825B030D
TC26/27/28/29
Compact capacitance level transmitter with settable relay built-in
Technical Data
TC26-9
Mechanical installation
Enclosure material:
PP+Carbon steel
Mechanical installation:
Bajonet
(to be insert into IP65 enclosure)
Mechanical protection:
IP50
Electrical connection:
2 x 6pole plug-in connectors
Working temperature:
-30 to +80°C
Power supply depend to the model:
TC26 24Vdc, TC27 24Vac,
TC28 115Vac, TC29 230Vac
Power consumption:
max 2,5W (1,5W Vdc)
Analog output:
4÷20mA max load 500 ohm
Relays output:
1 x SPDT 2A, 230Vac (resistive)
Serial port:
RS485
Measure range:
20pF÷10.000pF
Temperature compensation:
by ref. internal capacitor
Linearity:
0,5%
Calibration:
two push-buttons, for self-acquisition
LEDs display:
green LED flashing=measure
Fix=calibration
yellow LEDs for rel1 action
The TC26-9 insert must be lodge into the IP65 capacitance-
sensor head commection.
Important to screw tight the cover of the head connection and
the cable gland in order to grant the sensor IP65.
Thanks to the bajonet fixing-system, to insert or remove the
TC26-9 from the head connection need to push and rotate.
Rotate clock-wise to fix into the head
Rotate reverse-clock-wise to remove from the head
LEVEL 4-20mA trans 1 settable relay insert, digital
tecnology, termal-drift compensation, two pushbuttons or
RS485 port for calibration. Local or remote calibration
possibility.
TC26-9
General
fig.3
fig.1
fig.2
applied solutions for the applications