background image

QUICK START

125 A - 630 A

ATyS 

t

1

3

2

Max.

0.51 in.

13 mm.

125 A

160 A

200 A

250 A

315 A

400 A

500 A

630 A

35

35

50

95

120

185

2x95

2x120

-

-

-

-

-

-

2x32x5

2x40x5

50

95

120

150

240

240

2x185

2x300

25

25

25

32

32

32

50

50

M8

M8

M8

M10

M10

M10

M12

M12

73.46

/8.3

73.46

/8.3

73.46

/8.3

177.02

 /20

177.02

 /20

177.02

 /20

354.04

/40

354.04

/40

115.06

/13

115.06

/13

115.06

/13

230.13

/26

230.13

/26

230.13

/26

398.30

/45

398.30

/45

FRAME B3

FRAME B4

FRAME B5

Minimum cable section Cu (mm

2

)

Recommended Cu busbar cross-section (mm²)
Maximum Cu cable cross-section (mm²)
Maximum Cu busbar width (mm)
Type of screw

Recommended tightening torque (

lb.in

/N.m)

Maximum tightening torque (

lb.in

/N.m)

 Preliminary operations 

Check the following upon delivery and after removal of the 

packaging:

- Packaging and contents are in good condition

- The product reference corresponds to the order

- Contents should include:

 

Qty 1 x ATyS t

 

Qty 1 x Emergency handle and fixing clip

 

Quick Start instruction sheet

 Warning 

 

Risk of electrocution, burns or injury to persons and / 

or damage to equipment.

This Quick Start is intended for personnel trained in the 

installation and commissioning of this product. For further 

details refer to the product instruction manual available on 

the SOCOMEC website.
• This product must always be installed and 

commissioned by qualified and approved personnel.

• Maintenance and servicing operations should be 

performed by trained and authorised personnel.

• Do not handle any control or power cables connected to 

the product when voltage may be, or may become 

present on the product, directly through the mains or 

indirectly through external circuits.

• Always use an appropriate voltage detection device to 

confirm the absence of voltage.

• Ensure that no metal objects are allowed to fall in the 

cabinet (risk of electrical arcing).

-  For 125 - 160 A (Uimp = 8 kV). Terminations must respect 

a minimum of 8 mm clearance from live parts to parts 

intended to be earthed and between poles.

-  For 200 - 630 A (Uimp = 12 kV). Terminations must respect 

a minimum of 14 mm clearance from live parts to parts 

intended to be earthed and between poles.

Failure to observe good enginering practises as well as to 

follow these safety instructions may expose the user and 

others to serious injury or death.

 

Risk of damaging the device

In case the product is dropped or damaged in any way it is 

recommended to replace the complete product.

 Accessories

• Bridging bars and connection kits.
• Control voltage transformer (400 VAC   230 VAC).
• DC power supply (12/24 VDC   230 VAC).
• Phase barriers.
• Terminal shrouds.
• Terminal screens.
• Auxiliary contacts (Additional).
• Padlocking in 3 positions (I - O - II).
• Lockout accessories (RONIS - EL 11 AP).
• Door escutcheon frame.
• ATyS D10 Interface (remote display).
• Voltage sensing kit.
• Sealable cover.
• RJ45 cable for ATyS D10.

For further details refer to the product instruction manual 

under chapter "Spares and Accessories"

www.socomec.com

To download, brochures, catalogues 

and technical manuals: 

https://www.socomec.com/range-

automatic-transfer-switches_

en.html?product=/atys-t-atys-g_

en.html

549647C

Motorised Source Changeover Switch

Automatic Transfer Switching Equipment

EN

STEP 1

 

Cabinet / Back 

Plate Installation

STEP 3

 

COMMAND / 

CONTROL 

terminal 

connections

STEP 2

 

Power Terminal 

Connections 

STEP 4

 

Power SUPPLY and 

ATS Controller 

Terminal 

Connections

STEP 5

 

CHECK

STEP 6

 

PROGRAMMING 

STEP 7A

 

AUT Mode 

(Automatic Control)

STEP 7C

 

Manual Mode

STEP 7B

 

AUT Mode 

(Remote Control)

STEP 7D

 

Padlocking Mode

Installation and Commissioning

Installation

500 A, 630 A.

125 A to 400 A.

Power Terminal Connections

M8 Type Z

M8

  Caution: ensure 

that the product is 

installed on a flat 

rigid surface.

Recommended 

orientation

OK

OK

STEP 1

STEP 2

Clip for 

storage of 

the 

emergency 

handle

Mounting

Removing covers

To be connected using terminal lugs, rigid or flexable 

busbars.

Summary of Contents for ATyS t

Page 1: ... 125 160 A Uimp 8 kV Terminations must respect a minimum of 8 mm clearance from live parts to parts intended to be earthed and between poles For 200 630A Uimp 12 kV Terminations must respect a minimum of 14 mm clearance from live parts to parts intended to be earthed and between poles Failure to observe good enginering practises as well as to follow these safety instructions may expose the user an...

Page 2: ...trol wiring ATS Controller ATS Module Control Inputs Fixed ATS Module Output Contact Product available Remote interface RJ45 to ATyS D10 ATS Voltage Sensing Input Source supply I S I Phase Neutral S I Phase S I Phase 575 VAC ph ph max S I Neutral Phase 332 VAC ph n max ATS Power Supply Input I Power supply I L N Power supply I N L 208 277 VAC 20 50 60 Hz Recommanded to use SOCOMEC Voltage Sensing ...

Page 3: ...The ATyS t includes an Auto Configuration feature to detect the mains voltage and frequency nominal values phase rotation and neutral position and saves them in the ATS controller Note Before configuring the nominal values ensure that the product is properly wired verified and ready for commissioning It is imperative that the network supply is available and that the wiring to the ATyS t voltage se...

Page 4: ...X 1 30 33 1 30 33 1 30 33 1 30 33 1 67 42 5 1 48 37 5 1 67 42 5 1 48 37 5 3x Ø4 8 mm 19 20 21 22 5 4 2 1 3 13 17 18 14 15 12 16 8 9 6 7 10 11 W U CA 5 43 138 6 50 165 X T Fix M F C Fix 7 38 187 5 0 83 21 9 04 229 5 0 49 12 5 0 30 7 5 0 34 8 6 0 64 16 2 0 64 16 2 0 34 8 6 1 MANUAL Mode LED indication Yellow steady light when in Manual Mode 2 AUTO Mode LED indication Green steady light when in Auto ...

Reviews: