background image

N

ET

YS

INSTALLATION AND OPERATING MANUAL

NETYS PR

1000-3000 VA

Summary of Contents for NETYS PR

Page 1: ...NETYS INSTALLATION AND OPERATING MANUAL NETYS PR 1000 3000 VA ...

Page 2: ......

Page 3: ...INSTALLATION AND OPERATING MANUAL NETYS PR 1000 3000 VA IOMNETPRXX00 GB_02 03 2008 ...

Page 4: ...ions contained within Keep this manual at hand for rapid and easy consultation Reproduction of any part of this manual is forbidden without the manufacturer s consent The information and drawings contained herein may be changed without prior notice and are not binding upon the manufacturer SOCOMEC UPS retains the full and exclusive ownership rights over this document Only a personal right to utili...

Page 5: ...etys PR 3000 VA 17 8 CONNECTIONS 18 9 CONFIGURATION AND START UP 20 9 1 Configuration of the output voltage battery expansion units 20 9 2 Configuration from mimic panel 20 9 2 1 Output voltage configuration menu 20 9 2 2 Battery expansion configuration menu after Output Voltage configuration 20 10 MODES OF OPERATION 21 10 1 Switching the UPS on 21 10 2 Switching the UPS off 21 10 3 Normal mode 21...

Page 6: ...ITALIANO ...

Page 7: ...an territory the warranty shall be limited to the cover of the parts used to repair the fault The warranty shall not apply in the following cases Failures due to fortuitous circumstances or force majeure lightning floods etc Failures due to negligence or improper use use outside tolerance limits temperature humidity ventilation elec tric power supply applied load batteries Insufficient or inadequa...

Page 8: ... tasks If at any time a hazard condition is created during use disconnect the mains power supply if possible through the control panel upstream of the unit and shutdown the UPS completely following the appropriate procedure When assembling and replacing the battery the UPS should always be switched off and disconnected from the mains power supply Do not dispose of batteries in a fire the battery m...

Page 9: ...f the load current exceeds this value have qualified personnel connect the UPS to an industrial type IEC 309 compliant power supply mains with a current of correct dimensions for the UPS power rating Netys UPS is intended for commercial and industrial use it is not recommended for use in medical applications that are essential to the survival of the patient Use the UPS in accordance with the techn...

Page 10: ...UPS is the constant monitoring of the power supply which duly filtered and stabilised on models with AVR and if considered suitable is used to supply consumers In cases of a mains failure or if the mains is considered to be outside limits accepted by the load the inverter the heart of the UPS is activated immediately Drawing on the power stored in the batteries the inverter generates a voltage tha...

Page 11: ...ure between 0 C and 40 C and humidity less than 90 non condensing the best tem perature to guarantee the longest battery life is 15 20 C Ensure that the environment where the UPS will be installed is not dusty and leave a space of at least 20 cm around it to allow for adequate ventilation and access to the rear panel Make sure not to place the UPS or any other heavy object on the cables Checkthatt...

Page 12: ... ON OFF switch Press for 3 seconds Buzzer silence and self test mode button Button to confirm Configuration mode button Operating mode LED LED green lit NORMAL MODE mains OK LED green flashing NORMAL MODE AVR active LED yellow flashing wide range input mode Battery LED Flashing battery disconnected Lit battery needs to be replaced Battery Mode LED Low flashing BATTERY MODE mains absent or abnormal...

Page 13: ...NGLISH IOMNETPRXX00 GB_02 13 FRONTVIEW 5 Fan fault Fan failure Abnormal battery recharge Overtemperature stop Shortcircuit Abnormal output voltage 5 1 ALARM INDICATION 5 2 FAILURE INDICATION LED lit LED flashing LED flashing ...

Page 14: ...rotections RJ45 Fuse RS232 serial port RS232 serial port Slot for optional communicationboards USB port EmergencyPowerOff NTPprotections RJ45 Fan Air vents Fan Air vents Input socket Battery connection for external extension Battery connection for external extension Output sockets Fuse 1000VA 1500VA 2000VA ...

Page 15: ...2 15 6 REARVIEW RS232 serial port USB port EmergencyPowerOff Battery connection for external extension Output sockets NTPprotections RJ45 Fan Air vents Output sockets Input socket with fuse Output socket Slot for optional communicationboards 3000VA ...

