These instructions are written in accordance with the
installation guidelines of NFPA No. 72, National Fire
Alarm Code, and CAN/ULC-S524, The Installation of
Fire Alarm Systems.

CAUTION

Detector Storage

DO NOT install the detector until all construction
is completed.

DO NOT store this detection device where it can
be contaminated by dirt, dust, or humidity.

DETECTOR PLACEMENT

Although no specific spacings are set for the detectors
used for the 0 to 300 ft/min clean air velocity applica-
tion, use 30 foot center spacing (900 sq ft) from NFPA
72, National Fire Alarm Code, Chapter 5, if practical,
as a guide or starting point for a detector installation
layout. This spacing, however, is based on ideal
conditions—smooth ceiling, no air movement, and no
physical obstructions. In some applications, therefore,
considerably less area is protected adequately by each
smoke detector. This is why it is mandatory to closely
follow the installation drawings. In all installations
(except in special circumstances, such as in computer
room underfloors where the velocity may be up to 1200
ft/min) place the detector on the ceiling, a minimum of
12 inches from a side wall, or on a wall, 6 inches from
the ceiling.

If you have questions regarding detector placement,
follow the drawings provided or approved by Siemens
Building Technologies, Inc. or by its authorized
distributors. This is extremely important! The detector
placements shown on these drawings were chosen
after a careful evaluation of the area that is protected.
Factors such as air currents, temperature, humidity,
pressure, and the nature of the fire load were carefully
considered. Especially noted were the room or area
configuration and the type of ceiling (sloped or flat,
smooth or beamed). Siemens Building Technologies,
Inc.'s extensive experience in the design of the system
assures the best detector placement by following these
drawings. Sound engineering judgment by qualified
personnel must be followed.

Smoke and Fire Detector Models
ILI-1, ILI-1H, ILI-1A, and ILI-1AH

Fire Safety

Installation Instructions

TO AVOID NUISANCE ALARMS WITH THESE
DETECTORS:

DO NOT LOCATE 

the detectors next to an oil burner,

kitchen, or garage where exhaust fumes can trigger
an alarm. Other causes of nuisance alarms are dust
accumulation, heavy concentrations of steam, heavy
pipe or cigar smoke, aerosol sprays, high air velocity,
or in an area of prolonged high relative humidity where
condensation occurs.

NOTE:

Except in the case of the ILI-1A and ILI-1AH
where the detector can be used for high air
velocity applications of up to 1200 feet per
minute.

AIR CURRENTS

Before a detector can sense a fire, the products of
combustion or smoke must travel from the fire to the
detector. Since their travel is influenced by air currents,
consider the movement of air in the design of the
system. While combustion products tend to rise, drafts
from hallways, air diffusers, fans, etc., may help or
hinder the travel of combustion products to the
detector. When positioning a detector at a particular
location, consider the position of windows and doors,
both open and closed, and air movement. Never install
a detector in the air stream of a room air supply diffuser.
It is better to position a detector closer to an air return.

The distance that products of combustion or smoke travel
from a fire to the detector is not usually the shortest linear
route. Combustion products or smoke usually rise to
the ceiling, then spread out. With an average ceiling
height (8 to 10 feet), this is not an abnormal factor.
However, with high ceilings such as in churches, ware-
houses, auditoriums, etc., consider the height.

SPECIAL CEILING CONSTRUCTION FACTORS

Ceiling obstructions can change the natural movement
of air and combustion products. Depending on the
direction of smoke travel, joists and beams can slow
the movement of heated air and smoke, while pockets
between them can contain a reduced level of
smoke.Take obstructions created by girders, joists,
beams, air conditioning ducts, or architectural design
into consideration when determining area protection.

P/N 315-095387-5

Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN

Summary of Contents for ILI-1

Page 1: ...1AH Fire Safety Installation Instructions TO AVOID NUISANCE ALARMS WITH THESE DETECTORS DO NOT LOCATE the detectors next to an oil burner kitchen or garage where exhaust fumes can trigger an alarm Other causes of nuisance alarms are dust accumulation heavy concentrations of steam heavy pipe or cigar smoke aerosol sprays high air velocity or in an area of prolonged high relative humidity where cond...

Page 2: ...actor that can only be provided by experienced qualified personnel DETECTOR WIRING Siemens Building Technologies Inc detectors should be interconnected as shown in Figure 1 and wired to the control panel by following the Wiring Diagram installed on the inside face of the control panel or in the Control Panel Manual provided Note any limitations on the number of detectors permitted on each circuit ...

Page 3: ...rogramming Manual P N 315 092394 for additional information TESTING AND SENSITIVITY MEASUREMENTS XL3 Systems Only qualified service personnel should test Refer to the SYSTEM XL3 OPERATION INSTALLATION AND MAINTENANCE MANUAL P N 315 083206 Test as frequently as required by the Installation and Test Guidelines of NFPA72 Obtain detector sensitivity measurements from the System XL3 Control Panel Refer...

Page 4: ...ribed below CLEANING PROCEDURE Clean by lightly brushing all open slots and by using the suction of a vacuum cleaner Because the suction may cause the detector to alarm it is recommended that power to the detector be disconnected during cleaning The detectors are not designed for thorough cleaning in the field When the detector sensitivity falls outside the acceptable limits for that detector the ...

Reviews: