background image

Siemens 

Siemens 

Siemens 

Siemens 

Siemens Industry

Industry

Industry

Industry

Industry,,,,, Inc.

 Inc.

 Inc.

 Inc.

 Inc.

Building 

Building 

Building 

Building 

Building T

TT

TTec

ec

ec

ec

echnologies Di

hnologies Di

hnologies Di

hnologies Di

hnologies Division

vision

vision

vision

vision

P/N 315-034200-9

INTRODUCTION

The Model CDC-4 from Siemens Industry, Inc., is a card that
allows conventional detectors to be used on the FireFinder-XLS
system. It provides four Class A or Class B conventional detec-
tion zones. Each zone can support two-wire photoelectric or
ionization compatible smoke detectors and an unlimited number
of normally open circuit closure devices. The module also
supports Siemens Fire Safety flame and beam detectors. The
relay base, remote lamp and audible base may also be used with
the CDC-4. The CDC-4 uses one network address on the
FireFinder-XLS system. It has diagnostic LED indicators showing
module status and the status of each zone.

OPERATION

Activation of any device on the circuit initiates a zone alarm and
causes any previously programmed functions to operate. Any
circuit in an alarm or trouble condition is displayed on the PMI/
PMI-2/PMI-3.

The CDC-4 is designed to function in a local degrade mode
during failure of the FireFinder-XLS main processor or during
the loss of the system communication network. While in the
degrade mode, the CDC-4 can report both alarm and trouble
conditions and can activate local outputs on other modules
within the same enclosure.

The maximum zone alarm current can be set to either 175mA
or 100mA and is set in pairs for zones 1/2 and 3/4. When a
compatible detector is selected in the Zeus Programming Tool,
the maximum zone alarm current is automatically set by the
CDC-4. Detectors requiring the 100mA zone current limit (see
table on page 11) cannot be used on the same zone pair as
detectors requiring the 175mA zone current limit (see table on
pages 7-11).

CDC-4 zones may be configured either as alarm-causing or
supervisory-causing, if allowed by the local Authority Having
Jurisdiciton.

Do not use shorting devices on circuits with accessories on them. The shorting

devices will lower the zone voltage to a point where the accessories will not operate.

Figure 1

CDC-4 Conventional

Detector Card

Conventional Detector Card

Installation Instructions
Model CDC-4

Summary of Contents for CDC-4

Page 1: ... functions to operate Any circuit in an alarm or trouble condition is displayed on the PMI PMI 2 PMI 3 The CDC 4 is designed to function in a local degrade mode during failure of the FireFinder XLS main processor or during the loss of the system communication network While in the degrade mode the CDC 4 can report both alarm and trouble conditions and can activate local outputs on other modules wit...

Page 2: ...e reset switch and their functions are defined as follows POWER Green Normally ON When illuminated indi cates that power for the CDC 4 is applied to the card CARD FAIL Yellow Normally OFF When illuminated indi cates that the card microprocessor has failed HNET FAIL Yellow Normally OFF When illuminated indi cates that the HNET communication with the CDC 4 has terminated and the card goes into degra...

Page 3: ...LE Yellow Normally OFF When illuminated indicates that a trouble condition has been de tected in Zone 4 It will stay on continu ously until the condition is cleared ZONE 4 CLASS A OPEN Yellow Normally OFF When illuminated indi cates that there is a break in the Class A wiring in Zone 4 Three rotary dial switches at the bottom of the front panel are used to set the HNET network address of the CDC 4...

Page 4: ... without conduit may also be used The CDC 4 may be connected to existing device loops that have a 3 9K or 4 7K end of line resistor 1 4W 5 or a 50uF 50V end of line capacitor installed Always use a 50uF 50V end of line capacitor for new installations and whenever practical in existing detector loops for all detector models except the Siemens PBA 1191 which requires a 4 7K end of line resistor as s...

Page 5: ...or List for the maximum number of detectors per zone 5 Do not mix smoke detectors with the PBA 1191 6 Do not mix different manufacturer s smoke detectors on the same zone 7 Max resistance 70 ohms circuit 40 ohms circuit if accessories relay audible bases are used 8 Do not use shorting devices on circuits with accessories on them 9 Only one device accessory per circuit is guaranteed to activate on ...

