SIMATIC 

Industrie PC 

SIMATIC IPC627C 

Getting Started 

 

  

09/2011 

A5E02669077-03 

Introduction 

 

1

 

Description 

 

2

 

Application planning 

 

3

 

Mounting 

 

4

 

Connecting 

 

5

 

Commissioning 

 

6

 

Troubleshooting 

 

7

 

Dimensional drawings 

 

8

 

Appendix 

 

A

Summary of Contents for SIMATIC IPC627C

Page 1: ..._________ ___________________ ___________________ ___________________ ___________________ SIMATIC Industrie PC SIMATIC IPC627C Getting Started 09 2011 A5E02669077 03 Introduction 1 Description 2 Application planning 3 Mounting 4 Connecting 5 Commissioning 6 Troubleshooting 7 Dimensional drawings 8 Appendix A ...

Page 2: ...nce with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens products may only be used for the applications described in th...

Page 3: ...talling the device with mounting brackets 24 4 3 Installing the device with the vertical mounting kit 24 4 4 Installing the device with the vertical mounting kit for PC port access from the front 27 5 Connecting 29 5 1 Connecting peripherals 29 5 2 Connecting the 100 240 V AC Power Supply 30 5 3 Connecting the 24 V DC power supply 33 5 4 Connecting equipotential bonding 35 6 Commissioning 37 6 1 R...

Page 4: ...Table of contents SIMATIC IPC627C 4 Getting Started 09 2011 A5E02669077 03 A Appendix 45 A 1 Guidelines and declarations 45 A 2 Certificates and approvals 46 A 3 Service and support 49 Index 51 ...

Page 5: ...627C Operating Instructions The operating instructions are available on the supplied Documentation and Drivers CD To view and print the operating instructions run Start and follow the instructions on the screen The operating instructions provide useful information on many topics such as the hardware expansion options modification of the system configuration and technical data Conventions The term ...

Page 6: ...Introduction SIMATIC IPC627C 6 Getting Started 09 2011 A5E02669077 03 ...

Page 7: ... slot COM interface 4 USB ports 2 RJ 45 Ethernet connections IEC connector for AC power supply or connection for DC power supply On Off switch PROFIBUS or PROFINET ports Power supply fan Rear view Battery compartment Device fan Rating label with serial number Steel cover plate for the operator panel interfaces Status display Two part 7 segment display and two LEDs for POST code optional ...

Page 8: ...09 2011 A5E02669077 03 Side view drive side Mounting for WinAC backup battery please use the supplied battery mount without cover for WinAC module Input data of the power supply Drive bay module for hard disks and DVD burner Bottom Connection for equipotential bonding ...

Page 9: ... that the BIOS Setup entry After Power Failure is set to Power On WARNING The on off switch does not isolate the device from the mains When the switch is in 0 position Off the device is still supplied with mains voltage in order to generated the internal auxiliary voltage for the power supply NOTICE Terminate the operating system before shutting down the device with the on off switch otherwise dat...

Page 10: ...press briefly 1x Switch off the PC without shutting down the operating system press and hold more than 4 seconds hardware reset CAUTION Data may be lost when the PC performs a hardware reset WARNING The on off button does not isolate the device from the mains Note By default the BIOS Setup entry After Power Failure is set to Power On This means the device is switched on with the on off switch and ...

Page 11: ... LCD monitor with DVI interface VGA via DVI VGA adapter Compact Flash card Slot for Compact Flash card COM Serial V 24 port USB 2 0 4 ports for USB devices only 2 ports can be simultaneously used as high current ETHERNET 2x RJ 45 Ethernet connection for 10 100 1000 Mbps PROFIBUS MPI MPI interface RS485 electrically isolated optional 9 pin D sub socket optional product model PROFINET CP 1616 onboar...

Page 12: ...rom the numbering performed by the operating system Interfaces for connecting operator panels displays Arrangement of the interfaces LVDS display interface for TFT displays up to 1024 x 768 pixels Access to 2nd LVDS display interface for TFT displays up to 1280 x 1024 USB 2 0 for front Retaining screw for the steel cover plate that covers the interfaces described below I O interface for connecting...

Page 13: ...nts SIMATIC IPC627C Getting Started 09 2011 A5E02669077 03 13 AC power supply Position of the IEC power connector Description IEC power connector to AC power supply of the device The maximum permitted power range is 100 VAC to 240 VAC ...

Page 14: ...nection elements SIMATIC IPC627C 14 Getting Started 09 2011 A5E02669077 03 DC power supply Position of the DC power connector Description Plug connector for DC power supply of the device 24 V DC ground PE ground terminal ...

Page 15: ...O controller IO device cannot be addressed IO controller Duplicate IP address Fast flashing Exception error Diagnostics via Web or SNMP no longer possible SF PROFINET optional Status display for CP 1616 onboard AN Diagnostic information available No communication established Virtual status displays The two virtual CP 1616 LEDs can only be seen in the SIMATIC software and can be scanned via SNMP RU...

Page 16: ... two three color LEDs LED H1 red yellow orange 2 x 7 segment display LED H2 red yellow orange 7 segment display LED H1 LED H2 Power On status display test 88h Orange Orange BIOS self test xxh see BIOS post code Off Off BIOS self test completed 00h Off Off Operating system running or controlled by application 00h Off Off Operating system shutting down Off Off Off ...

Page 17: ...is situation ensure that no moisture condensation develops on or inside the device If condensation has developed on the device wait at least 12 hours before you switch it on 3 2 Unpacking and checking the delivery unit Note the following when unpacking the device Check the delivery unit for any visible transport damage Verify that the shipment contains the complete unit and your separately ordered...

Page 18: ... on the rating plate Rating plate Order number of the device Ethernet addresses The Ethernet addresses of the device are printed on the device and are stored in the BIOS Setup F2 key under Advanced Peripheral Configuration Microsoft Windows Product Key on the Certificate of Authenticity COA The COA label is bonded to the device The Product Key is always required to reinstall the operating system C...

Page 19: ...t the PC receives sufficient ventilation Do not cover the vent slots of the device The device together with its AC power supply fulfils the requirements for fire protected enclosures according to EN 60950 1 Therefore it can be installed without any additional fire protective covering The device with DC power supply does not fulfill the requirements according to EN 60950 1 in the power supply unit ...

Page 20: ... Getting Started 09 2011 A5E02669077 03 3 5 Permitted mounting positions PC mounting positions according to UL60950 1 UL508 EN60950 1 CSA22 2 No 60950 1 An inclination of 20 is permitted for all approved mounting positions Position 1 preferred Position 2 Position 3 desktop ...

Page 21: ...this position The CD drawer opens upward or downward which can lead to mechanical damages in the drawer mechanism NOTICE When using the device in the area of Industrial Control Equipment UL 508 ensure that the it is classified as Open Type A mandatory requirement for approval or operation according to UL 508 is therefore installation of the device in an enclosure certified for UL 508 NOTICE Mounti...

Page 22: ...Application planning 3 5 Permitted mounting positions SIMATIC IPC627C 22 Getting Started 09 2011 A5E02669077 03 ...

Page 23: ...e machine or the system is necessary to avoid endangering persons With this especially the programming configuration and wiring of the inserted I O modules have to be executed in accordance with the necessary risk analysis identified safety performance SIL PL or Cat The intended use of the device has to be secured The correct use of the device has to be verified with a function test on the system ...

Page 24: ...kage Instructions for wall mounting Mounting examples Material Hole diameter Mounting Concrete 8 mm diameter 60 mm depth Dowel 8 mm 50 mm screws 4 mm 50 mm Plasterboard min 13 mm thick 14 mm diameter Tilting dowel diameter 4 mm min length 50 mm Metal min 2 mm thick 5 mm diameter Metal screws diameter 4 mm min length 15 mm WARNING Ensure that the wall is capable of bearing four times the total weig...

Page 25: ...Mounting 4 3 Installing the device with the vertical mounting kit SIMATIC IPC627C Getting Started 09 2011 A5E02669077 03 25 Securing the vertical mounting plate to the device ...

Page 26: ...11 A5E02669077 03 1 Remove the equipotential bonding screw from the device and attach it with the vertical mounting plate 2 Attach the vertical mounting plate with four M4 screws and three M3 screws to the device Note Please note the information in the following section Permitted mounting positions Page 20 ...

