background image

Specifications

Model

HRS200-A

m

-46-

m

S

Cooling method

Air-cooled refrigeration

Refrigerant

R410A (HFC) 

Refrigerant charge

kg

1.65

Control method

PID control

Ambient temperature/Altitude

*

1, 7

°

C

Temperature: –5 to 45, Altitude: less than 3000 m

Cir

culating fluid system

Circulating fluid

*

1, 2

Tap water, 15% Ethylene glycol aqueous solution, Deionized water

Set temperature range

*

1

°

C

5 to 35

Cooling capacity

*

3, 7

kW

20.5

Heating capacity

*

4

kW

5.3

Temperature stability

*

5

°

C

±

1

Pump 
capacity

Rated flow (Outlet)

L/min

45 (0.45 MPa)

Maximum flow rate

L/min

130

Maximum pump head

m

50

Minimum operating flow rate

*

6

L/min

25

Tank capacity

L

25

Circulating fluid outlet, circulating fluid return port

Rc1 (Symbol F: G1, Symbol N: NPT1)

Tank drain port

Rc3/4 (Symbol F: G3/4, Symbol N: NPT3/4)

Automatic

fluid fill 

system

(Standard)

Supply side pressure range

MPa

0.2 to 0.5

Supply side fluid temperature

°

C

5 to 35

Automatic fluid fill port

Rc1/2 (Symbol F: G1/2, Symbol N: NPT1/2)

Overflow port

Rc1 (Symbol F: G1, Symbol N: NPT1)

Fluid contact material

Metal

Stainless steel, Copper (Heat exchanger brazing), Brass, Bronze

Resin

PTFE, PU, FKM, EPDM, PVC, NBR, POM, PE, NR

Electrical system

Power supply

3-phase 460 VAC (60 Hz)

Allowable voltage range 

±

10% (No continuous voltage fluctuation)

Applicable earth leakage
breaker (Standard)

Rated current

A

30

Sensitivity of leak current mA

30

Rated operating current

*

5

A

14.2

Rated power consumption

*

5

kW(kVA)

9.1 (11.4)

Noise level (Front 1 m/Height 1 m)

*

5

dB(A)

75

Waterproof specification

IPX4

Accessories

Alarm code list sticker 1 pc. (English),

Operation Manual (for installation/operation) 1 pc. (English),

Y-strainer (40 meshes) 25A, Barrel nipple 25A, 

Anchor bolt fixing brackets 2 pcs. (including 6 M8 bolts)

*

8

Weight (dry state)

kg

214

Thermo-chiller 

Air-cooled 460 V Type

Standard Type

How to Order

Option 1

Nil

None

A

With caster adjuster-foot

K

*

1

With fluid fill port

*

1   This is a manual fluid fill port that is different from the automatic 

fluid fill port. Fluid can be supplied manually into the tank without 
removing the side panel. (Fluid can be supplied manually for 
models without option K if the side panel is removed.)

Power supply

46

3-phase 460 VAC (60 Hz)

Pipe thread type

Nil

Rc

F

G (With Rc-G conversion fitting)

N

NPT (With Rc-NPT conversion fitting)

Cooling method

A

Air-cooled refrigeration

Cooling capacity

200

20.5 kW

HRS 200 A

46

S

*

1   When the ambient temperature or circulating fluid 

temperature is 10

°

C or below, refer to "Operation at 

low ambient temperature or low circulating fluid tem-

perature" (page 14).

*

2   Use fluid in condition below as the circulating fluid.

Tap water: Standard of The Japan Refrigeration And 

Air Conditioning Industry Association (JRA GL-02-

1994)

15% ethylene glycol aqueous solution: Diluted with 

clean water, without any additives such as antisep-

tics. 

Deionized water: Electric conductivity 1 

μ

S/cm or 

higher (Electric resistivity 1 M

·cm or lower)

*

3   

q

 Ambient temperature: 32

°

C, 

w

 Circulating fluid: 

Tap water, 

e

 Circulating fluid temperature: 20

°

C, 

r

 

Circulating fluid flow rate: Rated flow, 

t

 Power sup-

ply: 460 VAC

*

4   

q

 Ambient temperature: 32

°

C, 

w

 Circulating fluid: 

Tap water, 

e

 Circulating fluid flow rate: Rated flow, 

r

 Power supply: 460 VAC

*

5   

q

 Ambient temperature: 32

°

C, 

w

 Circulating fluid: 

Tap water, 

e

 Circulating fluid temperature: 20

°

C, 

r

 

Load: Same as the cooling capacity, 

t

 Circulating 

fluid flow rate: Rated flow, 

y

 Power supply: 460 VAC, 

u

 Piping length: Shortest

*

6   Fluid flow rate to maintain the cooling capacity. If the 

actual flow rate is lower than this, install a bypass 

piping.

