INTRODUCTION

The Model NRC Network Ring card from Siemens Industry,
Inc. is a card that networks multiple FireFinder-XLS systems
together in a Class X (Style 7) ring. The NRC can also be
configured for Class B (Style 4) operation in systems where
a ring is not required, as an alternative to the NIC-C card.

It provides communication between its host FireFinder-XLS
system and other FireFinder-XLS systems on an XNET network.
It replaces the NIC-C when a ring connection is needed.

The NRC can also be used to connect an NCCNT-G to the
XNET network. In this configuration, all events occurring on
the FireFinder-XLS network are displayed at the NCCNT-G.

One NRC is required in each FireFinder-XLS system on the
network. This NRC must reside in the same enclosure as the
PMI/PMI-2.

The NRC supervises the network to ensure proper opera-
tion. Any faults that are detected by the NRC are reported to
the PMI/PMI-2 for annunciation. In addition, the NRC has
diagnostic LEDs that indicate which faults have been found.
The NRC performs ground fault detection on its outgoing
ring port.

Features

The NRC isolates faults to the individual link in trouble. When
wired for Class X (Style 7), network ring communication
continues unaffected.

An RJ-12 monitor jack is included for connection of XNET
diagnostic tools. In addition, RJ-45 and USB jacks are
included for firmware download. These jacks are located on
the front bezel.

Network Ring Card

Installation Instructions
Model NRC

NRC

RESET
POWER
CARD FAIL
TROUBLE

MONITOR

PORT

ETHERNET

USB

Figure 1

NRC Network Ring Card

A6V10322639_b_en_--

Summary of Contents for NRC

Page 1: ... this configuration all events occurring on the FireFinder XLS network are displayed at the NCCNT G One NRC is required in each FireFinder XLS system on the network This NRC must reside in the same enclosure as the PMI PMI 2 The NRC supervises the network to ensure proper opera tion Any faults that are detected by the NRC are reported to the PMI PMI 2 for annunciation In addition the NRC has diagn...

Page 2: ...failure The Trouble LED will illuminate under the following conditions 1 Wire faults open or short in either Port 1 In or Port 2 Out See Figure 5 2 Ground fault on outgoing port Port 2 3 XNET communications problems between the PMI PMI 2 and the NRC PRE INSTALLATION The NRC does not have a network address but it does need to be included in the Zeus configuration INSTALLATION The NRC plugs perpendi...

Page 3: ... NRC software in an installed NRC go to the PMI PMI 2 and press the Menu button select Report press the More Info button and select the PMI Press the Configuration soft key and Touch Appl Rev for the Application Version The NRC software version will be shown with the PMI software version Refer to Figure 3 for an example of a display Figure 3 Typical PMI Display of NRC Software Version Menu Report ...

Page 4: ...4 15 16 17 18 19 20 21 22 23 24 DO NOT USE ONE SLOT OF CC 5 LAST NRC DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE Figure 5 NRC Network Wiring Style 7 Figure 4 NRC Wiring 1 5 2 6 3 7 4 8 TOP HEADER OF TERMINAL BLOCK ON THE CC 5 CC 2 PORT 1 PORT 2 A1 B1 A2 B2 B2 A2 B1 A1 NOTES 1 No EOLR required 2 22 AWG min 12 AWG max 3 3300 feet max per pair between NRCs Shielded or Unshielded twisted pa...

Page 5: ...Power limited to NFPA 70 6 All wires supervised 7 Ground fault detected at 8 5K ohms or less Figure 6 NRC Class B Style 4 Network Wiring Power B connections to the fiber module and monitoring of its trouble contacts are not required as the fiber modules must be installed in the same enclosure as the power supplies that provide them power NRC with NCC See the NCC WAN IOM manual P N 315 049679 for i...

Page 6: ...R PAIR FOM FN2006 FN2007 PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION NRC In Node 1 NRC In Node 2 NRC In Node n FOM FN2006 FN2007 OPTICAL FIBER PAIR OPTICAL FIBER PAIR FOM FN2006 FN2007 OPTICAL FIBER PAIR WIRE CONNECTION WIRE CONNECTION FOM FN2006 FN2007 PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 WIRE CONNECTION WIRE CONNECTION WIRE CONNE...

Page 7: ... FOM FN2006 FN2007 OPTICAL FIBER PAIR FOM FN2006 FN2007 OPTICAL FIBER PAIR WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION FOM FN2006 FN2007 WIRE CONNECTION WIRE CONNECTION PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 r e w o P t u p n I t n e r r u C e n a l P k c a B V 4 2 A m 0 4 1 t n e r r u C V 4 2 l a n i m r e T w e r c S 0 t n e r r u C e n a l P k c a B V 2 6 A m 0 2 t n e r r u C y b d n a...