20170724                              We reserve the right to alter specifications.  

GLOBAL

1

BACnet support for up to 4 units with double flow and heat recovery equipped with TAC5 control boards and SAT ETH-
ERNET. The BACnet Standardized Device Profile (Annex L) of the BACnet device is: BACnet Application Specific Control-
ler (B-ASC). The supported Data Link Layer Options are BACnet / IP and MS/TP slave.

2. Standard objects supported

Object Type

Analog Input

Object_Identifier, Object_Name, Object_Type, Present_Value,

Status_Flags, Event_State, Out_Of_Service, Units, Description.

Analog Value

Object_Identifier, Object_Name, Object_Type, Present_Value,

Status_Flags, Event_State, Out_Of_Service, Units, Description.

Integer Value

Object_Identifier, Object_Name, Object_Type, Present_Value,

Status_Flags, Event_State, Out_Of_Service, Units, Description.

Device

Object_Identifier, Object_Name, Object_Type, System_Status,

Vendor_Name, Vendor_Identifier, Model_Name, Firmware_Revision,

Application_Software_Version, Protocol_Version,

Protocol_Revision, Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_List, Max_

APDU_Length_Accepted, Segmentation_Supported.

1. Overview

BACnet gateway

Summary of Contents for BACnet gateway

Page 1: ...pe Present_Value Status_Flags Event_State Out_Of_Service Units Description Analog Value Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Units Description Integer Value Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Units Description Device Object_Identifier Object_Name Object_Type System_Status Vendor_...

Page 2: ...R5 Actual Exhaust Flow IV R8 Set Speed Exhaust IV W5 Exhaust Supply ratio IV R6 T exhaust AI5 Defrost Status IV R18 Setpoint Preheat Temperature AVR1 OUT INT ELECT PREHEAT IV R20 T out AI3 T extract AI4 Bypass Status IV R11 Setpoint T Freecool AV W5 Force Bypass IV W6 Current Postheat setpoint AV R3 Setpoint T Postheat AV W1 Heat Stop IV W9T antifrost internal hydraulic postheater AI6 OUT INT HYDR...

Page 3: ...T3 sensor 999 open 999 short circuit 6 T antifrost internal hydraulic postheater 99 9 99 9 C Temperature for the antifrost protection of the hydraulic postheater inside the unit meas ured on T4 sensor 999 open 999 short 7 T supply 99 9 99 9 C Supply temperature measured on T5 sensor 999 open 999 short 8 T antifrost external hydraulic postheater 99 9 99 9 C Temperature for the antifrost protection ...

Page 4: ...theat setpoint 0 1 99 9 C Current Postheat setpoint KWout NV BA KWext 0 OFF 4 Current Postcool setpoint 0 1 99 9 C Current PostCooling setpoint BA 0 OFF 5 OUT INT HYDRAULIC POSTHEAT 0 10 0 V Output for the power control of the hydraulic postheater inside the unit 6 OUT EXT HYDRAULIC POSTHEAT 0 10 0 V Output for the power control of the hydraulic postheater external to the unit 7 OUT EXT HYDRAULIC ...

Page 5: ...it for flow 6 Exhaust Supply ratio 5 999 F3F4 F1F2 7 Actual Supply Flow 0 99999 Actual Supply Flow unit defined in object Type of unit for flow 8 Actual Exhaust Flow 0 99999 Actual Exhaust Flow unit defined in object Type of unit for flow 9 Running Hours 0 999999 H Run time working hours 10 Antifrost Status 0 2 0 OFF 1 REC ON 2 NV ON 11 Bypass Status 0 2 0 CLOSED OFF 1 OPEN ON 2 PARTIALLY OPEN 12 ...

Page 6: ...pass 0 stop 1 run bit3 CT bit4 KWin bit5 KWout bit6 OR1 SAT pressure alarm bit7 OR2 SAT fan on bit8 OR3 SAT water pump NV bit9 OR4 SAT bypass on bit10 SATBA WP bit11 SATBA OUT9 KWext 20 OUT INT ELECT PREHEAT 0 100 Output percentage for the power control of the electrical preheater 21 OUT INT ELECT POSTHEAT 0 100 Output percentage for the power control of the electrical postheater inside the unit 2...

Page 7: ...nt T Postheat 0 99 9 C Postheating T setpoint 0 OFF 2 CPs Voltage reference 1 0 10 0 V CPs mode setpoint voltage for CPs on SUP or CPs on EXH 3 Setpoint T Postcool 0 99 9 C Postcooling T setpoint 0 OFF 4 CPs Voltage reference 2 0 10 0 V CPs mode setpoint voltage for CPs on SUP EXH 5 Setpoint T Freecool 0 99 9 C Freecooling T setpoint 0 OFF ...

Page 8: ... s or Torque 5 Set Speed Exhaust 0 99999 Set exhaust Flow m3 h or l s or Torque 6 Force Bypass 0 2 Override force bypass ON or OFF 0 normal 1 force_on 2 force_off 7 BOOST 0 1 force boost mode 0 1 8 Cool Stop 0 1 Override force cooling to stop if set to 1 Note that cooling will start if this object is set to 0 and if Heat Stop object is set to 1 9 Heat Stop 0 1 Override force heating to stop if set...

Page 9: ...Power supply 0V Ground V Positive wire VAC min 8V max 24V VDC min 12V max 25V The default configuration is indicated in the following table BACnet gateway o IP ADDRESS gateway 192 168 1 9 o SUBNET MASK 255 255 255 0 o GATEWAY 0 0 0 0 o PORT 47808 o BACnet device name Lemmens o Device Identifier 1 Unit n 1 IP ADDRESS 192 168 1 1 Unit n 2 IP ADDRESS 192 168 1 2 Unit n 3 IP ADDRESS 192 168 1 3 Unit n...

Page 10: ... add a unit o Change the gateway IP configuration o Change the gateway communication port o Change the last number of the IP address of the units on the corresponding row inside the table N B for the units only the last number of the IP address can be changed since it must be within the same range of the gateway IP address o Save the configuration o Open a previously saved configuration 5 3 Upload...

Page 11: ...hange anything the IP address may be different from the picture according to the one configured in the pro ject 4 Press the button Ping then the text Device Found will appear 5 Press the button Next the following dialog box will appear where only Configuration and Read the con figuration when finish must be checked 6 Press the button Execute update firmware 7 The status update window will appear t...

Page 12: ...ddress 192 168 1 9 If this address has been changed later on and the address is not known anymore follows this procedure to set the back the factory address 1 Turn off the Device 2 Put Dip2 of Dip Switch A at ON position Fig 1 3 Turn on the device 4 Connect the Ethernet cable 5 Insert the IP 192 168 2 205 6 Press the Ping button must appear Device Found 7 Press the Next button 8 Check all operatio...

Page 13: ...ns BACnet IP Annex J MS TP slave Clause 9 baud rate s 9600 19200 38400 57600 76800 115200 Point To Point EIA 232 Clause 10 baud rate s 9600 115200 Character Sets Supported ISO 10646 UTF 8 Network Security Options Non secure Device is capable of operating without BACnet Network Security ...

Page 14: ......