S4090-0002-7
Features
Individual Addressable Relay Module (Relay
IAM):
IDNet addressable control for use with Simplex
®
fire
alarm control panel models 4100ES, 4100U, 4010ES
and 4010
A single addressable point provides control and status
tracking of a Form “C” contact
Low power latching relay design allows IDNet
communications to supply both data and module power
Compact, sealed construction:
Enclosed design minimizes dust infiltration
Mounts in standard 4” (102 mm) square electrical box
Screw terminals for wiring connections
Visible LED flashes to indicate communications
Optional covers are available to allow LED to be
viewed after installation
UL listed to Standard 864
Description
IDNet Relay IAMs
allow fire alarm control panels to
control a remotely located Form “C” contact using IDNet
addressable communications for both data and module
power. Typical applications would be for switching local
power for control functions such as elevator capture, or
control of HVAC components, pressurization fans,
dampers, etc. Relay status is also communicated requiring
only one device address.
Product Selection
Model
Description
4090-9002
Relay IAM
Optional Trim Plates
Model
Description
4090-9801
For semi-flush
mounted box
Trim plate, galvanized
steel, with LED viewing
window; includes
mounting screws
4090-9802
For surface
mounted box
*
This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7300-0026:223 for allowable values and/or conditions concerning material presented in this
document. It is subject to re-examination, revision, and possible cancellation. Accepted for
use – City of New York Department of Buildings – MEA35-93E. Additional listings may be
applicable; contact your local Simplex product supplier for the latest status. Listings and
approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products
Westminster.
5
6
7
8
1
2
3
4
SIMPLEX TIME RECORDER CO.
4090-9002
RELAY IAM
INST. INSTR. 574-184
DATE CODE:
1
+IDNET
- IDNET
1
2
3
4
5
6
7
8
N.C.
N.O.
COM
-
-
-
4090 Series IDNet Relay IAM Package
(shown approximately 1/2 size)
Specifications
Communications
4100ES, 4100U, 4010ES or 4010
IDNet communications, 1 address per
device
Relay IAM Power
Supplied by IDNet communications
Contact Ratings*
(not rated for incandescent switching)
Type
Form C, SPDT
Power-Limited
2 A @ 24 VDC, resistive
from listed
fire alarm
supply
1 A @ 24 VDC, inductive
Nonpower-Limited 0.5 A @ 120 VAC, resistive
* Provide circuit fusing and transient suppression as
required per application. DC inductive loads can typically
be diode suppressed; 120 VAC loads may require RC
networks or varistors, depending on device type. Refer to
Installation Instructions 574-184 for additional information.
Wire Connections
Screw terminals for in/out wiring,
18 to 14 AWG wire (0.82 to 2.08 mm
2
)
IDNet Wiring
Reference
Up to 2500 ft ( 762 m) from control
panel
Up to 10,000 ft ( 3048 m) total wiring
distance (including T-Taps)
Compatible with Simplex 2081-9044
Overvoltage Protectors
Dimensions
4-
1/8” H x 4-1/8” W x 1-3/8” D
(105 mm x 105 mm x 35 mm)
Housing Material
Black thermoplastic
Mounting Plate
Sheet metal, galvanized
Temperature
Range
32° to 120° F (0° to 49° C),
intended for indoor operation
Humidity Range
Up to 93% RH at 100° F (38° C)
Multi-Application Peripherals
UL, ULC Listed; FM, CSFM,
IDNet™ Communicating Devices
and MEA (NYC) Approved*
Model 4090-9002 Relay IAM