Page 16: ... 16 IOMNETPRXX00 GB_02 7 1 1 7 1 5 7 1 7 7 1 2 7 1 4 7 1 6 7 1 8 7 1 MIGRATION KIT FROMTOWERTO RACK FOR NETYS PR 1500 2000VA MIGRATION KIT FROMTOWERTO RACK 7 7 1 3 Front bracket for rack assembling mode Rear bracket for rack assembling mode ...

Page 17: ...0 VA ENGLISH IOMNETPRXX00 GB_02 17 7 2 2 7 2 MIGRATION KIT FROMTOWERTO RACK FOR NETYS PR 3000VA MIGRATION KIT FROMTOWERTO RACK 7 7 2 1 7 2 3 WARNING The lateral brackets supplied MUST be mounted Rack fixing accessories ...

Page 18: ...ed By combining the UPS with one or maximum two battery expansion units back up times of up to 60 minutes may be obtained DANGER Make sure that the safety switch on the battery expansion unit is in the OFF position during the connection procedure Place the battery expansion unit beside the UPS on the side with no air vents Connect the battery expansion unit to the UPS using the special cable suppl...

Page 19: ...PRXX00 GB_02 19 8 CONNECTIONS UPS Battery External battery IN 230V Use the server s supply cord IEC 320 OUT 230V 6 x IEC320 1500VA 2000VA 3000VA OUT 230V 8 x IEC320 OUT 230V 16 A full load IN 230V Battery connection for external extension ...

Page 20: ...1 2 9 2 CONFIGURATION FROM MIMIC PANEL OutputVoltage and Battery Expansion parameters are also settable by mimic panel following the below procedure 9 2 1 Output voltage configuration menu Press button for 3 seconds to start the procedure first current set ting 230V LED flashing Push button again second current setting 240V LED flashing Push button again third current setting 220V LED flashing Pre...

Page 21: ... on the frontpanelremainsonpermanently Inthismode theloadsarepoweredfromthemainspowersupplyeitherdirect ly or through the AVR stabiliser which intervenes in cases of voltage peaks The batteries are constantly recharged 10 4 BATTERY MODE The UPS switches automatically to this operating mode when mains power fails spikes or lengthy black outs or if the mains is at a value considered to be dangerous ...

Page 22: ...ctinglaserprintersthatgenerateabsorptionpeaksliabletocauseoverloadsontheUPS 10 6 SELFTEST In NormalMode when the button is pressed for more than five seconds a procedure is run to check battery and inverter operation If everything is working properly the UPS automatically returns to Normal Mode if not the test is suspended and the battery failure is reported through the Battery failure LED If the ...

Page 23: ... Java Shutdown Client technology RS232 interface HID UPS management based on Windows embedded service USB interface NetVision Web SNMP manager for UPS control over LAN withTCP IP protocol Allows remote shutdown through Java Shutdown Client technology Web SNMP card BMS possibility to integrate the UPS with BMS Building Management Systems JBUS protocol 11 2 RS232 INTERFACE Communication with the ser...

Page 24: ...the UPS Troubleshooting for minor problems Problem Possible cause Solution The UPS works in battery mode even if mains power is available Poor connection to the input mains Check the connection of the cable to the UPS and to the mains outlet The mains voltage is out of range No solution because mode of opera tion is correct Input protection triggered blown fuse or automatic switch Replace the inpu...

Page 25: ...1500MT PR2000MT PR3000RT Power VA 1000 1500 2000 3000 Power W 700 1000 1340 2100 Mechanical characteristics PR1000MT PR1500MT PR2000MT PR3000RT Dimensions WxDxH mm 87 x 385 x 235 2 x 87x 415 x 220 2 x 87x 415 x 220 87 x 585 x 440 Dimensions WxDxH mm 2U RM 435 x 415 x 87 435 x 415 x 87 440 x 585 x 87 Net weight kg 9 6 18 19 31 5 Communication PR1000MT PR1500MT PR2000MT PR3000RT Communication interf...

Page 26: ...omec si SPAIN C Nord 22 Pol Ind Buvisa E 08329 Teià Barcelona Tel 34 93540 7575 Fax 34 93540 7576 info socomec aron com www socomec aron com UNITED KINGDOM Units 7 9 Lake Side Business Park Broadway Lane South Cerney Cirencester GL7 5XL Tel 44 0 1285 863300 Fax 44 0 1285 862304 uk ups sales socomec com IN ASIA CHINA No 1Yuanda Road Haidian District Beijing 100089 Golden Resources Times Shopping Ma...