TH1310WF
Installation Guide
Smart floor heating
thermostat (3600 W)
3) The thermostat offers 2 temperature regulation modes:
F mode (default):
Regulates the floor temperature by means of an
external temperature sensor with the possibility to limit ambient
temperature.
A mode:
Regulates ambient temperature with the possibility to limit floor
temperature by means of an external temperature sensor.
4) Maximum limit of the ambient temperature (F mode)
Thermostat limits floor heating so as not to exceed the set ambient
temperature limit
5) Maximum floor temperature limit (A mode)
The thermostat limits floor heating to the set temperature to ensure it does
not exceed the selected limit. Ideal for protecting engineered wood floors.
6) Minimum floor temperature limit (A mode)
The thermostat limits the minimum temperature of the floor in order to
keep it at a comfortable temperature.
This parameter can only be used when a floor sensor is connected to the
thermostat.
7) Assigning the auxiliary output (A mode):
The thermostat provides an auxiliary output that has three functions which
are set from the user settings.
15 sec function:
Short cycle auxiliary output (15 seconds). Used for a heater
controlled through an electronic relay (SSR).
15 min function:
Long cycle auxiliary output (15 minutes).
Used for a heater
controlled through an electromechanical relay or equipped with a fan.
In the 15 sec and 15 min functions,
the thermostat controls the ambient
temperature with the floor. Once the floor temperature has reached its
limit, if the desired ambient temperature is not reached, the auxiliary output
activates the heating device to reach the set temperature. (The auxiliary
output acts as a second heating stage.)
EXP function:
Auxiliary output to connect several heating floors
(TR1310 sold separately).
OFF function (default):
Disables the auxiliary output.
INSTALL YOUR THERMOSTAT
Unlock and lift the thermostat
cover.
Warnings
Before starting the installation of your new thermostat, please
make sure that the breakers for your heating system are off at
the main electrical panel!
The installation of this thermostat must be performed by a
certified electrician and comply with the national and local
electrical codes and regulations.
Line
Load
Floor heating
1
Connect the sensor.
(Only for control applications in
F mode or with floor limit.)
3
Connect the heating floor by using the
wire connectors load / line located on
the back of the thermostat. Connect the
ground wire to the screw in the
electrical box intended for this purpose.
2
Use the screws to secure
the thermostat to the
electrical box.
4
Replace the cover and lock.
5
Power up the thermostat.
After performing a test sequence,
the thermostat should display the
floor temperature. If not, refer to
the trouble- shooting guide in
this manual.
6
Sensor
USER SETTINGS
Increasing or lowering the temperature
To adjust the temperature, press or . The requested temperature
will blink to confirm the new setpoint.
Get the setpoint to its minimum and hold the button for 10 seconds
to access the menu.
Press the or button to change the setting.
All of the thermostat's settings can be set through the Neviweb app.
However, if you have not created your account and wish to change the
temperature format or the control cycle, you need to:
The following table lists the settings that can be changed directly on
the thermostat.
You can change more settings through the Neviweb application.
10 sec.
Press the and buttons simultaneously to save and go
to the next parameter. Continue to press until the end of the
list to exit the menu.
USER SETTINGS
(continued)
Settings which can be modified directly on the device:
Control
Load
Display
Max Floor
Max Air
Min Floor
Aux
Sensor
Load power
0 watt to 3600 watt
Temperature format
°C or °F (default: °C)
Control mode
A (Air), F (Floor) (default: F)
Maximum floor temperature
(Only visible in A mode)
5 °C to 36 °C (default: OFF)
Maximum limit of the ambient
(Only visible in F mode)
5 °C to 36 °C (default: OFF)
Minimum floor temperature limit
(Only visible in A mode)
5 °C to 36 °C (default: OFF)
Floor sensor
10K or 12K (default: 10K)
Assignment of auxiliary output
OFF, EXP, 15 sec, 15 min (default: OFF)
Name
Parameters & settings
Display
** To disconnect a thermostat from a network, refer to the disconnection
procedure on the back of this guide.
When installing your floor heating system: add a second
sensor in the floor whose tip can be stored in the
thermostat housing. This additional sensor can be
plugged in and used as a replacement without
altering your floor heating system.
Sensor
Leaving the standby mode
When the thermostat is on standby, press any button to turn back ON the
thermostat. The thermostat will resume operation under its last program
settings.
A thermostat that is placed on standby before a power failure will be on
standby by default when power is restored.
7
8