Page 6: ...p the system and verify that the CDC 4 power LED turns ON INITIATING DEVICES Refer to the UL Compatible Two Wire Detector List for the number of detectors that may be used on a CDC 4 zone Refer to Figure 3 for initiating device wiring All circuits are power limited to NFPA 70 per NEC 760 Each detector or group of detectors must use a two wire circuit of at least 18 AWG thermoplastic fixture wire e...

Page 7: ... a B V 4 2 0 t n e r r u C V 4 2 l a n i m r e T w e r c S y r o s i v r e p u S x a m e n o z r e p A m 8 A m 0 1 1 y r o s i v r e p u S x a m e n o z r e p A m 8 A m 0 1 1 m r a l A x a m e n o z r e p A m 0 2 3 A m 0 1 1 m r a l A x a m e n o z r e p A m 0 8 2 A m 0 1 1 t n e r r u C e n a l P k c a B V 2 6 x a m A m 0 5 1 t n e r r u C y b d n a t S V 4 2 y r o s i v r e p u S x a m e n o z r...

Page 8: ...T 4 B D S T 4 B D F T 4 B D 0 3 0 3 Y s n e m e i S 6 I D 6 I D S T 4 B D F T 4 B D S T 4 B D F T 4 B D 0 3 0 3 Y s n e m e i S 5 3 1 P 3 T D 5 3 1 P 3 T D S 3 B D S 3 B D d e t i m i l n U Y s n e m e i S 1 1 T D 1 1 T D 1 1 B D T P D A w S 3 B D 1 1 B D S 3 B D 0 3 0 3 Y s n e m e i S 1 2 1 I H 1 2 1 I H E 1 1 B D 1 1 B D E 1 1 B D 1 1 B D 0 3 0 3 Y Y s n e m e i S 1 2 1 H O 1 2 1 H O E 1 1 B D ...

Page 9: ... 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 0 2 1 8 6 5 4 0 2 2 1 8 6 5 4 7 2 2 1 8 6 5 4 0 3 2 1 8 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 3 0 3 5 2 5 2 5 2 0 3 N o l l o p A 0 8 3 0 0 0 5 5 0 8 3 0 0 0 5 5 0 0 2 1 8 6 5 4 0 2 2 1 8 6 5 4 7 2 2 1 8 6 5 4 0 3 2 1 8 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 0 2 1 8 6 5 4 0 2 2 1 8 6 5 4 7 2 2 1 8 6 5 4 0 3 2 1 8 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 2...

Page 10: ...c e l E L S E T C 9 2 4 A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T F A C 1 1 5 A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T F A C 8 1 5 A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T X B B 1 2 5 F F O 1 w S w A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T X R C 1 2 5 F F O 1 w S w A 1 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T X B B 8 2 5 F F O 1 ...

Page 11: ...2 4 S N 0 2 2 6 S N 3 B H 5 1 5 1 Y Y i k i h c o H 4 2 J I S 3 D H 4 2 2 4 S N 4 2 2 6 S N 5 B H 5 1 5 1 Y Y i k i h c o H F 4 2 K L S H F 4 2 K L S 3 D H D 2 2 S H 2 2 M A B Y 3 B H 3 B H 0 2 0 2 Y Y i k i h c o H F 4 2 K L S H F 4 2 K L S 3 D H D 4 2 2 S H 4 2 2 M A B Y 5 B H 5 B H 0 2 0 2 Y Y i k i h c o H F 4 2 K L S H F 4 2 K L S 3 D H 4 2 2 B S H 3 5 B H 0 2 0 2 Y N i k i h c o H F 4 2 K L ...

Page 12: ...4 B 1 0 4 B B 6 0 4 B d n a A 5 2 Y r o s n e S m e t s y S K R B H D 1 5 4 1 A 0 0 4 H D A 5 2 N r o s n e S m e t s y S K R B 1 5 1 2 A d n a P L 0 1 1 B P L 6 1 1 B A 5 2 Y r o s n e S m e t s y S K R B T 0 0 3 2 A A N A N 5 2 N r o s n e S m e t s y S K R B 0 0 4 2 A A N A N 5 2 Y r o s n e S m e t s y S K R B H T 0 0 4 2 A A N A N 5 2 Y r o s n e S m e t s y S K R B 1 5 4 2 A B 1 0 4 B 1 0 4 ...

Page 13: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 14: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 034200 9 Document ID A6V10239127 ...

Reviews: