LED Emergency Driver
Important: Read all instructions prior to installation.
BLD-YT08D-XXX Series
4400 Earth City Expy, St. Louis, MO 63045
866-590-3533 superbrightleds.com
Rev Date: V1.0 04/29/2021
5
yr
User Manual
Specifications
Safety and Notes
Model
BLD-YT08D-XXX
Operating Temperature
32°–122° F (0°–50° C)
Emergency Operation Duration
90 minute (minimum)
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
• Do not join battery connector or turn “ON” the battery switch
until installation is complete and AC power is supplied to the
emergency driver.
• This product is intended for use with an emergency LED
lighting load and supplies nominal of power and a maximum
voltage in emergency mode for a minimum of 90 minutes.
• An unswitched AC power source is required (120-277 VAC
50/60 Hz) to power these units.
• This product’s chassis must be grounded.
• This product is suitable for use in damp locations where the
ambient temperature is 0° C minimum, to 55° C maximum.
This product is also suitable for installation in sealed and
gasketed fixture. This product is not suitable for heated air
outlets and wet or hazardous locations. Maximum allowable
case temp is 70° C. Refer to the below image for TC
measurement location.
• This product contains a rechargeable LiFePO4 battery.
The battery must be recycled or disposed of properly.
• Make certain all connectors are in accordance with the
National Electrical Codes and any local regulations.
• This emergency LED driver is suitable for both factory
or field installation. For field installation, please see the
instructions on page 3.
Check product label for specific electrical
specifications related to installation.
Improper installation will void warranty.
• Do not install near gas or electric heaters.
• The use of accessory equipment is not recommended
by the manufacturer and may cause an unsafe condition.
• Do not use this product for applications other than the
intended use.
• Equipment should be mounted in locations and at heights
where it will not be subjected to tampering by unauthorized
personnel.
• This device complies with part 15 of the FCC Rules. Operation
is suitable to the following two conditions: (1) This device may
not cause harmful interference, and (2) This device must accept
any interference that may cause undesired operation.
• To reduce the risk of electric shock, disconnect both normal
and emergency power supplies and place the battery switch
in the “OFF” or disconnect the battery connector of the
emergency driver before servicing.
• Do not attempt to service the battery. It is a sealed, no-
maintenance battery that is not field replaceable. Contact
the manufacturer for information on service.
•
Servicing should be performed by qualified service
personnel only.
• Emergency driver and standard driver must be on the same
branch circuit.
• Driver output is Class 2 at the intended output voltage range.
BLD-YT08D-XXX
Testing
Manual Test
Test button can be held for manual testing purposes.
Note: A short-term discharge test may be conducted
after the emergency driver has been charged for one
hour. A 48-hour charging period must is required before
conducting a long-term discharge test.