© 2014- 2017 Tyco Fire Protection Products. Specifications and other information shown were current as of publication and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
579-1034
Rev. F
R
IMPORTANT:
When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that
requires the immediate attention of all occupants.
LOCATION REFERENCE:
Location and quantity of appliances required must conform to the applicable local standards and
guidelines (the National Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm
Systems; the appropriate model building codes, etc.) and specific requirements of the Local Authority Having Jurisdiction (AHJ).
These notification appliances are not intended for installation within hazardous locations as defined by the National Electrical
Code (NEC) or NFPA.
SAFETY:
Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety
precautions and instructions may result in loss of life and property due to non-functioning notification appliances. Some
notification appliances use high voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the
electrical power for the notification appliance circuit is disconnected at the control panel before installing, repairing, or internally
adjusting any notification appliances. Even with electrical power removed, some notification appliances (such as visible strobes)
store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH
EXPOSED CIRCUITRY.
Mounting instructions
1. Select the mounting location and install the electrical box using screws suitable for the mounting surface. See
for mounting
and location information.
2. Bring the building wiring through the rectangular opening in the backplate.
3. Connect the building wires to the backplate. See the wiring section on
page 2
4. Secure the backplate to the electrical box using the provided hardware. Install with the writing
Install this side up
at the top. Use a
torque wrench to tighten the screws to 12-15 inch-pounds. Do not over-tighten the screws.
5. Attach the cover to the appliance.
6. Set the appliance settings. See
page 3
.
7. Attach the assembled appliance onto the backplate.
UL listed TrueAlert ES indoor product identification reference
Type
Colors
Models
Operation
Wall Mount Horn
Audible Only (AO)
• Red
• White
Complete
appliances:
49AO-WRF
49AO-WRF-BA
49AO-WRS-BA
49AO-WWF
49AO-WWF-BA
49AO-WWS-BA
49AO-WRS
49AO-WRQ
Components:
49AO-APPLW
49AO-APPLW-BA
Backplate:
49MP-AVVOWR
49MP-AVVOWW
Covers:
49AOC-WRBLNG
49AOC-WRFEU
49AOC-WRFIRE
49AOC-WRS
49AOC-RBLANK
49AOC-WWBLNG
49AOC-WWFEU
49AOC-WWFIRE
49AOC-WWS
49AOC-WBLANK
These appliances provide an audible (AO) warning of an alarm
condition when activated from the control panel of a compatible
UL/ULC Listed, Simplex Fire Alarm System.
Note:
For information about TrueAlert ES appliance testing, see
TrueAlert ES Addressable Appliances testing and applications guide
(579-1049).
Kit contents
Appliance x 1
Cover x 1 Backplate x1 with 8-32 1 inch mounting screws x 2, and 6-32 1 inch mounting screws x 2.
Not included
Electrical box 1-1/2 inch (38.1 mm) minimum depth required: single gang, double gang, or 4 inch (101.6 mm) square.
Figure 1. Mounting instructions
NFPA 72 requires that
the device is not
less than 80 in. (203.2 cm)
and not greater than
96 in. (243.8 cm) above
the finished floor.
Single gang, double gang, or
4 in. (101.6 mm) square electrical box
Backplate
Appliance cover
Building wire
Screws: Use 8-32 screws for a 4 in. (101.6 mm) square electrical box
Use 6-32 screws for a single or a double gang electrical box
Appliance
TrueAlert ES Addressable
Indoor A/O Notification Appliances
Installation Instructions