background image

TPS3 03 DC

For DC Photovoltaic Applications

Surge Protective Device

DC Voltage Photovoltaic System Instructions – Do Not Use for AC Voltage Installation

Save These Instructions - This manual contains important instructions that shall be followed 
during installation and maintenance of the power system.

User Manual - Canada

Summary of Contents for TPS3 03 DC

Page 1: ...ive Device DC Voltage Photovoltaic System Instructions Do Not Use for AC Voltage Installation Save These Instructions This manual contains important instructions that shall be followed during installation and maintenance of the power system User Manual Canada ...

Page 2: ...age rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance wit...

Page 3: ... overvoltages TPS3 03 DC is parallel connected such that circuit ampacity is unlimited Proper installation is important to maximize performance Please follow steps outlined herein These instructions are not intended to replace national or local codes Follow all applicable electrical codes to ensure compliance UL 1449 Third Edition Sept 2009 2008 NEC Article 285 and CSA C22 1 CEC generated substant...

Page 4: ...n to the conductors Similar TPS3 03 DC models have demonstrated 200kA Short Circuit Current Ratings SCCR including leads on AC power systems and have been rated for Type 1 applications NEC Article 285 This device features internal overcurrent and overtemperature protection that will disconnect effected surge suppression components at the end of their useful life but will maintain power to the load...

Page 5: ...require additional sealing o rings etc see Figure 5 6 Connect conductors as appropriate 1000V models require insulated sleeving included SeeFigure 4 forwire outs short straightas possible seeFigure4 7 Label or mark conductors as appropriate ground green positive red negative black 8 Make sure system is grounded per NEC or CEC and is clear of hazards or faults before energizing 9 Energize and confi...

Page 6: ... During these fault conditions any electrical equipment including an SPD may be subjected to voltages which exceed their designed ratings This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an ungrounded power system CONDUCTING DIELECTRIC AND OR HI POTENTIAL TESTING WILL CAUSE INTERNAL DAMAGE TO TPS3 UNIT Do not perf...

Page 7: ...uct at Siemens option A Return Material Authorization number RA must be given by the company prior to the return of any product Returned products must be sent to the factory with the transportation charges prepaid In addition the company also warranties unlimited replacement of modular and component parts within the warranty period previously described The company specifically disclaims all other ...

Page 8: ...North Service Road East Oakville ON L6H 0H6 SPD Hotline 888 333 3545 info purgethesurge ca European Authorized Representative Obelis s a Boulevard Général Wahis 53 1030 Brussels BELGIUM Tel 32 2 732 59 54 Fax 32 2 732 60 03 E Mail mail obelis net ...