FDCL181 Line Separator  
Product Manual 

 

 
 

Overview  

FDCL181 Line Separator is used to detect and isolate the short-circuit part of the FD18-
BUS. Isolators are connected to prevent different branches from breaking down at the 
same time due to a short circuit.  

Characteristic 

l

 

Protection of FD18-BUS from short-circuit 

l

 

For T branches of FD18-BUS 

l

 

Indication of conditions by LED indicator  

l

 

Automatic address setting without encoder settings or  Dip-switch 

l

 

Communication via FD18-BUS

separate address 

 

l

 

Directly applicable in dry areas. Applicable in humid and dusty areas with a housing 

l

 

Sticker Method

 easy for commissioning 

Function 

l

 

Embedded in a FD18-BUS same function as a electronic switch to isolate the short 
circuit part of the line and ensure the normal operation of other parts. 

l

 

Connected to the detection bus by two four-entry terminals. 

l

 

Indication of short circuit isolation by a yellow LED. 

Summary of Contents for FDCL181

Page 1: ...ches of FD18 BUS l Indication of conditions by LED indicator l Automatic address setting without encoder settings or Dip switch l Communication via FD18 BUS separate address l Directly applicable in dry areas Applicable in humid and dusty areas with a housing l Sticker Method easy for commissioning Function l Embedded in a FD18 BUS same function as a electronic switch to isolate the short circuit ...

Page 2: ...ction up to 32 devices can be connected between two isolators l In a stub line connection up to 32 devices can be connected to one isolator Structure The module consists of the module carrier the printed circuit board and the cover The printed circuit board includes two LEDs to indicate isolating localization status To protect the modules from environmental influences housing FDCH221 is optional F...

Page 3: ...CH221 Installation of FDCH221 Housing 1 Open the housing 2 Determine the cable entries in the housing and break these open 3 Use two screws M 4 to fit the housing on a plane surface Fig 3 Distance between holes 182 0 1 0mm 4 Fix and guide in the cables with waterproof joint provided by users themselves 5 Fix the lid additionally with four screws Fig 4 Only this way is IP protection guaranteed The ...

Page 4: ...10 48 Specification Operating voltage 12 32VDC Operating current Quiescent 0 25 mA Activation current 0 45 mA Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 Communication protocol FD18 BUS Connection terminal 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With housing FDCH221 IP65 Details for ordering Type Material No P...