Instructions for the heat exchanger control system SILVER C 
RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120

1. General

The heat exchanger control system is a control system for 
380 W step motors. It is designed for precise and quiet 
control of rotary heat exchangers in the SILVER C RX 
ventilation units with standard rotor (RECOnomic) in size 
100/120, and with sorption rotor (RECOsorptic) in sizes 
05-120.

Integrated functions:
•  0 - 10 V DC analogue input for controlling the speed.
•  Alarm for overloading, over-voltage and under-voltage.
•  Protective motor switch with integrated current limit-

ing function.

•  Short-circuit protected inputs and outputs.
•  Digital input for start/stop.
•  Digital input for alarm resetting.
•  Integrated EMC filter.

In the size 50-80 SILVER C units the heat exchanger 
control system is located inside the filter section in the 
lower level. In the size 100/120 SILVER C units the heat 
exchanger control system is located inside the fan or filter 
section to the left of the centre section in the lower level 
(viewed from the inspection side). For access, open the 
inspection door.

Forbidden to start operation

It is absolutely forbidden to start operation until the 
entire air handling unit, where the above-mentioned heat 
exchanger control system is integrated, has been declared 
to conform to relevant regulations in Machinery Directive 
98/37/EEC and to existing national legislation, if applica-
ble.

The heat exchanger control system must not be energized 
until the entire installation conforms to the provisions in 
ALL relevant EU Directives. If the heat exchanger control 
system has been damaged, for instance during transport, 
it must be inspected and repaired by qualified personnel 
before the voltage is connected.

Safety functions

The heat exchanger control system is protected against 
phase-to-phase short.circuiting, and has integrated cur-
rent limiting function for protection of the motor.

The electrician is accountable for ensuring correct earth-
ing as well as protection according to local standards 
and regulations. An earth fault circuit breaker, multiple 
protective earthing or ordinary earthing can be used as 
extra protection, provided that the local regulations are 
complied with. The earth leakage currents exceed 3.5 mA. 
Therefore a fixed, permanent installation and heavy-duty 
protective earthing are required.

NOTE!

 If an earth fault occurs, there can be a direct cur-

rent component in the leakage current. Earth fault circuit 
breakers should therefore be designed to be able to detect 
this and be installed according to applicable national and 
international regulations, where they are used.

Summary of Contents for SILVER C RX

Page 1: ...ntil the entire air handling unit where the above mentioned heat exchanger control system is integrated has been declared to conform to relevant regulations in Machinery Directive 98 37 EEC and to exi...

Page 2: ...more accurate temperature The heat exchanger control system is controlled with 0 10 V signals The step motor is controlled in micro steps with sinusoidal constant current for ensuring motor shaft rota...

Page 3: ...ing sector To reverse the motor s direction of rotation transpose two optional conductors to Motor Terminal V U W See Fig 6 Automatic restart after alarm The heat exchanger control system automaticall...

Page 4: ...reset lowest and highest speeds See Fig 3 and 4 The Control with 0 10 V DC function is described in Section 3 Function Connect the start stop signal cable leads in the junction box to Ter minals 7 Sta...

Page 5: ...ER C units the heat exchanger control system is located inside the fan or filter section to the left of the centre section in the lower level viewed from the inspection side For access open the inspec...

Page 6: ...op Fig 5 There is no 0 10 V DC control signal Check that the 0 10 V DC control signal is correctly connected to Terminals 13 and 14 in the heat exchanger control system junction box marked GND and 0 1...

Page 7: ...Help to protect the environment by ensuring correct disposal of the packaging and use the products in accord ance with applicable environmental regulations Disposal of the product Products with this m...

Page 8: ...GB EXCHSILV2 141119 We reserve the right to alter specifications 8 www swegon com...