*

7   If the product is used at altitude of 1000 m or higher, 

refer to “Operating Environment/Storage Environ-

ment” (page 13) Item 13 “

*

  For altitude of 1000 m or 

higher.” 

*

8   The anchor bolt fixing brackets (including 6 M8 bolts) 

are used for fixing to wooden skids when packaging 

the thermo-chiller. No anchor bolt is included.

Option 2

Nil

None

W

SI unit only

(Pending for UL Standards)

INFORMATION

HRS200

 Series

18-E700

Summary of Contents for HRS200 Series

Page 1: ...ort 1 This is a manual fluid fill port that is different from the automatic fluid fill port Fluid can be supplied manually into the tank without removing the side panel Fluid can be supplied manually...

Page 2: ...ay panel Eye bolt M12 4 places 715 556 851 1114 428 421 278 110 108 Overflow port Rc1 Automatic fluid fill port Rc1 2 Fluid level indicator Signal cable entry Hole 40 Grommet with membrane Power cable...

Page 3: ...Thermo chiller automatic fluid fill port 3 User s equipment To wastewater collection pit Fluid supply Circulating fluid return port Overflow port Tank drain port 4 5 2 2 2 2 1 1 6 Ensure that the ove...

Page 4: ...p when this function is operated o lamp Equipped with a power failure auto restart function which restarts the product automatically after stopped due to a power failure Lights up when this function i...

Page 5: ...optional accessories depending on the accessory the allowable current of 24 VDC devices will be reduced Refer to the operation manual of the optional accessories for details Item Specifications Conne...

Page 6: ...830 401 118 1538 HRS200 A 46 SW The circulating fluid temperature and pressure are displayed in SI units MPa C only If this option is not selected a product with a unit selection function will be prov...

Page 7: ...ed by user it is necessary to lift the thermo chiller by a forklift or sling work Carefully read the procedure manual included with this kit before performing the installation Part no Applicable model...

Page 8: ...ectric conductivity target 5 0 to 45 0 S cm Set range of electric conductivity hysteresis 2 0 to 10 0 S cm Operating temperature range Circulating fluid temperature 5 to 60 C Power consumption 400 mA...

Page 9: ...now Protection Hood Stainless steel snow protection hood for air cooled chiller According to the mounting direction of the snow protection hood the ventilation from the fan can be selected from four d...

Page 10: ...ment Element Parts List No Description Material Qty Note q Body PC PP 1 w Element 1 PP 1 e Extension piece Stainless steel 2 Conversion from NPT to Rc r Handle 1 When H is selected t Sealant tape PTFE...

Page 11: ...rm code 2 Operable items Operation start stop Circulating fluid temperature setting Alarm sound stop Key lock Key operation sound ON OFF Digital display brightness adjustment Alarm sound ON OFF HRS CV...

Page 12: ...0 C Circulating fluid return temperature T2 297 K 24 C Circulating fluid temperature difference iT 4 K T2 T1 Conversion factor minutes to seconds SI units 60 s min 1 Refer to the next page for the typ...

Page 13: ...1 kg L or using current unit system weight volume ratio 1 kgf L Specific heat C 4 19 x 103 J kg K or using current unit system 1 x 103 cal kgf C 2 Values for density and specific heat change slightly...

Page 14: ...ulating fluid spec ified in Operation at low am bient temperature or low cir culating fluid temperature 5 In locations where condensation may occur 6 In locations which receive direct sunlight or radi...

Page 15: ...glycol aqueous solution 15 wt 5 to 10 Ethylene glycol aqueous solution 15 wt Be sure to read this before handling the products For safety instructions and tempera ture control equipment precautions re...

Page 16: ...nd tempera ture control equipment precautions refer to the Handling Precautions for SMC Prod ucts and the Operation Manual on the SMC website https www smcworld com HRS200 Series Specific Product Prec...

Page 17: ...mS cm 100 1 to 300 1 v v Chloride ion Cl mg L 50 or less v Sulfuric acid ion SO4 2 mg L 50 or less v Acid consumption amount at pH4 8 mg L 50 or less v Total hardness mg L 70 or less v Calcium hardnes...

Page 18: ...rformed or will stop Power supply voltage is not within the rated voltage range of 10 In case the water level inside the tank is reduced abnormally Circulating fluid temperature is too high Compared t...

Page 19: ...Safety Instructions Be sure to read the Handling Precautions for SMC Products M E03 3 and Operation Manual before use...

Reviews: