background image

Required tools

Contents

Assembly

2.5 mm

13 mm

19 mm

0.5 x 3 mm

PZ 5

1  mm

3

3KL84...-.. (500A-800A)
3KA84...-..(630A-1600A)

IEC 60947-1
IEC 60947-3

Hazardous voltage will cause death or serious injury.

 Turn off and

lock out all power supplying this device before working on this device.
Replace all covers before power supplying this device is turned on.

Installation & Maintenace must be carried out by qualified personnel.

NOTICE

DANGER

EN

!

3K.84..-5
M10 x 30

3K.84..M12 x 40

8UC64..

For 3KL8

2P: 2x
3P: 3x
4P: 4x

1x

1x

2x

2P: 4x
3P: 6x
4P: 8x

2P/3P/4P : M8 x 20 (4x)
Torque 10....14 Nm
(Not in scope of supply)

Permissible mounting position

Drilling Plan for mounting plate

L1V30606645004-01 | 01

Center of
Shaft

M8 (4x)

20.5

A

POLE

A

SENTRON SUPERSWITCH

Switch Disconnector Fuse - Size 4

Mounting Details:

All manuals and user guides at all-guides.com

all-guides.com

Summary of Contents for SENTRON SUPERSWITCH 3KL84 Series

Page 1: ...is device is turned on Installation Maintenace must be carried out by qualified personnel NOTICE DANGER EN 3K 84 5 M10 x 30 3K 84 M12 x 40 8UC64 For 3KL8 2P 2x 3P 3x 4P 4x 1x 1x 2x 2P 4x 3P 6x 4P 8x 2P 3P 4P M8 x 20 4x Torque 10 14 Nm Not in scope of supply Permissible mounting position Drilling Plan for mounting plate L1V30606645004 01 01 Center of Shaft M8 4x 20 5 A POLE A SENTRON SUPERSWITCH Swi...

Page 2: ...04 01 02 2 2 3KL831 3KA831 3KL8322 3KA822 Max Lug Size 2 X 185 mm M12 X 40 Max Busbar Size 2 X 50 X 5 mm M12 x 40 Torque 20 Nm to 28 Nm 3KL823 3KA823 5 Neutral Link Max Lug Size 120 mm M10 x 30 2x Torque 10 Nm to 28 Nm Installation of Shaft All manuals and user guides at all guides com ...

Page 3: ...ial 3P Phase Barrier in position 1 2 3 are essential 4P Phase Barrier in position 1 2 3 4 are essential 8UC Coupler depth adjustment Use Depth Setting Templet 8UC6046 2 Pz5 X 13 5 2 1 2 4Nm Panel Door 1 5 4Thk 297 7 325 7 Coupler 7 1 45 5 1 3K 8UC Phase Barrier 3KX84330AE Mounting Details for Front Drive 8UC6414 1BB00 All manuals and user guides at all guides com ...

Page 4: ...sembly L1V30606645004 01 04 2P 3KX84310AF 3P 3KX84310AE 4P 3KX84310AG 2P 3KX84360AF 3P 3KX84360AE 4P 3KX84360AG Terminal cover Rear Cover Rear Phase Barrier Kit 2P 3P 4P 3KX84469AE All manuals and user guides at all guides com ...

Page 5: ... BS 3KX84300HG 3KX84300JG 3KX35821YC 3KX35821YD Fuse Cover Fuse Cover Phase Barrier kit 3KX84409AE Unlocked Locked 2P Add Fuse cover phase Barrier in Position 3 2P Add Fuse cover phase Barrier in Position 4 3P Add Fuse cover phase Barrier in Position 5 2P 3P 4P Replace phase barrier in position 1 with Fuse Cover Phase Barrier Mounting Aux Switch All manuals and user guides at all guides com ...

Page 6: ...utline of Enclosure 40 262 25 440 Dimension Details for SDF in Enclosure Overall Dimensional details 3KL8 2P 3KL8 4P 3P 3KL8 3P N For other Dimensions refer 3P 3P N For other Dimensions refer 3P 3P N 223 5 96 208 400 All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 7: ...E F G H J K L 3KA 2 3KA 3 842 843 844 3KA 2 3KA 3 845 846 40 50 6 10 64 4 58 4 20 40 20 274 314 354 153 9 159 9 For missing Dimension refer 3P N For missing Dimension refer 3P N 3KA8 3P N 3KA8 2P 3KA8 4P All manuals and user guides at all guides com ...