background image

Gateways

 KNX - DMX512 

 

BES-GW612100

  

v2.1.2 

Programming manual 

z

Summary of Contents for BES-GW612100

Page 1: ...Gateways KNX DMX512 BES GW612100 v2 1 2 Programming manual z ...

Page 2: ...ON PROGRAM INFORMATION 5 3 2 INDIVIDUAL ADDRESS 5 3 3 RESTORE FACTORY SETTINGS 5 3 4 ADDING DMX LIGHTS 6 3 4 1 Device type 6 3 4 2 Parameters 7 3 5 COMMUNICATION OBJECTS 8 3 5 1 Objects table 8 3 5 2 Objects description 9 3 6 SCENES SEQUENCES PROGRAMMING 10 3 6 1 How to create a scene 10 3 6 2 Nomenclature 10 3 6 3 Commands 11 4 INSTALLATION 12 ...

Page 3: ...annels supported by DMX protocol and to execute up to 16 scenes being easily programmable through the projects developing software ETS Thanks to this gateway it is possible to develop the integration of a DMX device or system into a KNX home automation installation and regulate individually each DMX channel in a simply way like any other KNX dimmer or to program a complex group of commands in a sc...

Page 4: ...l Size 6 modules Connections BUS connection terminal KNX Screw terminals for main supply and DMX bus DMX Channels Up to 512 DMX channels emulation Environment temperature range Operation 10ºC 55ºC Storage 30ºC 60ºC Transportation 30ºC 60ºC Regulation According to the directives of electromagnetic compatibility and low voltage EN 50090 2 2 UNE EN 61000 6 3 2007 UNE EN 61000 6 1 2007 UNE EN 61010 1 ...

Page 5: ...55 to the devices in programming mode check procedure from the ETS even if it has been already programmed with virtual DMX dimmers However an individual address existence check or line scan will report all virtual dimmers in the KNX DMX gateway memory When a virtual dimmer is programmed in the gateway memory the individual address cannot be overwritten with the same device because the ETS will sho...

Page 6: ... in the corresponding application To do so from the topology window do right click on the device and select Edit parameters General The device type parameter allows selecting the corresponding device that will be programmed by the application The ETS will show or hide communication objects and parameters according to this parameter In this case the device that must be selected is Dimmers DMX Chann...

Page 7: ...light whose address is configured here Name Ramp speed sec Values From 0 to 255 Description It is the brightness change rate measured in seconds The brightness changes gradually when using Channel X value or dimming communication objects Typical value 10 seconds Now we can associate the device communication objects to the group addresses as always in the ETS The KNX telegrams will be translated by...

Page 8: ... software requests for it Repeat again to control the next DMX light with address 2 adding a new Dimmer application to the gateway memory and setting its DMX address parameter a value of 2 and so on with the other DMX lights 3 5 Communication objects 3 5 1 Objects table Object Name Function Length DPT Flags C R W T U 0 CH1 on off 1 bit 1 001 1 CH1 dimmer 4 bits 3 007 2 CH1 value 1 byte 5 001 3 CH1...

Page 9: ...or down slowly according to the ramp speed configured Name Object 3 CH1 On Off state Function 1 bit communication object for feedback signalling of the on off state of the channel Description When the light is off and receives a switch on telegram or a brightness value a 1 is sent through this object When the light is on and it receives a switch off telegram or a brightness value of 0 a 0 is sent ...

Page 10: ... Scenes sequences programming The DMXBUS K gateway allows to program 16 scenes including up to 256 commands each 3 6 1 How to create a scene The scenes which will be executed must be created previously using text files that have to be loaded in the microSD card of the gateway The memory card must have a maximum capacity of 2GB and be FAT16 formatted 3 6 2 Nomenclature These text files can be gener...

Page 11: ...he ramp speed changing speed from the actual value to the Y value WAIT X Where X is the pause value in seconds LOOP With this command the scene is executed again from the beginning Send 100 value of the scene to stop the execution Scenes examples text files generated into the memory card EXECUTE 1 100 5 EXECUTE 1 75 3 EXECUTE 1 0 3 EXECUTE 2 100 5 WAIT 2 EXECUTE 2 0 3 WAIT 2 EXECUTE 3 75 3 EXECUTE...

Page 12: ...stallation Feed low voltage lines BUS and inputs in separate ducting to that of power 230V and outputs to ensure there is enough insulation and avoid interferences Do not connect the main voltages 230V or any other external voltages to any point of the BUS or inputs ...

Page 13: ... be completely excluded Consequently any liability for this is not accepted Please inform us of any suggestion Every correction will be incorporated in new versions of this manual Manual version v1 2 Výhradní distributor pro ČR a SR Stakohome Innovation s r o Aloisovská 934 8 198 00 Praha 9 Hloubětín Česká republika Tel 420 226 517 522 Mob 420 777 780 384 info besknx cz www besknx cz z ...