SOCOMEC - Ref.: 541 613 B
RESYS
066
B
INSTALLATION
Installation must only be carried out by qualified per-
sonnel.
Before installation, disconnect from the power supply.
Connect the device as shown on the diagram below
(N.B. some optional functions do not need to be cabled).
When installing the device, make the connections
between the relay and the differential toroid as short as
possible.
Do not put relay cables or the differential toroid beside
power conductors.
Do not place differential toroids close to sources of
intense magnetic fields.
>
Note
This differential relay conforms to type A which trips
sinusoidal alternating currents and pulsed currents,
whether they are applied suddenly or change slowly.
This product is also immune to interference.
This relay must be installed in accordance with the
regulations currently in force.
The device must be checked periodically to see that it
complies with the regulations.
>
Test Function
Bargraph blinks
“Trip” LED and “Alarm” relay activated
>
Continuous monitoring
Test OK
NO
NO
Toroid input short circuit
NO
NO
Relay/Toroid connection break
YES
NO
>
Activation of “Test” button
(Press (>1s) or external button)
Test OK
YES
YES
Toroid input short circuit
NO
NO
Relay/Toroid connection break
YES
NO
>
Pre-alarm function
When the measured current exceeds 50% of the thres-
hold value, the pre-alarm relay changes state (if selec-
ted in this mode). Automatic reset to its original state if
30% lower than pre-set threshold.
>
Description of front panel
1 - Adjustment/setting I∆n
2 - Green “ON” LED
3 - “RESET” button
4 - Red “TRIP” alarm LED
5 - LED bargraph (% x I∆n)
6 - Configuration DIP switch
(x 4)
7 - “TEST” push-button
8 - Time setting
• With I∆n set at 30 mA, the timing is set at 0 (instanta-
neous) and can not be modified.
• The pre-configured factory setting for the device is 30
mA/0s. These values can be modified as needed for
operation. A plastic seal is provided with the device
in order to lock the protective cover and ensure the
settings.
RESYS P40
EN
Operating instructions
Earth leakage relay
A and AC types
>
Configuration (DIP switch)
Switch
Relay configuration
A
B
AL1
AL2
0
0
Positive security
Positive security
1
0
Negative security
Pre-alarm (neg. security)
0
1
Negative security*
Positive security*
1
1
Negative security
Pre-alarm (pos. security)
C
Storage mode
1
Automatic reset
0
Storage mode*
D
Toroidal transformer ratio
1
600 : 1 > Socomec* toroid
0
1000 : 1 > other manufacturers
* factory configuration
• (negative security: relay excited in case of alarm/positive secu-
rity: relay not excited in case of alarm).
TermINAL cONNecTION dIAgrAm
L1
L2
L3
N
E
Toroid
50 m* maxi
Alarm 2 (AL2)
or pre-alarm
Alarm 1
(AL1)
6 7 8 9 10 11 12
1 2 3 4 5
A2
(-)
A1
(+)
re
se
t
test
50 m maxi
The output relays are shown in the non-excited state (for
example, as if the auxiliary supply was not present)
The protective earth wire must not pass through the toroid. For
single-phase applications, only the phase and the neutral must
pass through the toroid.
* Cabling: For distances > 1 m, use a twisted pair for connection
between the relay and the toroid.
>
Troubleshooting
If the product is not working properly, check that is it properly
connected.
dImeNSIONS
48
9
80
22
48
32
TecHNIcAL SPecIFIcATION
• Us Supply (6, 7) :
12 - 125 VDC (85 - 110 % de Us)
115, 230 VAC (85 - 115 % de Us) (see terminal connection
diagram). All AC supplies are galvanically isolated frm
toroid, TEST and RESET inputs.
• Frequency :
50 / 60 Hz (AC supply)
• Isolation :
Over-voltage cat. III
• Impulse voltage:
(1,2 / 50 µS) IEC 60664
2,5 kV (115 VAC supply)
4 kV (230 VAC supply)
• Consumption (max.) :
6 VA (AC supply) - 5 W (DC supply)
• Measured residual current:
0 to 30 A (15 / 400 Hz) via external toroid with ratio 600 : 1
or 1000 : 1 connected to terminals 4 and 5)
• Sensitivity I
∆
n :
30, 100, 300, 500 mA, 1, 3, 5, 10, 30 A (adjustable)
• Tripping accuracy:
80 - 90 % de I∆n
• Reset value:
≈ 85 % of trip threshold
• Time delay I
∆
s :
0*, 60, 150, 300, 500, 800 ms, 1, 4, 10 s
(adjustable) *time set for “0” or “Instantaneous” < 25 ms
for residual current @ 5 x I∆n.
• Reset time:
< 2 s (after eliminating the auxiliary power supply)
• Indication des Leds :
- Power supply present::
green
- Bargraph :
3 x green (30, 50 and 70% of the threshold value set)
- Tripping:
red
• Operating temperature:
-20 to +55 °C
• Storage temperature:
-30 to +70 °C
• Relative humidity:
+95 %
Outputs
- Number of contacts::
1 changeover contact relay +
1 single contact relay
- Type of contact :Alarm 1 (8, 9, 10)
AC1 (250 V) 8 A (2000 VA)
AC15 (250 V) 2,5 A
DC1 (25 V) 8 A (200 W)
Alarm 2 / Pre-alarm (11, 12)
AC1 (250 V) 6 A (1500 VA)
AC15 (250 V) 4 A
DC1 (25 V) 6 A (150 W)
- Lifetime:
150.000 operations at nominal load
- Dielectric voltage:
2 kV AC (rms) IEC 60947-1
- Impulse voltage:
4 kV (1,2 / 50 µS) IEC 60664
• Remote Test and Reset (1, 2, 3) :
With N.O. contact (e.g. push-button)Min. contact closure
time: ≥ 80 ms
• Box :
black, self-extinguishable, NORYL UL94 VO (front
panel and clip in ABS)
• Weight:
120 g (DC auxiliary power supply) / 200 g (AC
auxiliary power supply)
• Installation:
encastré, cut-out 45 x 45 mm
• Connecting terminal:
≤ 2,5 mm
2
flexible
• Certification:
conforms to IEC 60755, 60947, 61000-4-2, 61000-4-3,
61000-4-4, 61000-4-5, 61000-4-6, 61000-4-12, 61000-4-
16, 61543.
CE compliant.
>
References :
Auxiliary power supply
Reference
12-125 VDC
4942
3602
115 VAC
4942
3711
230 VAC
4942
3723
> Accessories
Toroids (C.T.) :
∆IC - Ø 15 mm
4950
6015
∆IC - Ø 30 mm
4950
6030
∆IC - Ø 50 mm
4950
6050
∆IC - Ø 80 mm
4950
6080
∆IC - Ø 120 mm
4950
6120
∆IC - Ø 200 mm
4950
6200
∆IC - Ø 300 mm
4950
6300
Use of toroids ≥ 120 mm: setting I∆n min = 300 mA
Other toroids: consult us
cuTOuT
45
45