background image

 

 

Logger 3000
SolarInfo Logger
User Manual

 

 

Summary of Contents for Logger 3000

Page 1: ...Logger 3000 SolarInfo Logger User Manual...

Page 2: ......

Page 3: ...Mechanical Installation 10 5 1 Unpacking and Inspection 10 5 2 Installation Place Requirement 11 5 3 Installation 11 5 3 1 Rack mounted Installation 11 5 3 2 Wall mounted Installation 12 6 Electrical...

Page 4: ...ter Setting 28 8 7 4 Checking the Parameter Setting Log 29 8 8 Management 30 8 8 1 Search Device 30 8 8 2 Device Operation 34 8 9 Settings 37 8 9 1 Time Settings 37 8 9 2 Serial Port Settings 38 8 9 3...

Page 5: ...III 10 1 Technical Data 49 10 2 Exclusion of Liability 50 10 3 About Us 51...

Page 6: ...IV...

Page 7: ...of the inverter EM device and related safety notices For the details of the electrical connection of these devices please refer to the corresponding manuals 1 2 How to Use this Manual Read this manua...

Page 8: ...NG indicates a hazard with a medium level of risk which if not avoided could result in death or serious injury CAUTION indicates a hazard with a low level of risk which if not avoided could result in...

Page 9: ...to the operator or a third party Therefore the following safety instructions must be read and always kept in mind prior to any work All detailed work related safety warnings and notes will be specifi...

Page 10: ...t switch to make sure the Logger3000 is voltage free during installation Maintenance and Replacement The maintenance of the Logger3000 can only be conducted by Sungrow s service dept or qualified pers...

Page 11: ...The Logger3000 can connect to the inverter transformer EM device and meter in the PV system through the RS485 method The Logger3000 can connect to Insight or the third party SCADA the switch as shown...

Page 12: ...M Meter Transformer Core switch SCADA system iSolar Cloud Logger Ethernet Fig 3 1 Application to PV system Solution 1 Inverter RS485 RS485 PLC Internet iSolar Cloud Router Logger EM Meter Transformer...

Page 13: ...nce The Logger3000 can maintain the system time network serial port and protocol point through embedded WEB browser Data gateway The Logger3000 can transmit data to Sungrow s background and the third...

Page 14: ...R indicator off power supply is abnormal RUN Running indicator RUN indicator flash running normal RUN indicator off running abnormal BLE Bluetooth indicator BLE on Bluetooth is connected BLE off no co...

Page 15: ...tallation flow Step Content Reference 1 Unpacking and inspection 5 1 2 Select the optimal installation place 5 3 3 Mechanical installation 5 4 4 Electrical connection 6 5 Inspection before commissioni...

Page 16: ...ocuments Quick User Manual quality certificate packing list product test report and warranty card C Communication terminal resistor 12x120 note if there are more than 15 devices connected to the RS485...

Page 17: ...rk cable within the scope of delivery is 2m If there is external devices e g EM device and etc connected to the Logger3000 user needs to add corresponding communication SPD according to the on site si...

Page 18: ...ring installation of the Logger3000 Improper handling of the device may cause device tilting or falling down and may cause personal injury It is recommended to install the Logger3000 1 5m higher than...

Page 19: ...ion surface Step 4Fix the Logger3000 to the surface by inserting the screw hole in the hanger of the Logger3000 through the tapping screw and washer Step 5Tighten the tapping screw by torque screwdriv...

Page 20: ...B5 A6 B6 GND PT1 GND PT2 AI1 AI2 AI3 AI4 H L CAN 24V AC L AC N GPS BDS RF L1 L2 DO 1 2 3 NO NC COM Identify the cable connection terminals according to the table below before cable connection Tab 6 1...

Page 21: ...antenna port Used for time service and positioning N RF Wireless antenna port Reserved function O Grounding port Connects to protective earthing P L1 L2 Reserve Reserve Digital input and output ports...

Page 22: ...Logger3000 in RS485 daisy chain When the meter connects to the Logger3000 the communication protocol should meet the DL T645 2007 requirement Inverter 1 Logger 120 EM RS485 Daisy chain Inverter 2 Mete...

Page 23: ...4 Connection to PV System Background The Logger3000 can connect to the PV system background through the internet port The communication protocol is standard Modbus TCP or IEC104 As the slave device th...

Page 24: ...5 Protection Earthing Connection The ground cable should be grounded reliably otherwise Lethal electrical shock to the operator if a fault occurs The device may be damaged by lightning Step 1Prepare t...

Page 25: ...ake the AC power supply for example Step 1Prepare the power cable and the terminals Cable Cable recommended AC power supply Cross sectional area 1mm2 1 5mm2 DC power supply Cross sectional area 1mm2 1...

Page 26: ...owser The O M password of the Logger3000 is adamg1 4 Make sure the device is firmly connected to the Logger3000 and open the device close the circuit breakers on the two side of the inverter 5 Refer t...

Page 27: ...earch function is valid only for string inverters that support the search and device automatic allocation For other devices like the meter transformer and etc please connect to the Logger3000 through...

Page 28: ...ithin the same network segment of the Logger3000 The debugging computer connected to the ETH2 of the Logger3000 The default address of the ETH2 is 192 168 1 100 You can set the IP address of the debug...

