background image

Universal Stopper Install

STI-13000 & STI-14000 Series

Rely on STI

®

Specifications

Polycarbonate Enclosure

· Flammability - flush and surface mount models (Fig. 2, 3 & 4): UL 94 V-2, enclosed flush and enclosed back box models (Fig. 5 & 6): UL 94 5VA

· Cover wall thickness  0.125 inches

Dry Contact Relay

·  30 VAC/VDC, 1A

Temperature Range

·  Electronics operating range: -40° to 120°F (-40° to 49°C)

 

Below -4°F (-20°C), a remote power source is recommended

·  Polycarbonate rated: -40° to 284°F (-40° to 140°C)

Installation Notes

·  When used outdoors, the manual station must also be rated for outdoor use.

·  UL Listing does not permit external power source or connection of horn relay contacts to fire alarm or life safety devices.

·  When properly installed, the operation of this cover will not interfere with the function of your life safety system.

·  Horn operation and performance must be tested annually.  Battery replacement is recommended annually dependent on usage and 

battery expiration date.

·  Ensure the service pin is properly inserted in the service pin receptor to silence horn while performing installation or servicing horn.

·  If mounting to an uneven surface, a backplate (STI-1314) is recommended to help ensure proper sealing to mounting surface. 

·  The backplate may be drilled if wire access or screw mounting holes are needed. 

Approvals

It has been tested and approved or listed by:

·  UL, CUL Listed - S2466

·  UL Certified to meet ADA

·  NEMA Type 3RX models with enclosed flush mount and enclosed back box options

Polycarbonate Cleaning Instructions

Rinse with water to remove abrasive dust and dirt.  Wash with soap or mild detergent, using a soft cloth.  Rinse once more then dry with a 

soft cloth or chamois.  Exercise caution when using water inside enclosure.  Make sure unit is completely dry inside before reassembling.  

To remove grease or wet paint from exterior of cover, rub gently with a soft cloth thoroughly wetted with Naptha.  Then wash and rinse. 

Do not use razor blades.

4.08 in.

(104mm)

5.42 in.

(138mm)

4.96 in.

(126mm)

4.31 in.

(110mm)

3.25 in.

(83mm)

2.54 in.

(84mm)

2.66 in.

(68mm)

2.0 in.

(51mm)

1.5 in.

(38mm)

1.0 in.

(25mm)

FLUSH END VIEW

.67 in.

(17mm)

5.95 in.

(151mm)WITHOUT HORN

5.28 in.

(134mm)WITH HORN

.42 in.

(11mm)

5.42 in.

(138mm)WITH HORN

6.36 in.

(162mm)WITHOUT HORN

FLUSH SIDE VIEW

LIFT HERE

TEXT HERE

5.950 in.

(151.13mm)

6.798 in.

(172.68mm)

5.7 in.

(144.78mm)

3.83 in.

(97.28mm)

4.08 in.

(103.63mm)

4.898 in.

(124.42mm)

5.699 in.

(144.75mm)

LIFT HERE

TEXT HERE

5.950 in.

(151.13mm)

6.798 in.

(172.68mm)

5.7 in.

(144.78mm)

3.83 in.

(97.28mm)

4.08 in.

(103.63mm)

4.898 in.

(124.42mm)

5.699 in.

(144.75mm)

LOCKING
TAB

LIFT HERE

TEXT HERE

5.95 in.

(151mm)

6.80 in.

(172mm)

5.7 in.

(144mm)

3.83 in.

(97mm)

4.08 in.

(103mm)

4.90 in.

(124mm)

5.70 in.

(144mm)

LOCKING TAB

Fig. 1 - Dimensions

Center pull station to the Universal Stopper with 
the help of dimensions shown in Fig. 1.

Open cover, use frame or optional backplate to 
mark mounting holes.

NOTE: Be sure the entire cover travel will not 
interfere with operation of the pull station or 
other safety system equipment when installed.

Horn 

(battery included)

  

current draw 

dBA @ 9VDC

 STI-13*20 & STI-13*30 models

 

9vdc 

12vdc   

24vdc 

1 ft. 