Page 27: ...the front SIMATIC IPC627C Getting Started 09 2011 A5E02669077 03 27 4 4 Installing the device with the vertical mounting kit for PC port access from the front The optional vertical mounting kit allows space saving installation of the device Securing the vertical mounting plate to the device ...

Page 28: ... SIMATIC IPC627C 28 Getting Started 09 2011 A5E02669077 03 1 Secure the vertical mounting plate on the device using five M4 screws two screws on top and three not shown in figure on the bottom of the device Note Please note the information in the following section Permitted mounting positions Page 20 ...

Page 29: ... Strictly adhere to the specifications in the manuals for the peripheral devices NOTICE The connected or built in peripherals should not introduce a negative field voltage into the device A negative field voltage greater than 0 5 V to ground on the 3 3 VDC 5 VDC 12 VDC power rail due to a connected or integrated component can prevent normal operation or even destroy the computer When measuring the...

Page 30: ...rm with local mains voltage CAUTION The mains connector must be disconnected to fully isolate the device from mains Ensure easy access to this area A master mains disconnect switch must be installed if the device is mounted in a switch cabinet Always ensure free and easy access to the power inlet on the device or that the safety power outlet of the building installation is freely accessible and lo...

Page 31: ...ns and stipulated IDs of the country where the system is to be installed For the USA and Canada For the United States and Canada a CSA or UL listed power cord must be used The connector must be compliant with NEMA 5 15 120 V AC power supply To be used is a flexible power cord approved to UL and with CSA label and which has the following features Type SJT with three leads min 18 AWG conductor cross...

Page 32: ...nnect the device to the 120 V AC 230 V AC power supply 1 Ensure that the ON OFF switch is in 0 position Off when you plug in the power cord in order to avoid unintentional startup of the device 2 Connect the IEC connector 3 Connecting the power cord to the power socket 4 Fasten the cable with the supplied power plug latch if necessary ...

Page 33: ...h meet the requirements of a safe extra low voltage SELV in addition a protective conductor must be connected The conductors must withstand the short circuit current of the 24 V DC power source so that a short circuit will not damage the cable Only connect cables with a minimum cross section of 1 3 mm2 AWG16 and a maximum cross section of 3 3 mm2 AWG12 NOTICE The 24 V DC power source must be adapt...

Page 34: ...itch off the 24 V DC power source 3 Insert the DC power plug DC 24 V ground protective conductor 4 Fasten the cable with the supplied power plug latch if necessary Note Reverse polarity protection The DC power supply 24V has a mechanism to protect against reverse polarity In the event the 24 V DC lines are reversed 24 V DC nominal 15 20 and connected to ground the device will not sustain any damag...

Page 35: ...n which the device is to be installed The minimum cross section is 5 mm2 The equipotential bonding terminal is necessary to protect the device and improves the discharge of interference generated by external power cables signal cables or cables to the I O modules Connecting equipotential bonding Connect the equipotential bonding terminal on the device large surface large area contact to the centra...

Page 36: ...Connecting 5 4 Connecting equipotential bonding SIMATIC IPC627C 36 Getting Started 09 2011 A5E02669077 03 ...

Page 37: ...e features an off off switch and an on off button By default the BIOS Setup entry After Power Failure is set to Power On This means that the device is turned on using the on off switch If the BIOS Setup entry is set to Stay Off or Last state and the on off switch is set to I ON the device can only be turned on by pressing the on off button Connect the peripherals such as the keyboard mouse monitor...

Page 38: ... become corrupted 4 Automatic restart After you have entered all necessary information and after the operating system setup is completed the PC is automatically restarted and displays the user interface of the relevant operating system When you switch on the PC now the user interface of the operating system or logon dialog of the operating system with Windows Embedded Standard 2009 is automaticall...

Page 39: ...er save mode Press any key on the keyboard The brightness button has been set to dark Increase the screen brightness For detailed information refer to the monitor operating instructions Check whether the power cord has been properly connected to the monitor and to the system unit or to the grounded shockproof outlet Check whether the monitor cable has been properly connected to the system unit and...

