© 2014- 2017 Tyco Fire Protection Products. Specifications and other information shown were current as of publication and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.

579-1034

Rev. F

R

IMPORTANT:

 When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that 

requires the immediate attention of all occupants.

LOCATION REFERENCE:

 Location and quantity of appliances required must conform to the applicable local standards and 

guidelines (the National Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm 
Systems; the appropriate model building codes, etc.) and specific requirements of the Local Authority Having Jurisdiction (AHJ). 
These notification appliances are not intended for installation within hazardous locations as defined by the National Electrical 
Code (NEC) or NFPA.

SAFETY:

 Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety 

precautions and instructions may result in loss of life and property due to non-functioning notification appliances. Some 
notification appliances use high voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the 
electrical power for the notification appliance circuit is disconnected at the control panel before installing, repairing, or internally 
adjusting any notification appliances. Even with electrical power removed, some notification appliances (such as visible strobes) 
store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH 
EXPOSED CIRCUITRY.

Mounting instructions

1. Select the mounting location and install the electrical box using screws suitable for the mounting surface. See 

Figure 1

 for mounting 

and location information.

2. Bring the building wiring through the rectangular opening in the backplate. 
3. Connect the building wires to the backplate. See the wiring section on 

page 2

.

4. Secure the backplate to the electrical box using the provided hardware. Install with the writing 

Install this side up

 at the top. Use a 

torque wrench to tighten the screws to 12-15 inch-pounds. Do not over-tighten the screws.

5. Attach the cover to the appliance.
6. Set the appliance settings. See 

page 3

.

7. Attach the assembled appliance onto the backplate.

UL listed TrueAlert ES indoor product identification reference

Type

Colors

Models

Operation

Wall Mount Horn 

Audible Only (AO)

• Red 
• White

Complete 
appliances: 

49AO-WRF
49AO-WRF-BA
49AO-WRS-BA
49AO-WWF
49AO-WWF-BA
49AO-WWS-BA
49AO-WRS
49AO-WRQ

Components:

49AO-APPLW
49AO-APPLW-BA

Backplate:

49MP-AVVOWR
49MP-AVVOWW

Covers:

 

49AOC-WRBLNG
49AOC-WRFEU
49AOC-WRFIRE
49AOC-WRS
49AOC-RBLANK
49AOC-WWBLNG
49AOC-WWFEU
49AOC-WWFIRE
49AOC-WWS
49AOC-WBLANK

These appliances provide an audible (AO) warning of an alarm 
condition when activated from the control panel of a compatible 
UL/ULC Listed, Simplex Fire Alarm System.

Note: 

For information about TrueAlert ES appliance testing, see 

TrueAlert ES Addressable Appliances testing and applications guide

 (579-1049).

Kit contents

Appliance x 1

Cover x 1 Backplate x1 with 8-32 1 inch mounting screws x 2, and 6-32 1 inch mounting screws x 2.

Not included

Electrical box 1-1/2 inch (38.1 mm) minimum depth required: single gang, double gang, or 4 inch (101.6 mm) square.

Figure 1. Mounting instructions

NFPA 72 requires that
the device is not
less than 80 in. (203.2 cm)
and not greater than
96 in. (243.8 cm) above
the finished floor.

Single gang, double gang, or 
4 in. (101.6 mm) square electrical box

 Backplate

Appliance cover

Building wire

Screws: Use 8-32 screws for a 4 in. (101.6 mm) square electrical box
              Use 6-32 screws for a single or a double gang electrical box

Appliance

TrueAlert ES Addressable 
Indoor A/O Notification Appliances 
Installation Instructions 

Summary of Contents for TrueAlert ES Series

Page 1: ... the mounting surface See Figure 1 for mounting and location information 2 Bring the building wiring through the rectangular opening in the backplate 3 Connect the building wires to the backplate See the wiring section on page 2 4 Secure the backplate to the electrical box using the provided hardware Install with the writing Install this side up at the top Use a torque wrench to tighten the screws...

Page 2: ...agrams for the driving compatible fire alarm control panel for further instructions Notification appliances are rated using an individual module label Maintain the correct polarity on the terminal connections Terminals 1 and 2 can each accommodate two wires one wire going in and one wire going out to the next appliance TrueAlert SLC wiring connections are supervised and power limited These applian...

Page 3: ... Setting the DIP switch address Setting the horn configuration switch Figure 4 Setting the appliance configuration Certain options for the horn can be configured directly on the appliance using the Configuration switch CFIG1 on the back of the appliance See Figure 4 AO Settings Position 1 Configuration Control OFF to enable Local Audible control positions 2 7 below ON for Panel control Position 2 ...

Page 4: ...92 4 31 Max 94 4 93 9 Low volume setting 17 Min 84 1 83 6 23 86 7 86 6 31 Max 89 1 88 6 Notes 1 The coded category covers both Temporal and March time cadences 2 Reverberant dBA measurements are a minimum UL rating based on sound power level measurements made in UL s reverberant test chamber 3 High and low volume settings are configured with DIP switch CFIG1 on the controller 4 If you install the ...

Reviews: