background image

825B030D

TC26/27/28/29

Compact capacitance level transmitter with settable relay built-in

Technical Data

TC26-9

 

Mechanical installation

Enclosure material:

PP+Carbon steel

Mechanical installation:

  Bajonet

(to be insert into IP65 enclosure)

Mechanical protection:

  IP50

Electrical connection:

 2 x 6pole plug-in connectors

Working temperature:

          -30 to +80°C

Power  supply depend to the model:

   TC26  24Vdc,  TC27  24Vac,

               TC28 115Vac, TC29  230Vac

Power consumption:

         max 2,5W (1,5W Vdc)

Analog output:

         4÷20mA max load 500 ohm

Relays output:

   1 x SPDT 2A, 230Vac (resistive)

Serial port:

       RS485

Measure range:

                    20pF÷10.000pF

Temperature compensation:     

by ref. internal capacitor

Linearity:

         0,5%

Calibration:

two push-buttons, for self-acquisition

LEDs display:

 

     green LED flashing=measure

                     Fix=calibration

                                  yellow LEDs for rel1 action

The TC26-9 insert must be lodge into the IP65 capacitance-
sensor  head commection.
Important to screw tight the cover of the head connection and
the cable gland in order  to grant  the sensor IP65.
Thanks to the bajonet  fixing-system, to insert or remove the
TC26-9 from the head connection need to push and rotate.
Rotate clock-wise to fix into the head
Rotate reverse-clock-wise to remove from the head

LEVEL 4-20mA trans 1 settable relay insert, digital
tecnology, termal-drift compensation, two pushbuttons or
RS485 port for calibration. Local or remote calibration
possibility.

TC26-9

 

General

fig.3

fig.1

fig.2

applied solutions for the applications

Summary of Contents for TC26

Page 1: ...ion by ref internal capacitor Linearity 0 5 Calibration two push buttons for self acquisition LEDs display green LED flashing measure Fix calibration yellow LEDs for rel1 action The TC26 9 insert must be lodge into the IP65 capacitance sensor head commection Importanttoscrewtightthecoveroftheheadconnectionand the cable gland in order to grant the sensor IP65 Thanks to the bajonet fixing system to ...

Page 2: ...part gain the access to two 6 pole plug in connectors Electricalconnectionmustbemadewithamulti wires roundcableofproperdiameter otherwisethesealofthecablegland maybeimpaired Nospecialcableorcoax cablearerequestsfor compactversion andnopracticedistancelimits FortheVdcpower supplytakeinconsiderationthatthenegativeofthepowersupply iselectricallyconnectedtothenegativeoutputcurrent FortheVac powersuppl...

Page 3: ...d 100 level in order to memorise the relevant capacity electronically In the measuring mode the TC has the Mode LED flashing Tocalibrate0 4mA needstohavethe level at the 0 Press simultaneously P1 and P2 release themandverifythat Modeled willstayfix lightened Press two times P1 The measured capacity has been memorised and associated to 4mA output Press simultaneously P1 and P2 again to switch in me...

Page 4: ...se them and verify that Mode led will stay fix lightened Open the calibration mode Press two times P1 The measured capacity has been associated at the moment to 4mA output Now pushing few times the P2 key increase the output current from 4mA to 8 16mA P1 decrease the value Once the correct current output is displayed in to the current meter press simultaneously P1 and P2 again to Exit from calibra...

Reviews: