background image

 

IV386  Rev.000 SIEL S.p.A. 

 

Data di emissione: 2015-10-02 

 

                 Pag. 55 di 263 + FR 

I

NTRODUCTION

 

 
Thank you for choosing our product.
 
Our  company  is  highly  specialised  in  the  development  and  production  of  uninterruptible  power  supplies  (UPS). 
 
 
The  UPS  device  described  in  this  manual  is  a  high  quality  product  that  has  been  carefully  designed  and  manufactured  to 
guarantee optimal performance. 
 
This manual contains detailed instructions for product use and installation. 

This manual must be stored in a safe place and  CONSULTED BEFORE DEVICE USE for proper usage instructions as 
well as maximum performance from the device itself. 

 

NOTE:

 Some images contained in this document are for information purposes only and may not faithfully demonstrate the parts 

of the product they represent 
 
 
 

 

E

NVIRONMENTAL 

P

ROTECTION

 

 
Our  company  devotes  abundant  resources  to  analysing  environmental  aspects  in  the  development  of  its  products.  All  our 
products pursue the objectives defined in the environmental management system developed by the company in compliance with 
applicable standards. 
 
Hazardous materials such as CFCs, HCFCs or asbestos have not been used in this product. 
 
Packaging  is  composed  of 

RECYCLABLE  MATERIALS

.  Dispose  of  all  material  in  compliance  with  applicable  standards  in  the 

country in which the product is used. Refer to the following table to identify materials: 
 
 

D

ESCRIPTION

 

M

ATERIAL

 

Pallet 

Wood 

(FOR) 

 

Package box 

Corrugated cardboard 

(PAP) 

 

Protective bag 

High density polyethylene 

(PE-HD) 

 

Adhesive buffers 

Low density polyethylene 

(PE-HD) 

 

Bubble wrap 

 
 
 

 

D

ISPOSING OF THE PRODUCT

 

 
The UPS contains internal material which (in case of dismantling/disposal) are considered TOXIC AND  HAZARDOUS WASTE, 
such as electronic circuit boards and batteries. Treat these materials according to the laws in force, contacting qualified centres. 
Proper disposal contributes to respect for the environment and human health. 
 
 
 
 
 

 

© 

The reproduction of any part of this manual, even in part, is prohibited unless authorised by the Manufacturer. 
The manufacturer reserves the right to change the product described at any time without prior notice for improvement purposes. 

 

 

Summary of Contents for SAFEPOWER EVO-HF 160

Page 1: ...environmental management system developed by the company in compliance with applicable standards Hazardous materials such as CFCs HCFCs or asbestos have not been used in this product Packaging is com...

Page 2: ...ROTECTION 67 AIR EXCHANGE IN THE BATTERY ROOM 67 REMOVING THE UPS FROM THE PALLET 68 CHECKING THE CONTENTS OF THE ACCESSORIES BOX 70 UPS POSITIONING 70 ELECTRICAL CONNECTIONS 71 CABLE SIZES 71 PRELIMI...

Page 3: ...ON FROM THE BATTERY 85 SHUTDOWN 85 FAN MANAGEMENT 85 GRAPHIC DISPLAY 86 DISPLAY MENU 88 OPERATING MODE 89 MANUAL BYPASS SWMB 89 REDUNDANT AUXILIARY POWER ADAPTER FOR AUTOMATIC BYPASS 90 POWER WALK IN...

Page 4: ...uit solutions with cutting edge components provide superior performance Here are some examples ZERO IMPACT SOURCE ensures low input distortion power factor close to one and maximum compatibility with...

Page 5: ...IV386 Rev 000 SIEL S p A Data di emissione 2015 10 02 Pag 59 di 263 FR FRONT UPS VIEWS Control panel with graphic display UPS feet Ventilation grille Wheels for UPS handling Front door with lock...

Page 6: ...IEL S p A Data di emissione 2015 10 02 Pag 60 di 263 FR User interface Left to right SWOUT Output switch SWBYP Bypass input switch SWMB manual bypass switch SWOUT Output switch Power module fans Prima...

Page 7: ...SER INTERFACE Schuko plug and fuse Left to right R E P O Remote Emergency Power Off connector AS400 Contacts port USB communication port RS232 communication port COLD START battery start up button Slo...

Page 8: ...IV386 Rev 000 SIEL S p A Data di emissione 2015 10 02 Pag 62 di 263 FR UPS REAR VIEW Control fans IN OUT connection access Auxiliary contact access Secondary bypass fans Battery charger fans...

Page 9: ...UT access panel to access the UPS terminal board BATTERY N Power connections BATTERY and NEUTRAL INPUT L1 L2 L3 N Power connections INPUT PHASES AND NEUTRAL BYPASS L1B L2B L3B Power connections SEPARA...

Page 10: ...SWITCH OUT AUX CONTACT Connection for remote auxiliary output switch AUX RELAY SLOT Relay slot SEPARATE BYPASS INPUT THIS SERIES OF UPS UNITS CAN BE CONFIGURED IN DUAL INPUT MODE I E WITH THE BYPASS L...

Page 11: ...teady on battery operation Flashing battery operation with early low battery or imminent shutdown warning Flashing in standby programmed restart function active and mains absent Load on bypass LED Ste...

Page 12: ...Installation Instructions avoid dusty environments ensure that flooring is flat and able to sustain the weight of the UPS and Battery Boxes avoid environments that are too narrow which might prevent...

Page 13: ...p the concentration of hydrogen generated during charging within safe limits The room should preferably be ventilated naturally if it cannot be forced ventilation may be employed Standard EN 50272 2 r...

Page 14: ...AL INJURY AND OR EQUIPMENT DAMAGE Find the 4 hooks at the sides of the package lift them to open as shown in the figure Lift the lid and open the carton Remove the accessories container NOTE the acces...

Page 15: ...ift the UPS off the pallet with a lift truck take care to position the forks properly CAUTION Whenever you need to lift the UPS make sure that the forks are always positioned as indicated by the label...

Page 16: ...e only to be used for accurate positioning so for short trips plastic parts and the door are not able to act as pushing points or handles leave sufficient clearance in front of and behind the device t...

Page 17: ...nection to be made is the protective conductor earth wire to be connected to the screw marked PE The UPS must operate while connected to the earthing system The input Neutral must always be connected...

Page 18: ...l on the back of the device see UPS rear views hook up the GND cable to the power connection bar marked PE connect the input bypass output and battery cables to the terminal board following the positi...

Page 19: ...00 SIEL S p A Data di emissione 2015 10 02 Pag 73 di 263 FR ELECTRICAL SYSTEM CONNECTION DIAGRAMS UPS without neutral connectivity variation UPS with galvanic input insulation UPS with galvanic output...

Page 20: ...one 2015 10 02 Pag 74 di 263 FR UPS without neutral connectivity variation and with separate bypass input UPS with galvanic input insulation and with separate bypass input UPS with galvanic output ins...

Page 21: ...e shared inside the device therefore they will have to be connected to the same potential If the two power supplies are different you must use an isolation transformer on one of the inputs UPS without...

Page 22: ...rs which causes backfeed on the bypass line the protection switches off the inverter and switches the load to the bypass If the fault occurs with the UPS in battery operation the load remains unpowere...

Page 23: ...e the device A single differential switch must be fitted upstream of the point at which the line divides to supply the trip switch protected rectifier and bypass inputs for the UPS See following diagr...

Page 24: ...ntacts of the remote maintenance and remote output bypass switches are available at the back of the UPS see Auxiliary contacts section These are identified respectively by the words SERVICE BYPASS and...

Page 25: ...inside a remote Battery Box Use ONLY the kit provided by the manufacturer use which does not observe the specifications may cause the equipment to malfunction or fail For installation connect the cab...

Page 26: ...s and power cables suitable for UPS currents Use a double insulation cable with a 1mm2 section for connecting SERVICE BYPASS and AUX SWOUT terminals to relative REMOTE MAINTENANCE BYPASS 3 and OUTPUT...

Page 27: ...parallel connection of two UPS s When UPS s are connected in parallel the ECO LINE INTERACTIVE SMART SMART ACTIVE and STBYOFF STAND BY OFF modes are not available The optional parallel connection kit...

Page 28: ...d battery efficiency conditions The following is a block diagram of the UPS which describes the individual components that it is composed of UPS block diagram IMPORTANT Our UPS have been designed and...

Page 29: ...all switches are open Closing the external battery line switch fuse Check the polarity of the connections then close the external battery line switch fuses CAUTION any connection not compliant with th...

Page 30: ...anagement Setting the nominal battery capacity CAUTION you must configure the UPS to set the correct total nominal battery capacity This operation must be performed by means of the configuration softw...

Page 31: ...When asked to confirm select YES and press again to confirm The leds around the display turn on for 1 second and the buzzer will start beeping every 7 seconds The start sequence is completed when the...

Page 32: ...ter Battery Line Inverter Load Inverter Output Line Battery Charge Automatic Static Bypass The diagram shows the status of the three power logical modules PFC Converter Inverter Automatic Static Bypas...

Page 33: ...lative to the selected menu UPS STATUS ERRORS FAULTS UPS operation status display area The first row is always active and constantly displays UPS status in real time The second is activated only in th...

Page 34: ...IV386 Rev 000 SIEL S p A Data di emissione 2015 10 02 Pag 88 di 263 FR DISPLAY MENU...

Page 35: ...f the input for bypass use Outside of this tolerance the UPS desynchronizes bringing itself to the nominal frequency and bypass can no longer be used free running mode CAUTION When UPS s are connected...

Page 36: ...pped with a Power Walk In mode which can be activated and configured via configuration software When this mode is enabled once the mains power is restored after a period of autonomy the UPS begins abs...

Page 37: ...p Press keys F1 and F4 simultaneously for t 2 sec and English will automatically be reset Function modification can be locked out with the configuration software Configurations which can be modified b...

Page 38: ...ange for switching to the bypass Low 180V High 264V Eco mode sensibility Selects the intervention sensitivity during operation in ECO mode Normal Eco mode min max threshold Selects the accepted voltag...

Page 39: ...of the UPS RS232 AND USB CONNECTORS RS232 CONNECTOR USB CONNECTOR PIN NAME TYPE SIGNALS PIN SIGNALS 1 IN 1 VBUS 2 TX OUT TX serial line 2 D 3 RX IN RX serial line 3 D 4 4 GND 5 GND POWER 6 OUT 7 8 15V...

Page 40: ...jumper is removed in the presence of power the UPS will begin operation via the inverter If the jumper is removed without power the UPS will begin operation via batteries 4 5 12 BATTERY LOW OUTPUT 1...

Page 41: ...ypass to compensate for current surges due to the insertion of a distorted current Sound C This signal is emitted when the UPS switches to battery operation before No Battery is signalled sound D It i...

Page 42: ...ftware from www ups technet com selecting the desired operating system Connect the UPS RS232 communication port to a PC COM communication port by means of the supplied serial cable or connect the UPS...

Page 43: ...ect the mains to the terminals as indicated in the Installation paragraph THE SWITCH BEHIND THE DOOR SWIN IS OPEN Close the switch NO MAINS VOLTAGE BLACKOUT Verify electrical main voltage presence If...

Page 44: ...persists THE DISPLAY SHOWS ONE OR MORE OF THE FOLLOWING CODES F09 F10 UPS INPUT STAGE MALFUNCTION Activate manual bypass SWMB switch off and re start the UPS Exclude manual bypass Contact the nearest...

Page 45: ...force power on manually via the ON menu THE DISPLAY SHOWS ONE OR MORE OF THE FOLLOWING CODES F06 F07 F08 INPUT SWITCH SHORTCIRCUITED Operate the manual bypass SWMB switch the UPS off open SWIN and co...

Page 46: ...DING 40 C SOURCES OF HEAT NEAR THE UPS VENTILATION SLITS OBSTRUCTED OR TOO CLOSE TO WALLS TEMPERATURE SENSOR OR BATTERY CHARGER COOLING SYSTEM MALFUNCTION Remove the cause of over temperature Insert m...

Page 47: ...Economy mode on S09 Ready for start up S10 UPS locked load not powered S11 UPS locked load on bypass S12 BOOST stage or battery charger locked load not powered S13 Frequency converter load powered by...

Page 48: ...n Phase3 bypass line out of tolerance range A16 Bypass frequency out of tolerance range A18 Voltage on bypass line out of tolerance range A22 Load on Phase1 set user threshold A23 Load on Phase2 set u...

Page 49: ...nusoid inverter deformed F15 Phase2 sinusoid inverter deformed F16 Phase3 sinusoid inverter deformed F17 Inverter stage fault F19 Positive battery overvoltage F20 Negative battery overvoltage F23 Outp...

Page 50: ...se2 inverter overvoltage L16 Phase3 inverter overvoltage L17 Phase1 inverter undervoltage L18 Phase2 inverter undervoltage L19 Phase3 inverter undervoltage L20 Continuous voltage on inverter output or...

Page 51: ...of 1 sec OUTPUT STAGE Nominal Voltage 4 380 400 415 V AC three phase with neutral 4 wire Nominal frequency 5 50 60Hz Output nominal current 232A 290A Apparent nominal output power 160kVA 200kVA Active...

Page 52: ...h 25A 2 Nominal battery current in the following conditions nominal load PF 1 battery at nominal voltage 3 100 load THDv 1 4 To keep the output voltage within the specified precision you may need to r...

Reviews: