Air sampling smoke detection system
TITANUS 3000

Quick Guide for Commissioning

1 Installation

§

  Connect power (24V)

§

  Connect outputs for info- (AL1), pre- (AL2) and mainalarm (AL3) as well as “fault”

(switchover relay contacts)

§

  Connect reset input

§

  Connect ext. input “night” (LowSens., 2.Sens) (if required)

§

  Connect pipe system or test pipe

2 Set 

Up

Set DIP switches on pcb “basis E597.1” and on pcb “interface K3I 100” according to
tables below:

Selectable Settings

ext. input “LowSens”:

function “

day

switch combination on 

basis

 pcb       (

G,F,E

)

passive or not used

function “

night

switch combination on 

interface

 pcb  (

1,2,3,4

)

active (24V)

Algorithms

switch

1 /G

2 /F

3 /E

4

DO1151A

DO1153A

DO1161A

OFF

OFF

OFF

OFF

1)

1)

1)

ON

OFF

OFF

OFF

real estate  3% slow *)

1%              *)

0,8%             *)

OFF

ON

OFF

OFF

equipment    3% med.

0,5%

0,35%

ON

ON

OFF

OFF

equipment    3% fast

0,3%

0,25%

OFF

OFF

ON

OFF

life safety   1,5% med.

0,3% -> 0,2%

0,15%

ON

OFF

ON

OFF

life safety   1,5% fast

1)

0,15 -> 0,1%

OFF

ON

ON

OFF

life safety   1,5% slow

1)

1)

ON

ON

ON

OFF

detector test mode

detector test mode

detector test mode

1) = invalid combination; algorithm is set to *)

Air flow monitoring

switch

delay time

switch

range

A

B

C

D

OFF

ON

short

30 s

ON

OFF

small

I

ON

OFF

middle

2 min.

 (standard)

OFF

ON

middle

II

ON

ON

long

15 min.

OFF

OFF

large

III

       (standard)

OFF

OFF

very long

1 h

ON

ON

very large

IV

Fault

Modus

switch

switch

J

H

I

OFF

Fault not latching               

(standard)

OFF

OFF

normal operation 

(standard)

ON

Fault latching until reset

OFF

ON

direct mode normal on

ON

ON

direct mode high on

Atmospheric pressure compensation

R34

MP1 (+)

MP2 (-)

see correction table for atm.pressure

or

2,50 V 

(standard)

Fire & Security Products

Siemens Building Technologies Group

Reviews: