background image

REQUIRED TOOLS:

2.0  Aviation Snips  •  #2 Flathead Screwdriver  •  #1 Phillips Screwdriver  •  

Adjustable Wrench  •  Pliers  •  Electric Drill with 7/64 in. (0.28 cm), 3/32 in. (0.24 

cm), 1/4 in. (0.64 cm) and 3/8 in. (0.95 cm) Drill Bits  •  Hammer  •  Center Punch

INSTALLING THE HUMIDIFIER: 

3.0 

CAUTION: 

When selecting a location for the humidifier, make sure the spray 

will not impinge or accumulate on any fan, limit controls, resistance heating coils or 

heating/air coils. 

3.1  Select a location where the air will push the 

spray mist away from the humidifier. 
3.2 

Mount the humidifier on the warm air 

plenum only

, with the nozzle pointing up in the 

direction of airflow (see Figure 1, left). On narrow 

plenums, mount the humidifier on the narrow side. 
3.3  If there is not enough room on the warm air 

plenum, mount the humidifier further downstream 

on the warm air duct, away from the heating and 

cooling coil. 
 3.4  If it is necessary to mount the spray nozzle 

further away from the humidifier (in order to move 

the nozzle further into the air stream for better 

absorption), remove the nozzle adapter and 45° 

fitting from the solenoid valve. Use the fittings 

supplied in the parts bag to relocate the nozzle 

using 1/4 in. (0.64 cm) copper tubing (not supplied). 

(See Figure 2, below, left.) 

CAUTION: 

Do not allow 

copper tubing to come in contact with sharp edges 

or surfaces that may cause wear on the tubing. 

 3.5  Tape the template (provided) on the warm air 

plenum in the location selected for the humidifier. 

CAUTION: 

Make sure the template is level. 

 

3.6 Center punch and 

drill four 7/64 in. (0.28 cm) 

mounting holes, as shown 

on the template. 

DANGER: 

Make sure you are not 

cutting or drilling into air 

conditioning or electrical 

accessories. 

 

3.7  Drill a 3/8 in. (0.95 

cm) hole in the center of the 

shaded area of the template; 

cut a rectangular opening 

(staying within the shaded 

area), as indicated. 
 

3.8  Install the drain cup 

over the nozzle; attach it with 

a #6 x 3/8 in. (0.95 cm) sheet 

metal screw. (See Figure 3, 

left.) 
3.9  Install 3/16 in. (0.48 

cm) ID tubing on the copper 

humidifier drain and run it to a 

waste drain. (An occasional 

drip from the drain tube when 

the humidifier is operating is 

normal.) 
3.10 Attach the humidifier 

with four #8 sheet metal 

screws. 

INSTALLING THE INSPECTION WINDOW: 

NOTE: 

A clear, plastic window is supplied with the humidifier to be mounted on the 

ductwork. This allows you to observe whether the humidifier is functioning properly, 

and whether there is water impinging on parts or surfaces within the system. 

4.0  Select a mounting location on the ductwork where the humidifier spray 

nozzle can be viewed easily.
4.1  Drill a 3/8 in. (0.95 cm) hole and cut a 4-1/2 in. x 2 in. (11.43 cm x 5.08 

cm) rectangular opening. 

DANGER: Make certain that you are not drilling or 

cutting into any air conditioning or electrical accessories during installation. 

4.2  Position the window over the opening; mark and center-punch the two 

mounting hole locations. 
4.3  Drill the two 3/32 in. (0.24 cm) mounting holes. 
4.4  Attach the window with two #6 phillips-head screws (not provided). 

On/Off Light

Replaceable

Stainless Steel Nozzle

Cup Prevents Drip

Into Furnace

FIGURE 3

IMPORTANT

THIS HUMIDIFIER MUST BE INSTALLED BY A QUALIFIED CONTRACTOR. 
DO NOT INSTALL ON ANY SYSTEM WITH WATER PRESSURE LESS THAN 

40 PSI (275.79 KPA).
Installation on water systems with hardness ratings greater than 7 grains is 

not recommended. Such installations can result in nozzle blockage, dripping, 

erratic spray patterns and other maintenance problems. Hardness above 7 

grains will also produce dust from solids in the water supply, which will be 

distributed throughout the home. Consult your municipal water provider 

before continuing. 

SAFETY PRECAUTIONS

READ THESE PRECAUTIONS AND ALL INSTALLATION INSTRUCTIONS 

BEFORE INSTALLING THE HUMIDIFIER. 
NOTE: 

Skuttle Mfg. Co. (aka Skuttle Indoor Air Quality Products) assumes no 

responsibility under warranty if installer does not follow these instructions and 

safety precautions. 

•  Do not install a humidifier where the heating temperatures can exceed 200°F 

(93.33°C). Excessive temperatures will damage the humidifier, possibly 

causing an overflow condition and water damage to the home. 

