USER GUIDE

ups

520 Rackmount

750 VA, 1050 VA, 1425 VA, and 2250 VA

A

Company

Summary of Contents for 1050 VA

Page 1: ...USER GUIDE ups 520 Rackmount 750 VA 1050 VA 1425 VA and 2250 VA A Company ...

Page 2: ...t generated by the UPS This UPS generates no more than 1 mA of current To limit the total leakage current to 3 5 mA the load leakage must be limited to 2 5 mA The three wire receptacle that you plug the UPS into must have a good low impedance ground protec tive earth connection to provide a safe path for leakage current ...

Page 3: ...u p s 5 2 0 Rackmount 750 VA 1050 VA 1425 VA and 2250 VA User Guide STM 0405A Copyright 1998 Best Power All rights reserved A Company ...

Page 4: ...n you return a SOLA 520 Rackmount to the factory for any reason please use the original packing material in which your unit was shipped to you You may be responsible for repair charges for damaged units which are not packed in SOLA packing material If you have discarded the original packing material please call the nearest SOLA office so that we can ship new packing material to you If you have any...

Page 5: ...bleshooting 10 Replacing the Batteries 11 Battery Replacement Instructions 12 Communication Port 13 DB 9 Pinouts 14 Specifications 14 Appendix A Adjusting Voltage Settings 16 Warranty 18 SOLA Australia Offices 19 SOLA Best Offices 20 Trademarks Windows is a registered trademark of Microsoft Corporation All other brand and product names are trademarks or registered trademarks of their respective ho...

Page 6: ...ore often CAUTION Whenever the SOLA 520 Rackmount is On there may be dangerous voltage present at the unit s outlets This is true because the unit s battery supplies power even if the unit is not plugged into the wall outlet The unit contains dangerous voltages To reduce the risk of electric shock install in a temperature controlled and humidity controlled indoor area free of conductive contaminan...

Page 7: ...uts and sudden increases in power It also provides spike suppression and line noise filtering to protect your equipment Front panel LEDs and an audible alarm keep you aware of the unit s status Use the drawings on this and the following page to identify features of the unit Line Buck boost Battery Power Load or Battery Charge see page 7 Alarm Program Button On Standby Button D C B A ...

Page 8: ...1050 and 1425 F ront P anel 4 SOLA Never Stops Innovating 1 Status Indicators 2 On Standby Button 3 Alarm Program Button 4 Battery Access Panel 5 Circuit Breaker 6 RJ11 RJ45 Jacks 7 Input Power Connector 8 Aust 10 A Outlets 9 DB9 Communication Port 10 BestDock Access Panel 8 ...

Page 9: ...rting angle brackets available as standard rack hardware from electronics distributors below the intended rack location for the SOLA 520 Rackmount Secure the shelf or brackets at both the front and back of the rack using bolts nuts and washers Carefully lift the unit onto the shelf or brackets and slide it into the rack as shown below The mounting holes on the sides of the front panel should match...

Page 10: ... lights will come on and remain on If the unit beeps or if the top light does not remain on even though input power is available from the wall outlet go to the Troubleshooting section 4Switch off the equipment you want to protect and plug each load into the outlets on the back of the SOLA 520 Rackmount 5Switch on the protected equipment one load at a time If the UPS beeps an alarm when you start y...

Page 11: ...ems You should have an electrician check your nominal line voltage and determine if the problem is due to a Surge high voltage or Brownout low voltage Changing the setting without this knowledge could make the problem worse Steady SOLA 520 is operating on AC line Blinking SOLA 520 is bucking or boosting input AC line A B C D A B C and D indicate battery charge A B C D 75 100 B C D 50 75 C D 25 50 ...

Page 12: ...tching to battery Buck Automatically decreases high input power to prevent the unit from switching to battery Table 1 Symbols and LEDs AC LINE Green LINE CORRECTION Green BATTERY MODE Yellow OVERLOAD D LED Yellow WARNING D LED Yellow Number of Beeps What It Means 1 every 10 seconds Line Loss The unit is on battery power See Table 3 for more information 2 every 10 seconds Low Battery Alarm The unit...

Page 13: ...low the instructions enclosed with the CD ROM BestDockTM The SOLA 520 Rackmount BestDock communication slot accepts optional communication cards like the internal BestLink SNMP WEB adapter The insertion of a card into the BestDock communication slot replaces the normal communication channel from the SOLA 520 Rackmount DB 9 Communication Port The DB 9 port becomes the connection point for configuri...