3 ft. 

10 ft.

 Low volume 

36 mA 

42 mA  

22 mA 

98 

87 

75 

 High volume 

155 mA 

146 mA 

95 mA 

108 

93 

82

 Standby current 

0.03 mA 

0.64 mA 

1.9 mA 

-

    

 

current draw 

 

 

dBA @ 3VDC

 STI-14*20 & STI-14*30 models

 

3vdc 

12vdc   

24vdc 

1 ft. 

3 ft. 

10 ft.

 Low volume 

60 mA 

46 mA 

25 mA 

84 

74 

62

 High volume 

140 mA 

87 mA 

45 mA 

95 

85 

76

 Standby current 

0.04 mA 

0.10 mA 

0.014 mA 

-

See website for accessories

Summary of Contents for STI-13000 Series

Page 1: ...MA Type 3RX models with enclosed flush mount and enclosed back box options Polycarbonate Cleaning Instructions Rinse with water to remove abrasive dust and dirt Wash with soap or mild detergent using a soft cloth Rinse once more then dry with a soft cloth or chamois Exercise caution when using water inside enclosure Make sure unit is completely dry inside before reassembling To remove grease or we...

Page 2: ...HE CONDUIT WINDOWS AND TABS THEN TRIM SHARP EDGES BEFORE INSTALLATION LOCKING TAB DRILL 1 8 in HOLE WHILE COVER IS CLOSED INSERT THE BREAKWAY SEAL KIT 65 COMPLETELY INTO THE LOCKING TAB NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS LOCKING TAB DRILL 1 8 in HOLE WHILE COVER IS CLOSED INSERT THE BREAKWAY SEAL KIT 65 COMPLETELY INTO THE LOCKING TAB NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLI...

Page 3: ... x 1 2 in PHIL PANHEAD SCREW 2 PROVIDED SEALED MOUNTING PLATE SHOWN LOCATE GROMET AS NEEDED DRILL 5 8 in 16mm HOLE INSERT GROMET AS SHOWN FEED WIRES THROUGH GROMET INCLUDED WITH SEALED MOUNTING PLATE 3 4 in NPT PLUG 1 PROVIDED USE A FLAT HEAD SCREWDRIVER OR COIN TO REMOVE APPLY THREAD SEALANT SCREW NPT BACK INTO BACK BOX LOCKING TAB DRILL 1 8 in HOLE WHILE COVER IS CLOSED INSERT THE BREAKAWAY SEAL...

Page 4: ...r intervention ailleurs sur un vrai incendie s avère nécessaire en même temps À cela s ajoute l agitation éprouvée dans l établissement au moment du déclenchement d une fausse alerte Si vous rencontrez ou risquez de rencontrer un problème avec les fausses alertes d incendie ou avec l éventuel endommagement par effet climatique ou physique de vos dispositifs de déclenchement des alertes d incendie ...

Page 5: ...maximale des modèles SS2xx 4 et LT1 UL est de 30 VCC 3A WARNING This product can expose you to chemicals including Bisphenol A which is known to the State of California to cause reproductive harm and Dichloromethane which is known to the State of California to cause cancer For more information go to www P65Warnings ca gov Three year warranty or a one year limited warranty from date of purchase on ...

Page 6: ...ALS MAY BE USED INSERT NOTCH AS SHOWN THEN ROTATE UPWARD TERMINAL BLOCK KIT E10196 NO 1 PROVIDED KIT E10198 NC 1 PROVIDED SEE VIEW IN DIRECTION OF ARROW FOR CONTACT INDENTIFIER LOCATIONS UP TO 3 TERMINALS MAY BE USED FOR EACH STATION ASSEMBLY OUTGOING INCOMING SCREWS 6 32 x 1 OUTLET BOX 2 PROVIDED SCREWS 6 32 x 1 50 WHEN USING KIT 102722 COLOR SPACER SEE REVERSE SIDE 10 32 x 3 8 in GROUND SCREW 1 ...