GB.CACZ08.050101
Specifications are subject to alteration without notice.
www.swegon.se 1
Backside
Insulation
Plate
Staple fibre baffle
Backside, unit
Angle brackets
Mounting angle
1. Preparations, unit
1. Loosen the screws to the plate on the backside of the
lower section. Dismount the plate.
2. Remove the insulation, which now is visible, from the
lower section.
3. Loosen the screws, which are visible now when the
insulation is removed. Pull off the backside of the lower
sections. They can be relatively hard to remove. NOTE! For
the sake of stability, silencer baffles must remain in the
lower section.
4. Remove the staple fibre baffle, located inside the back-
side removed.
5. Dismount the angle brackets of the staple fibre baffle
and put back the screws.
6. Fasten the mounting angle from the mounting kit and
fasten it with screws in pre-drilled holes in the front.
7. If air distribution plate CACZ-1-10-a is to be mounted,
this is convenient carried out now, see 5. Mounting of air
distribution plate in lower section of unit.
2. Preparations, separate lower sec-
tion
1. Mount the cover plates, with screws, from the moun-
ting kit on the sides of the separate lower section. Appr.
half of the cover plate shall be inside the lower section.
2. Mount the sealing gasket on the lower edge of the
separate lower section, below the mounting angle, and on
the sides in the gap between the perforated side and the
cover plates. See to that sealing gasket seal properly in the
corners.
3. Dismount the front and the silencer baffles on the sepa-
rate lower section, see 3.2.4 in "Installation and mainte-
nance".
3. Assembly of unit and lower section
1. Put the lower sections together. The distance plates
from the mounting kit shall be between the lower sections
along the upper edge.
2. Bolt the lower sections together, from within, at upper
and lower edge. Check angles so that the separate lower
section is straight.
3. Screw mounting angles, from within, to the unit lower
section.
Unit and separate lower section
Unit
Separate lower section
Wall
In this joint distance plates
shall be fastened.
Cemented from within.
Backside, separate lower section
Sealing
gaskets
Cover plates
MOUNTING INSTRUCTION FOR SEPARATE LOWER SECTION
CACZ-1-08
Caution! Do not dismount all parts from a lower section, which has a
upper section on top of it. If front louvre, silencer baffles and backside
is dis-mounted, the lower section is unstable and might collapse. If, for
instance, silencer baffles are left mounted, it is possible to remove the
backside without any problems.
Hole dimensions in wall for separate lower section:
Height 880 mm, width 1120 mm.
4. Cement, from within, in the gap on the upper edge
where distance plates are located.
5. Mount the silencer baffles and the front, see 3.2.4 in
"Installation and maintenance". NOTE! If air distribution
plate CACZ-1-10-a shall be used, one baffle is mounted
first, then the air flow distribution plate, see 6. Mounting
of air distribution plate in separate lower section.