background image

6 9 0 +

6 9 0 +

 

 

Q u i c k   S t a r t

Q u i c k   S t a r t

 

 

Associated Literature 

690+ Installation  Manual  HA465492Uxxx 

690+  Software    Manual  HA465038Uxxx 

V

IE W

  L

EV E LS

 

There are three View Levels to the menu 

Operator 

– A very simple level . No setup allowed 

Basic 

– Default mode of the menu. Allows quick 

setup, save, restore and full diagnostics 

Advanced 

- Allows full access to the 

comprehensive set of function blocks in the Setup 

menu and more choices in the System menu to 

choose Language defaults and more 
View Levels may be selected from the Quick 

Setup menu, under View Level 

M

AC ROS

 

The 690+ comes packaged with several Macros, 

which are preconfigured schemes. Current macros 

include

 

Basic speed control 

- Load this to return to factory 

default parameters 

Raise/Lower 

– Pushbutton ramp using increase/

decrease inputs

 

PID

 – Provides closed loop process control

 

SPW

 – Speed program winder (closed loop trim)

 

PRESET SPEEDS 

– Provides 8 preset speeds 

To load a Macro, go to SYSTEM\RESTORE 

CONFIG and select the macro you wish to load

 

f r a m e s   C

f r a m e s   C

-

-

F

F

 

 

1 5

1 5

-

-

1 5 0   H P

1 5 0   H P

 

 

7 . 5

7 . 5

-

-

9 0   k W

9 0   k W

 

 

P

OW ER

 C

ON NE C T IONS

 

3-phase supply to L1, L2, L3. 

Motor connections to M1, M2, M3 

Brake resistor between DBR+, DBR- 

Motor thermistor to MOT TEMP 

Common Bus to DC+, DC- 

Frame F only: 115/230V fan supply to 
L,N 

 
Ground lugs have been provided for each 
of the power circuits. Follow proper ground-
ing and shielding methods as described in 
chapter 3 of the Installation Manual, 
 
If the stop time is expected to be less than 
the natural coasting time of the load, order 
the factory mounted braking module option 
on frames D through F. Frame C has a 
built-in braking module. Connect the brak-
ing resistor across DBR+ and DBR-.  

Flux Vector  

Sensorless Vector  

Volts/Hertz 

B

E F OR E

 Y

O U

 S

TA RT

 

This document covers the steps necessary 
for a basic start up of the 690+ drive.  Drive 
start ups should be performed by qualified 
electrical technicians who are familiar with 
AC drives and their applications. For de-
tailed installation and safety information 
refer to the Installation Manual. For ad-
vanced features and applications, refer to 
the Software Manual. 

Ensure that all local electric codes are met 
while installing the drive. Check that all live 
parts are covered to protect against electric 
shock and that unexpected rotation of the 
motor will not result in bodily harm or injury. 
This document expects that the drive is 
already installed in its intended location 
and that all relevant installation procedures 
have been followed. Please ensure that the 
drive has adequate ventilation so that am-
bient temperature does not exceed 45°C 
(112°F) under normal operating conditions. 
To access the terminals, loosen the two 
retaining screws at the bottom of the drive, 
pull up gently on the terminal cover and 
slide it off. 

C

ON TRO L

 M

OD E S

 

The 690+ supports 3 different  control 
modes 

Volts/Hertz 

mode – Most basic open loop 

operation, used in fans/pumps and multi-
motor applications. No options needed 

Sensorless Vector

 mode – Tight speed 

regulation with good transient torque 
capability, without the need for speed 
feedback. No options needed 

Flux Vector

 mode – Precise flux vector 

control with full torque down to zero speed 
and improved dynamic performance. 
Optional Speed Feedback Technology 
Card required on the drive and an encoder 
on the motor 

T

EC HN OLOGY

 B

OX E S

 

The 6055 series of Technology 

boxes  is available to communi-

cate with protocols such as De-

viceNet, PROFIbus, ModBus, 

RS485 serial comms, CAN bus 

and LON works.  Any of these 

may be plugged into the right-side 

techbox port. Securely snap into 

place, then tighten the ground 

screw  
Networking a standard 690+ to 

LINK 

is done 

with the 

LINK 

 

techbox. This has a built-in proc-

essor that can be configured using DSD, the 

I

NT ER NA L

 L

INKS

 

Under SETUP\LINKS, you may connect and dis-

connect internal block diagram connections, to use 

special functions like PID, winder blocks, diameter 

block, etc., and to tag analog and digital I/O to se-

lected points inside the drive to suit your applica-

tion needs. Specify sources and destinations to 50 

internal links. 

The power terminals shown are for frame D. 
Although other frames may vary slightly in 
appearance, their terminal designations and 
functionality are identical 

Visit us at www.SSDdrives.com 

USA: (704) 588-3246      UK: +44 (0)1903 737000 

HA470631U200    Issue 5 

3 phase power

3 phase power

thermistor

thermistor

~

~

motor

motor

braking 

braking 

resistor

resistor

3 phase power

3 phase power

thermistor

thermistor

~

~

motor

motor

braking 

braking 

resistor

resistor