Page 14: ... 2 Loose plug 3 Tripped circuit breaker 4 Power cord failure 1 Wait for power to return 2 Make sure the power cord is connected 3 Reset the circuit breaker 4 Phone SOLA Service Green LINE LED flashes Input voltage is high or low Nothing The UPS is correcting the input voltage You may require an electrician to investigate the reason for the input voltage deviation Yellow BATTERY LED on Green LINE L...

Page 15: ...r pockets these objects could fall into the UPS Never allow any tool to contact both a battery terminal and the UPS cabinet or another battery terminal Do not lay tools or metal parts on top of batteries To ensure continued superior performance of your UPS and to maintain proper charger operation you must replace the UPS batteries with the same number and type of batteries These batteries must be ...

Page 16: ... with the protected equipment attached Option You may switch off and unplug the protected load equipment from the SOLA 520 Rackmount Then turn off the SOLA 520 Rackmount and disconnect the line cord 3Use the drawings below to identify the location on the battey pack in the model SOLA 520 Rackmount that you have 4Remove the screws holding the exterior battery access panel 1 to the front panel Set t...

Page 17: ... earlier to re install the interior panel to the battery chamber and the exterior panel to the front panel 11 If you followed the option in step 2 Reconnect the line cord to the SOLA 520 Rackmount and turn the unit on 12 Reconnect the load equipment Switch on the protected load equipment one piece at a time Communication Port The SOLA 520 Rackmount is plug and play compatible with Windows 95 The S...

Page 18: ...the UPS switches to battery power Pin 9 Unused Contacts consist of open collector circuits capable of switching up to 30 VDC 6 mA resistive load Specifications SOLA reserves the right to change specifications without prior notice Line Transient Protection Passes ANSI IEEE C62 41 Category A testing Safety Compliance TÜV GS listed AS3260 EMC Compliance CISPR 22 Class B Vfg 243 91 46 92 B EN55022 CE ...

Page 19: ...el 35 A AC input Plug Cord Information 750 VA CEE 22 recessed plug 1050 VA CEE 22 recessed plug 1425 VA CEE 22 recessed plug 2250 VA CEE 19 recessed plug AC Output Distribution 750 VA 3 Aust 10 A 1050 VA 4 Aust 10 A 1425 VA 4 Aust 10 A 2250 VA 4 Aust 10 A Load Compatibility Can support 100 power factor corrected switch mode power supply load Audible Noise 45 dBa at one meter except 2250 VA model w...

Page 20: ...ues will change to the default values and any previous changes you have made will be lost If you have questions contact the nearest SOLA office or call National Service and Repair Centre on 1800 034 401 except Melbourne 9768 3105 Melbourne only Do not change voltage settings when unit is operating on batteries To change the values follow these steps 1 Press the button shown until LEDs on the front...

Page 21: ...d Continue pressing and releasing the button until the proper LEDs are lit 4 Once the correct LEDs are lit press and hold the button for 10 seconds to save your changes If the SOLA 520 Rackmount is running on AC input power the display will change back to the percent of full load The new val ues will take effect after the display returns to normal mode Press this button for 10 SECONDS to save your...

Page 22: ......

Page 23: ......

Page 24: ...of defective parts at the factory or other service locations as nominated by SOLA Australia provided the unit has been returned by the user packed adequately to prevent shipping damage and approval has been obtained from SOLA Australia Ltd before shipment All costs associated with the return of the product to SOLA Australia are at the customer s expense 5 Units returned for in warranty repairs whi...

Page 25: ...VIC 3175 Phone 61 3 9706 5022 Fax 61 3 9794 9150 National Service and Repair Centre Free Call 1800 034 401 except Melbourne 9768 3105 Melbourne only Customer Service Offices Adelaide PO Box 481 Marlestone Business Centre SA 5033 Phone 08 8347 3622 Fax 08 8445 6328 Brisbane Unit 2 8 Lockhart Street Woolloongabba QLD 4102 Phone 07 3891 1211 Fax 07 3891 2492 Perth Unit 2 321 Great Eastern Highway Red...

Page 26: ...array of off the shelf products for the fastest possible delivery In addition SOLA field sales offices are conveniently located to provide prompt attention to customer needs Call SOLA direct to find the location of your closest authorised distributor SOLA BEST Offices SOLA Australia Ltd Best Power Best Power Technology Limited 13 Healey Road PO Box 2 BEST House Moorside Road Dandenong VIC 3175 Nec...