background image

 

 
 
 
 
 

Powers

®

 Controls  

Technical Instructions

Document No. 155-066P25

TH 192-2

October 26, 2010

 

TH 192 HC Heating/Cooling Room 
Thermostat 

80

60

70

TH0356R1

POWERS

60

50

70

80

 

Description 

The TH 192 HC thermostats are proportional single output, dual setpoint, 2-pipe (high 
air capacity) sensor controllers. Each thermostat includes a wall mounting plate for 
installation in a variety of rough-in terminal boxes. Sensitive bimetals respond to 
temperature change to modulate control air through a flapper nozzle. Two setpoint dials 
are provided. When the supply air pressure changes from 18 to 25 psi (124 to 172 
kPa), the thermostat automatically switches from the cooling to the heating setpoint 
respectively. Air connections are made with 5/32” (4 mm) O.D. plastic tubing, directly to 
the thermostat chassis for retrofit applications or with plug-in adapters (provided with 
the TH 192 rough-in terminal box or optional accessories) which slide into the wall 
mounting plate.  

Features 

 

Direct and reverse acting models for heating and cooling modes. 

 

Separate adjustable temperature setpoint indicating dials for heating and cooling. 

 

Fahrenheit or Celsius setpoint dials. 

 

Highly sensitive bimetal thermostatic element. 

 

Individual field adjustable sensitivity with graduated scale. 

 

Operating mode automatically switches between heating and cooling on change of 
main air supply pressure. 

 

Integral field adjustable limit stops. 

 

Control pressure test port accessible without removing cover. 

 

Easily replaceable thermometer, setpoint dials, filters, and restrictor plate. 

 

Covers available for concealed or exposed thermometers and for either concealed, 
key, or exposed knob adjustment and setpoint indication. 

 

Standard plastic thermostat covers provide Desert Beige or white finish. 

Siemens Industry, Inc. 

Summary of Contents for TH 192 HC

Page 1: ... chassis for retrofit applications or with plug in adapters provided with the TH 192 rough in terminal box or optional accessories which slide into the wall mounting plate Features Direct and reverse acting models for heating and cooling modes Separate adjustable temperature setpoint indicating dials for heating and cooling Fahrenheit or Celsius setpoint dials Highly sensitive bimetal thermostatic...

Page 2: ...imum economy and occupant comfort automatically as seasons change from the heating setpoint 65 68 F 10 20 C to the cooling setpoint 76 80 F 24 27 C TH 192 HC thermostats are available with covers that conceal or expose the setpoint adjustment dials Figure 1 Typical TH 192 HC Thermostat Application Piping TO CONTROLLED DEVICES AIR SUPPLY R1 S TH 192 HC 2 PIPE THERMOSTAT TH0256R1 Figure 2 TH 192 HC ...

Page 3: ...tpoint adjustment cover or key type cover See Table 2 Covers See Table 2 for product number and ordering information on TH 192 HC thermostat covers 1 Is the setpoint adjustment exposed for customer adjustment or concealed to prevent alteration of setting 2 Is the thermometer exposed or concealed 3 Is the setpoint indication exposed or concealed behind cover 4 Is a plastic or zinc cast metal cover ...

Page 4: ...t knobs 2 To order a plastic cover with white finish add the W suffix code To order a metal cover with a white finish add the H suffix code Specifications Control action See Table 1 Operating ranges 45 to 85 F 7 to 30 C Supply air pressure maximum 30 psi 207 kPa Normal air supply pressure Heating 25 psi 172 kPa Cooling 18 psi 124 kPa Sensitivity adjustment 1 to 4 psi F 12 to 50 kPa C Nominal air c...

Page 5: ...rect or reverse acting cooling control In direct acting control an increase in temperature increases the control air pressure and a decrease in temperature decreases the control pressure In reverse acting control an increase in temperature decreases the control air pressure and a decrease in temperature increases the control pressure The TH 192 HC provides two separate bimetal elements one for hea...

Page 6: ...gauge or manometer to measure supply pressure to thermostat Use 30 psi 207 kPa supply through a positioning switch so pressure can be fully variable 2 Determine current change over point Turn cooling dial so cooling and heating control pressures are different Then note the changeover point on the control gauge as the supply pressure changes 3 Remove thermometer for access to changeover adjustment ...

Page 7: ...een the setpoint cam gear teeth Rotate limit stop to its new position Do not pull limit stop any more than necessary to clear the gear teeth Changing the limit stop position one gear tooth changes the limit stop setting by 1 1 3 F 0 7 C Figure 7 TH 192 HC Limit Stop Adjustments Sensitivity Adjustment To change thermostat sensitivity use a flat blade screwdriver to carefully move the sensitivity sl...

Page 8: ...ng Calibration Step 1 Remove cover using 192 632 calibration tool Verify room temperature is between 70 and 80 F 21 and 27 C Step 2 Verify that supply pressure is 18 psi 124 kPa Set cooling dial to room temperature by turning the exposed adjustment knob or using a hex key as shown Allow thermostat to stand for about five minutes to adjust to the new setting Step 3 Moisten needle and insert 192 633...

Page 9: ... room temperature by turning the exposed adjustment knob or using a hex key as shown Allow thermostat to stand for about five minutes to adjust to the new setting Step 3 Moisten needle and insert 192 633 test gauge and needle adapter in the test port Read control pressure Step 4 If control pressure does not read 7 to 8 psi 48 to 55 kPa turn calibration screw using 192 632 calibration tool or 1 8 3...

Page 10: ...y gently pushing down the bimetal Figure 9 Accessing Output Pressure Test Port Excessive air leakage from exhaust port on left side of thermostat Supply and return line connection Connections are interchanged or connection to port is incorrect As required Chassis Tube Connector and Restrictor Plate Replacement 1 Remove thermostat chassis from wall Terminal does not have a ball check valve NOTE You...

Page 11: ...ck connected 1 8 NPT male 142 0373 1 1 2 diameter compound gauge 0 30 psig 0 200 kPa bottom connected 1 8 NPT male Replacement for use with 192 633 142 0426 Chassis tube connector replacement kit with mounting screws material for 10 thermostats included 192 525 Restrictor plate replacement kit with filters and gasket material for 10 thermostats included 192 321 Plug in adapters for quick thermosta...

Page 12: ...e IL 60089 4513 USA Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Service Parts Continued Description Part Number Replacement thermometer kits brown packages of 5 Scale Range Thermostat Model 45 to 85 F 192 775 10 to 30 C TH0443R1 Model 3 and Up 192 776 45 to 85 F 192 786 10 to 30 C TH0442R1 Models 1 and 2 192 ...