Page 29: ...three types of user O M user R D user and anonymous The default password for O M user is adamg1 The R D user is for Sungrow internal use only Anonymous user can log in directly to check the present d...

Page 30: ...unction display area Display the present selected check or set function interface D System time Display the present system time E User Display the present login user F Info icon Internet access CPU us...

Page 31: ...Operation Flow Operate as follows to log in the Logger3000 for the first time Step 1Complete the electrical connection Before logging the Logger3000 WEB make sure the Logger3000 is correctly connecte...

Page 32: ...forward the data to the upstream devices Please refer to 8 9 6 Service Settings 8 7 Monitoring Monitoring module is to set the parameter of the devices that are managed by the Logger3000 The Monitorin...

Page 33: ...ou can also set the parameter for a single inverter Click the device to be set under the Overview and then click Setting to finish the parameter setting of a single inverter 8 7 2 Query Query is to re...

Page 34: ...ote in red after the set value 8 7 3 Initial Parameter Setting The string inverter can connect to the grid after setting the initial parameter when it is installed for the first time After connecting...

Page 35: ...ce Island GR 12 Netherlands NL 13 Portugal PT 14 China CHN 15 Sweden SE 16 Other 50Hz 17 Romania RO 18 Thailand TH 19 Tokelau TK 27 United Arab Emirates AE 28 Israel IR 29 Hungary HN 60 Canada CA 61 A...

Page 36: ...device and Device operation 8 8 1 Search Device Search device is to search the devices that support the search function like the string inverters and to allocate address for them Select Management Se...

Page 37: ...g ways Search by Port Select the serial port name and input the device number to search the devices connected to this serial port of the Logger3000 Search by Address Select the serial port name and in...

Page 38: ...played Search by addr only the devices searched according to the address range will be displayed Reallocate Address Select the serial port name and input the start address to allocate address to the d...

Page 39: ...After modifying the actual device address change the address of other devices in the WEB For devices that support the search function reallocate the address by the automatic searching and automatic a...

Page 40: ...address and modify the device address click the Save button to save the present operation and the settings will be valid Export Results Click Export results to export the list of the devices searched...

Page 41: ...operation make sure the communication address of the device is preset correctly Add device After adding devices to the Logger3000 you should allocate address to them and conduct corresponding setting...

Page 42: ...ommunication port COM6 33 is the device address 33 After modifying the actual device address you can modify the address in WEB It is not recommended for you to modify the device address Make sure the...

Page 43: ...t and other info unchanged proceed as follows Delete the SG50KTL and click the Save button Add the SG40KTL and click the Save button The SG50KTL device is changed to SG40KTL 8 9 Settings The settings...

Page 44: ...Settings Serial port settings is to set the serial port of the Logger3000 Including com port function baud rate check bit data bit and stop bit Select Settings Serial port settings to enter the serial...

Page 45: ...3 Network Settings Network settings is to set the network of the Logger3000 Select Settings Network settings to enter the network setting interface The default IP address of ETH2 is 192 168 1 100 8 9...

Page 46: ...000 serial port parameter network parameter and service settings you must restart the system to activate the modification 8 9 6 Service Settings You can forward the data to the background through the...

Page 47: ...rvice settings to enter the Modbus service settings interface Edit the network service settings If the background IP address of the network service settings is 0 0 0 0 any background device with a leg...

Page 48: ...e IEC104 service Select Settings IEC104 service settings to enter the IEC104 service settings interface Cloud Service Settings Cloud Service Settings is for Logger3000 to forward the Cloud service Sel...

Page 49: ...ce The Maintenance module is to maintain the Logger3000 and the devices connected to the Logger3000 including Upgrade device and export faultwave data 8 10 1 Upgrade device Upgrade device is used to u...

Page 50: ...44 Step 3Select the device to be upgraded to finish the device update...

Page 51: ...alified personnel can perform the work described in this chapter Do not leave any screws washers or other metallic parts inside the Logger3000 to avoid damages to the Logger3000 Wait at least 5 minute...

Page 52: ...Check the heat dissipation hole and the cover Terminal and cable connection Check if the screws of the control terminals are loose Refasten them with screwdriver if necessary Check if the connection...

Page 53: ...ces does not match the actual device address 5 Device does not operate normally 1 Check the RS485 connection cable connection reconnect and tighten the cable if there is loose peeling off reverse conn...

Page 54: ...the background is failed 2 Network parameter setting is incorrect 3 The protocol conversion configuration is incorrect 1 Check if the Ethernet port of the Logger3000 is connected to the PC or router...

Page 55: ...ommunication method RS485 Max communication range RS485 1000m Other parameter Display WEB LED indicator Language Chinese English Power supply AC110V 240V 50 60HZ or DC24 0V Power consumption Typical 5...

Page 56: ...tions If a product covered by warranty becomes defective during warranty period Sungrow will provide a toll free repair or exchange The unqualified product that is replaced shall return to Sungrow Cus...

Page 57: ...ct us Company Sungrow Power Supply Co Ltd Website www sungrowpower com Email info sungrow cn service sungrow cn Address No 1699 Xiyou Rd New High Technology Industrial Development Zone Hefei P R China...

Reviews: