monitoring. 
Reboot a single or dual-power server with one command. Receive 
SNMP or email based alerts when power or environmental conditions 
exceed thresholds. Assign users specific access rights to designated 
outlets or groups. 

Only the Switched CDU products provide the flexibility needed for all 
data centers and remote sites, including power requirements for 
high-amp, high voltage; UL 60950-1 branch circuit protection; SSL & 
SSH security; and SNMP-based input current monitoring. 

> High Density: 

 Single-power 

input feed; 24 outlets per 

enclosure

> High Power Distribution

:  

Three-Phase 400V power; 16 or 

32-Amp power input feed 

options with 230V output 

> Input Current Monitor:

 

Precisely measure the aggregate 

current draw (in amps) on each 

power circuit.  On-site 

verification of the input current 

with the LED digital display. 

Remote verification via web 

browser or serial screen.

IP Access & Security: 

 Web 

interface, SSL, SSH, Telnet, SNMP, 
FTP, SNTP, Syslog, LDAP, LDAPS, 
TACACS

 

and RS-232 access

> SNMP Traps: 

Provide automated 

alerts for power and 

environmental conditions

Power-up Sequencing:

 Prevent 

an in-rush power overload

> Environmental Monitoring: 

 

Each Switched CDU supports two 

external temperature & humidity 

probes and reports conditions 

thru the user interface without 

the need for additional IP 

addresses

> Add an Expansion Module: 

 

Daisy chain the Switched CDU 

Expansion Module (CW/CX) for 

power monitoring of separate 

power circuits from a single IP 

address

 

Key Features

Model

Available Input

 Voltages

Outlets

Available Input

 Cord

Amperage

Dimensions**

(L x W x D)

69.0 x 1.75 x 2.25 in.

(1753 x 44.4 x 57 mm)

69.0 x 1.75 x 2.25 in.

(1753 x 44.4 x 57 mm)

69.0 x 1.75 x 2.25 in.

(1753 x 44.4 x 57 mm)

Additional Features and Specifications

Branch Circuit Protection

> Compliant to UL 60950-1

Agency Approvals

> US & Canada (cTUVus mark) to UL 60950-1:2003    

    and CAN/CSA 22.2 No. 60950-1-03          

> European Union (TUVGS mark) to EN 60950-1:2001 

> FCC Class A, Part 15 

    

> CE

> EMC - EN 55022 Class A, EN 55024

Communications and Security

> 10/100 BaseT Ethernet 

        

> HTTP/HTTPS  

        

> SSLv3/TLSv1  

       

> SNMPv2   

 

        

> SSHv2

> Telnet

> LDAPS/LDAPv3

> RS-232 (Serial)

Accessories

> Optional Temperature & Humidity Probe

 

EMTH-1-1 Temperature & Humidity Probe, 10 ft (3m)

 

© Server Technology, Inc. 12/2007 version. Information in this document is subject to change without notice. Sentry and Server Technology are trademarks of Server Technology, Inc. Patent # 7,043,543. Patents Pending. Printed in US.

Additional Benefits:

CW-24V4J411

CW-24V4K411

3-Phase, 400 V

50/60Hz

3-Phase, 400 V

50/60Hz

IEC 60309

Cordset, 10 ft (3m)

IEC 60309

Cordset, 10 ft (3m)

(24) IEC 60320/C13

(24) IEC 60320/C13

CX-24V4J411*

3-Phase, 400 V

50/60Hz

3-Phase, 400 V

50/60Hz

IEC 60309

Cordset, 10 ft (3m)

IEC 60309

Cordset, 10 ft (3m)

CX-24V4K411*

(24) IEC 60320/C13

(24) IEC 60320/C13

16A

16A

32A

32A

* CX part numbers refer to the Expansion CDU
**Please note that the depths of these enclosures are 3.30 in. (84mm) deep at the placement of the circuit breakers

APAC

Server Technology Intl

37th Floor, Singapore Land Tower
50 Raffles Place
Singapore 048623
+65 (0) 6829 7008  Tel
+65 (0) 6234 4574 Fax
salesint@servertech.com

 

HEADQUARTERS - NORTH AMERICA

Server Technology, Inc.

1040 Sandhill Drive
Reno, NV 89521
United States
1.775.284.2000  Tel
1.775.284.2065 Fax
sales@servertech.com
www.servertech.com
www.servertechblog.com

EMEA

Server Technology Intl

Sienna Court
The Broadway
Maidenhead
Berkshire
SL6 1NJ
United Kingdom
+44 (0) 1628 509053 Tel
+44 (0) 1628 509100 Fax
salesint@servertech.com

Branch Circuit Protection

The Sentry CDU Family meets the UL 60950-1 requirement 
for Branch Circuit Protections
 

> UL-489 rated circuit breakers

69.0 x 1.75 x 2.25 in.

(1753 x 44.4 x 57 mm)

Expansion Modules
> CX-24V4J411
> CX-24V4K411

Reviews: