Hazardous voltage.
Will cause death or severe
injury.

Turn off and lock out all power
supplying this device before
removing cover(s) or device and
while cover(s) are removed.

Replace all covers and shields
before power supplying this device
is turned on.

Item:

Solid State Molded Case Circuit Breakers
Electronic Sentron Standard Mining Duty

Devices:

Siemens  JM Frame Type JM6 and
LM Frame Type LM6.

Page

1 of 4

Pc. No. 

411625A00

NOTE: This instruction outlines the recommended
installation procedure.

INTRODUCTION

The JM and LM Frame circuit breaker line includes
JM6 and LM6 circuit breaker types.  These circuit
breakers are rated for operating voltages up to 600
VAC, 50/60 Hz.

INSTALLATION

JM and LM Frame circuit breakers are for use in
individual enclosures, panelboards, switchboards
or other approved equipment.

The installation procedure consists of inspecting,
attaching required accessories, mounting the
circuit breaker and connecting and torquing the line
and load wire connectors.

Mounting hardware and unmounted wire connectors
(where required) are available as separate catalog
items.

A. Turn off and lock out all power before installing

or servicing this circuit breaker.

Fig. 1

B. Make sure that the device is suitable for the

installation by comparing nameplate ratings with
system requirements.  Inspect the circuit breaker
for completeness and check for any damage
before mounting.

C. Device must be in “TRIPPED” or “OFF” position

prior to mounting.  See Fig. 4.

Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.
For questions call 1-800-241-4453 or our web site:
http://www.sea.siemens.com/dpd

Installation Instructions

SAFETY INSTRUCTIONS

Summary of Contents for 411625A00

Page 1: ... for use in individual enclosures panelboards switchboards or other approved equipment The installation procedure consists of inspecting attaching required accessories mounting the circuit breaker and connecting and torquing the line and load wire connectors Mounting hardware and unmounted wire connectors where required are available as separate catalog items A Turn off and lock out all power befo...

Page 2: ...lans refer to Fig 3 3 If device contains internal accessories make sure terminals can be connected when the circuit breaker is mounted Fig 3 Fig 2 9 75 4 40 6 86 OF HANDLE ESCUTCHEON OF HANDLE ESCUTCHEON DRILL AND TAP 1 4 20 HOLE 4 OR 6 PLS REQUIRED FOR SCJD6 SCLD6 ONLY OF HANDLE ESCUTCHEON SEE FIG 2 OF HANDLE ESCUTCHEON SEE FIG 2 1 50 3 00 1 25 2 50 3 07 1 50 2 00 3 25 6 50 4 Remove the line and ...

Page 3: ...Manual operation of the circuit breaker is controlled by the circuit breaker handle and the PUSH TO TRIP button The circuit breaker handle has three indicating positions two of which are molded into the handle to indicate ON and OFF The third position indicates a TRIP position and is between the ON and OFF positions See Fig 4 A Circuit Breaker Reset After tripping the circuit breaker is reset by m...

Page 4: ...tting lr is a percentage of the Maximum Continuous Current rating ln Two long time delay settings are available These are delay times of 3 seconds or 25 seconds at 6 times the Continuous Current Setting lr These are selected by using the appropriate area of the setting See Figure 5 Instantaneous Pickup All models have an Instantaneous Pickup adjustment This adjustment sets the Instantaneous Pickup...