SunEarth-Steca TR0301U Technician Menu – v5

 

The Operating Instruction Manual does not cover this technician menu.  

WARNING!  Adjusting settings incorrectly can result in poor system performance and may result in damage to solar 
thermal system components.  These settings should only be adjusted by a qualified technician with thorough knowledge of 
the workings and components of solar thermal systems.   

To activate or access the 

technician 

menu:  

 

Hold all three buttons down for ~5 seconds until the screen changes.   

 

The screen should show “on” and flashing between T1 and T2.

  If it doesn’t work, try again, all three buttons at the same 

time for 5 seconds 

In the technician menu you can adjust the following: 

Menu 

Item 

Default   Description 

on 

16F 

Differential “on”- turns the pump on when the temperature T1-T2= 16F. Display flashes 
between T1 and T2.  

(See the Operating Instructions 7.1 Automatic storage tank charging) 

oFF+4F <=on<=100F

 

off 

8F 

Differential “off”-turns the pump off when the temperature T1-T2=8F. Display flashes 
between T1 and T2.  

(See the Operating Instructions 7.1 Automatic storage tank charging) 

0< oFF<on-4F

 

HYS 

6F 

Hysteresis for MAX tank temperature T2- turns the pump off when T2=140F (0 ~ 95°C), turns 
the pump on when T2=134F (0 ~ MAX T2/2 ). Display flashes MAX T2. 

(See the Operating 

Instructions 7.2 Automatic charging shutdown) 32F~203F 

on 

261°F 

Over temperature function “on”- turns the pump back on when T1=261°F Display flashes heat 
waves on the collector and T2.  

(See the Operating Instructions 7.3 Automatic pump blockage) 

176°F<=on<=oFF-4F

 

oFF 

266°F 

Over temperature function “off”- turns the pump off when T1=266°F.  Display flashes heat 
waves on the collector and T2.

 (See the Operating Instructions 7.3 Automatic pump blockage) 

on+4F<=oFF<=392°F

 

oFF 
 

95°F 

 

Holiday/vacation setting- turns the pump on periodically recirculating fluid to the collectors 
cooling the tank until T2=95°F.  Display flashes umbrella and T2.  

(See the Operating Instructions 7.5 Holiday Function).  68°F<=oFF<=MAX T2-20F 

on 

32°F 

Minimum temperature of collector- turns the pump on 
32°F<= on <= over temperature on -20F 

off 

off 

Off: pump 

stops

 if Freeze recirculation functionis active and there is an error on T1 

On: pump 

starts

 if Freeze recirculation function is active and there is an error on T1 

off 
 

extra 

off 

Stagnation Reduction funciton delays fluid standstill(stagnation) by repeatedly stopping the 
pump as the T2 approaches its MAX tank setting. 
ON: The pump starts cycling at 20

°

F below the MAX tank main menu setting

 

40 

 

extra 

40 

After the initial pump stoppage, pump restarts when collector temperature is 40

°

F less than the 

OVER TEMPERATURE FUNCTION(default 266

°

F). Pump now stops and starts within a 

20

°

F range until MAX tank main menu setting is reached. 

  

T1-collector sensor, T2-tank sensor, T3-optional informational sensor-does not effect operation of the controller 

Within the technician menu, 

the graphical display on the screen will indicate what you are adjusting.   

 

Use the arrow keys to scroll up and down through the menu to get to the function that you want to change.  The graphical 
display on the screen will indicate what you are adjusting 

(see table above)

.   

 

Hold the “SET” button down for ~3 seconds to access adjustment of the function value, just like the main menu described in 
the manual 

(see 8.2 Setting the controller)

 .  The screen will change and will flash between the number set in the controller 

and the function being changed.   

 

Use the arrow keys to adjust the number. 

 

Use the “SET” button to set the number into the software.  The controller has EPROM memory so settings will be saved even 
when the controller is powered off.   