Page 40: ...AID software reports the following errors The RAID plug in failed to load because the drive is not installed The Serial ATA plug in failed to load because the driver is not installed correctly The Intel Matrix Storage Console was unable to load a page for the following reason A plug in did not provide a page for the selected device A plug in failed to load RAID is not activated RAID is activated I...

Page 41: ...SIMATIC IPC627C Getting Started 09 2011 A5E02669077 03 41 Dimensional drawings 8 8 1 Dimensional drawings of the device Figure 8 1 Dimensional drawing for mounting with angle bracket ...

Page 42: ...ings of the device SIMATIC IPC627C 42 Getting Started 09 2011 A5E02669077 03 Figure 8 2 Dimensional drawing for mounting without angle bracket NOTICE When mounting devices with optical drives or WinAC backup batteries change the fitting depth ...

Page 43: ...ings 8 1 Dimensional drawings of the device SIMATIC IPC627C Getting Started 09 2011 A5E02669077 03 43 9 9 Figure 8 3 Dimensional drawings for vertical mounting model without DVD burner and without WinAC backup battery ...

Page 44: ...TIC IPC627C 44 Getting Started 09 2011 A5E02669077 03 NOTICE When mounting devices with optical drives or WinAC backup batteries change the fitting depth Figure 8 4 Dimensional drawing for installation with the vertical mounting kit for PC port access from the front ...

Page 45: ... EN 61000 3 3 1995 A1 2001 A2 2005 voltage fluctuation and flicker standards Low voltage directive The devices comply with the requirements of the EC Directive 2006 95 EC Low Voltage Directive Conformance with this directive has been verified according to EN 60950 1 2006 A11 2009 Declaration of Conformity The EC declaration of conformity and the corresponding documentation are made available to au...

Page 46: ... meets DIN ISO 9001 2000 requirements This has been certified by DQS the German society for the certification of quality management systems Q Net certificate no DE 001108 QM Software License Agreement The device is shipped with preinstalled software Please observe the respective license agreements Approvals for the USA Canada and Australia Product safety The following approval is available for the...

Page 47: ...user will be required to correct the interference at his own expense Shielded Cables Shielded cables must be used with this equipment to maintain compliance with FCC regulations Modifications Changes or modifications not expressly approved by the manufacturer could void the user s authority to operate the equipment Conditions of Operations This device complies with Part 15 of the FCC Rules Operati...

Page 48: ... No 142 Process Control Equipment ANSI ISA 12 12 01 Hazardous Location CSA 213 Hazardous Location APPROVED for Use in Cl 1 Div 2 GP A B C D T4A Cl 1 Zone 2 GP IIC T4 Read the following information Note This product must be installed according to the NEC National Electric Code stipulations When used in environments according to class I division 2 see above the device must be mounted in an enclosure...

Page 49: ...MI device Installed additional hardware Installed additional software Tools downloads Please check regularly if updates and hotfixes are available for download to your device The downloads are available on the Internet under After Sales Information System SIMATIC PC PG see above See also Contacts http www siemens com automation partner SIMATIC Guide manuals http www siemens com simatic tech doku p...

Page 50: ...Appendix A 3 Service and support SIMATIC IPC627C 50 Getting Started 09 2011 A5E02669077 03 ...

Page 51: ...ormity 45 Device Unpacking 17 Diagnostics Troubleshooting 39 Dimensional drawings Device 41 Display interfaces 12 DVI VGA port 11 E EMC 47 EMC directive 45 Equipotential bonding terminal 35 ETHERNET interface 11 F First commissioning 38 Front view 7 I Identification data 18 IEC power connector 13 Installing the device 23 Interfaces 11 COM 11 ETHERNET 11 Operator panels 12 PROFIBUS MPI 11 USB 11 VG...

Page 52: ... 30 IEC power connector 13 PROFIBUS MPI interface 11 R Rating plate 18 46 Rear view 7 Restart 38 S Screw mounting the brackets 24 Serial interface 11 Side view 8 Status display 16 Status displays 15 Supply voltage 31 T Transport 17 Troubleshooting FAQs 39 U USB interface 11 V Vent slots 19 Vertical mounting 24 Front interfaces 27 VGA port 11 ...