•  Do not install a humidifier where the surrounding temperature can be 32°F 

(0°C) or colder. Frozen water will damage the humidifier and burst the supply 

pipe, resulting in home damage. 

•  Do not cut or drill into any air conditioning or electrical accessories during 

humidifier installation. 

DANGER: Electrocution is possible if you come 

in contact with a live wire; blindness can occur if refrigerant contacts 

your eyes. 

•  When the humidifier is installed in an area where water damage could occur, 

connect the humidifier’s overflow provision to a suitable drain pan. 

•  For above-ceiling installations, always install a drain safety pan, plumbed to 

a suitable drain. 

•  For initial recommended humidistat settings, refer to Table 1, below. 

(Because relative humidity affects people differently, these settings can 

be raised or lowered slightly to suit personal comfort levels.) 

CAUTION: 

Setting the humidistat higher than the recommended setting can cause 

condensation, resulting in home damage. 

If excessive moisture appears 

on windows or walls, reduce the humidistat’s humidity setting enough to 

eliminate condensation. If the situation continues, turn off the humidifier’s 

water source until condensation is gone. 

•  Make sure the installation, wiring and plumbing of the humidifier comply with 

local codes, ordinances and regulations. 

Outside 

Temperature

Recommended 

Setting

Outside 

Temperature

Recommended 

Setting

-20ºF (-28.89ºC)

Low

10ºF (-12.22ºC)

Med

-10ºF (-23.33ºC)

Low

20ºF (-6.67ºC)

High

0ºF (-17.78ºC)

Med

Above 20ºF (-6.67ºC)

High

TABLE 1

INSTRUCTIONS

INSTRUCTIONS FOR HEAT PUMPS AND HIGH-EFFICIENY FURNACES

1.   Remove the screw holding the two wires eyelet on thermal switch.
2.   Remove the two screws holding the thermal switch in housing.
3.   Remove eyelet from the two wires.
4.   Strip 3/8" to 1/2" coating from the two wires.
5.   Follow the wiring diagram for heat pump and high-effiency furnaces.

GENERAL INFORMATION: 

1.0  This humidifier puts moisture into the home by spraying a fine mist of water 

into the warm air plenum, which is carried into the living area by the duct system. 
1.1  When wired as recommended, the humidifier will operate only when the 

furnace blower is operating and the humidistat is calling for humidity. 
1.2  The nozzle capacity (flow) is rated at 40 psi (275.79 kPa). This capacity 

varies according to line pressure, as shown in Table 2, below. Select the nozzle 

that delivers the required spray in accordance with the pressure in your area. 

Nozzle Size

Volume Capacities per Hour at Various Water Pressures

40 psi 

(275.79 kPa)

60 psi

(413.69 kPa)

80 psi

(551.58 kPa)

100 psi

(689.48 kPa)

125 psi

861.85 kPa)

.37 (1.40)

.37 gph 

(1.40 lph)

.45 gph 

(1.70 lph)

.55 gph 

(2.08 lph)

.60 gph

(2.27 lph)

.70 gph

2.65 lph)

.50 (1.89)

.50 gph

(1.89 lph)

.60 gph

(2.27 lph)

.70 gph

(2.65 lph)

.80 gph

(3.03 lph)

.85 gph

(3.22 lph)

.75 (2.84)

.75 gph

(2.84 lph)

.89 gph

(3.37 lph)

1.10 gph

(4.16 lph)

1.20 gph

(4.54 lph)

1.40 gph

(5.30 lph)

TABLE 2 

(See example on back, at end of document)

 

gph = gallons per hour; lph = liters per hour

1.3  If the water pressure is excessive, a pressure regulator valve will be 

necessary to obtain the proper volume of moisture. 

Skuttle Model 592

24-Volt Spray Humidifier

INSTALLATION INSTRUCTIONS

101 Margaret Street, Marietta, OH 45750

Phone: (800) 848-9786  •  Fax: (740) 373-9565

Email: techservice@skuttle.com  •  Web: www.skuttle.com

                                    

BEGIN READING ON OPPOSITE PANEL

 

Part No. 000-0756-233

Rev. 11/13 HBP

Continued on back...

Humidifier 

Warm Air

Cold Air

FIGURE 1

Standard 1/8 in. (0.32 cm) MIP 

by 1/4 in. (0.64 cm) OD Comp.

(Fittings Included)

Standard 1/8 in. (0.32 cm) FIP 

by 1/4 in. (0.64 cm) OD Comp.

(Fittings Included)

1/4 in. (0.64 cm)

Copper Tubing 

(Not Supplied)

FIGURE 2

DO NOT INSTALL IN LINED DUCTWORK OR ON DUCT BOARD. 

Reviews: