Installation Instructions
Document No. 129-477
November 15, 2017
Series 2200 Room Units
Page 1 of 4
Product Description
These room units measure temperature in the
occupied space in which they are installed. Models
with display allow users to view the measured
temperature value. A version with temperature
setpoint adjustment is also offered.
The effective sensing and setpoint range is 55°F to
95°F (13°C to 35°C).
These room units can be mounted on electrical
boxes, stud-type mounting brackets, or drywall.
Hardware is included for installation on drywall or on
a 2” × 4” electrical box.
Product Numbers
QAA2212.xWxN
QAA2232.xWxN
QAA2220.xWxN
QAA2235.xWxN
QAA2221.xWxN
QAA22SS.xW
x
N
QAA2230.EWxN
Accessories
AQA2200-INTL
Room Unit Back Plate (10-pack)
563-102 GSKT KIT Room Sensor Insulating
Gasket (10-pack)
(For hollow wall installations)
Caution Notations
CAUTION
Equipment damage or loss of
data may occur if you do not
follow a procedure as
specified.
Expected Installation Time
20 minutes
Item Number 129-477, Rev. JA
Required Tools
•
Sizes 1 and 2 Phillips screwdrivers
•
Small and medium flat-blade screwdrivers
•
1/16-inch
hex key
•
Medium-duty
electric
drill
•
3/16-inch (4.8 mm) drill bit
•
One-inch (25 mm) hole saw
•
Small
level
•
Tape
measure
•
Marker or
pencil
Prerequisites
•
Review these instructions before beginning.
•
Installed: appropriate field wiring within the
maximum wiring run length for the individual
equipment controller. The maximum
recommended length is 100 feet (30 m).
•
All wiring must comply with National Electric
Code (NEC) and local regulations.
Figure 1. Typical Temperature Room Unit.