Installation Instructions
Document No. 538-863
October 10, 2011
APOGEE
®
Dial-Up Modem
Item Number 538-863, Rev. GA
Page 1 of 2
Product Description
Accompanying U.S. Robotics Sportster 56K bps
modem has been factory configured for use with
APOGEE Field Panel Dial-Up Application.
APOGEE Auto-dial Application will reset Insight
®
modem as needed.
Contents of 538-859 Carton
Description
Qty.
Sportster 56K Modem Model No. USR5686
1
Power Adapter 120 Vac
1
1
7 foot Modular Phone Cord
1
User Documentation Package
1
Installation Instructions
1
1.
For international installation, locally purchase U.S. Robotics
Sportster 56K bps modem configured for the country where
used and program settings per this instruction.
Prerequisites
Analog telephone line connected through a NEC
800.30 type telephone primary protector.
UL497A telephone transient suppressor
installed. For field panel a 538-600 telephone
transient suppressor is installed. Suppressor
sold separately or included in modem kits, refer
to Installation Instruction 538-674.
UL1449 listed power line protector. Not required
if plugged into a field panel service box outlet or
outlet assembly.
Expected Installation Time
15 minutes
Warning/Caution Notations
WARNING
Personal injury/loss of life
may occur if a procedure is
not performed as specified.
CAUTION
Equipment damage or loss
of data may occur if the
user does not follow
procedure as specified.
WARNING:
Connect modem to telephone line through
a UL497A listed Telephone Transient
Surge Suppressor and and NEC 800.30
telephone primary protector.
Required for modem installation in a field
panel used per
Smoke Control Application
and Engineering Manual
(125-1806).
WARNING:
Connect modem to power through a
UL1449 listed power protector or field
panel service box outlet.
CAUTION:
Modem must be connected to an analog
telephone line. Using a non-analog line
(e.g., PBX, digital, multi-line) will damage
modem. A transient surge protector is
required.
CAUTION:
This modem has been factory set to
automatically start in the dial-up mode.
Refer to
APOGEE Automation Start-Up
Procedures Manual
on InfoLink.
External Switch Settings
DIP switches, located on the back of the modem,
have been configured to start-up in the APOGEE
Dial-Up Application for field panels as shown in the
following illustration:
Figure 1 Sportster Modem DIP Switches, Dial-Up
APOGEE Insight Auto-Dial Application will override
DIP switch settings as needed.