background image

INSTALLATION INSTRUCTIONS 

FOR SYMCOM’S OVERLOAD RELAY 

MODEL 777-

575-

FT

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION!

FOLLOW NATIONAL, STATE, AND LOCAL CODES!

READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

SymCom’s electronic overload relays are fully programmable for customized 

protection with a digital readout and RS-485 communications.  The 777-FT also 

has a fast linear trip mode.

2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848

CONNECTIONS

1.   Using the four corner tabs or the DIN rail mounting bracket, mount the  

  unit near the magnetic contactor.  To use the DIN rail bracket, 

  hook the top clip first, then apply downward pressure until the lower clip  

  “clicks” onto the rail.

2.1 For amperages from 26-90 amps, insert the motor conductors from the top of  

      the unit through the holes marked ‘A’, ‘B’, and ‘C’.  Make certain that the

  conductor through each hole corresponds to the right motor conductor (i.e.  

      the ‘A’ phase conductor should go through the ‘A’ round hole).  See Figure 1 

  for a typical wiring diagram.

2.2 For amperages less than 26 amps, loop the motor conductors according to  

     Table 1.  Figure 2 shows an example of the looping required for current ranging 

      from 8.1 to 12 amps (MULT=3).

2.3 For amperages greater than 90 amps, external CT’s (current transformers)  

      are required.  SymCom recommends CT’s with terminals be used for ease of  

      installation. All CT secondaries must make five passes through the round 

      holes on the MotorSaver.  See Figure 3 for a typical wiring diagram using  

      external CT’s.     

NOTE: Pay close attention to the diagrams to eliminate any power factor  

    

errors.

3.  Connect the three phase power from the line side of the contactor to ‘L1’, ‘L2’,  

      and ‘L3’ terminals using 12-18AWG copper wire.

4.   Connect the control circuit wires to the appropriate terminals. The relay is a  

  fail safe design so the ‘NO’ contact should be in series with the coil on the    

  contactor for motor control (see Figure 4).  For alarm circuits, the ‘NC’ contact  

  is in series with the alarm circuitry (not shown).

Summary of Contents for 777-575-FT

Page 1: ...t motor conductor i e the A phase conductor should go through the A round hole See Figure 1 for a typical wiring diagram 2 2 For amperages less than 26 amps loop the motor conductors according to Tabl...

Page 2: ...IAGRAM FOR 26 90 FLA FULL LOAD AMPS NUMBER OF LOOPS NUMBER OF CONDUCTORS THROUGH A B and C MULT PROGRAM SETTING 2 0 2 5 9 10 10 2 6 3 0 8 9 9 3 1 3 5 7 8 8 3 6 4 0 6 7 7 4 1 5 0 5 6 6 5 1 6 0 4 5 5 6...

Page 3: ...RMS 600 VAC MAX SYMCOM INC 800 243 8848 RAPID CITY SD IND CONT EQ LISTED 784X LR46510 L1 L2 L3 NO C NC MODEL 777 FT OVERLOAD RELAY 20 90A RESET PROGRAM RD3 RF VUB OC RU ADDR MULT RD2 KWS HV LKW RD1 C...

Page 4: ...GRAM adjustment is between approximately 7 O Clock and 11 O Clock Likewise the ADDR setting will only be programmed when the DISPLAY PROGRAM adjustment is between approximately 11 O Clock and 5 O Cloc...

Page 5: ...ection for the application All parameters are actual values except the VUB and CUB settings which are percentages The range these parameters can be programmed to is found in the specifications at the...

Page 6: ...consulted for OC settings However OC is typically between 110 and 125 of Full Load Amperage FLA UC The UC undercurrent setting is typically set to 80 of full load amperage FLA The overload relay with...

Page 7: ...rip mode TC J00 the RD1 position becomes the motor acceleration time To view and adjust MA TC must be J00 The motor acceleration time is related to the load on a motor For high inertia loads such as f...

Page 8: ...The following settings are available 0 1 oc1 2 oc2 3 oc3 4 oc4 A and ocA A setting which includes oc will allow the overload relay to automatically reset after an overload fault eg a setting of oc2 w...

Page 9: ...bled 1 minute after the motor starts and provides a 2 second trip time for motors exceeding 400 SFA regardless of trip class J00 Fast Linear Trip Mode This setting provides an adjustable linear trip t...

Page 10: ...s that 1 start attempt usually clears the sand out of the impeller RF oc1 UCTD UCTD 10 GF Because it may take several days to get a new pump motor and schedule for maintenance personnel to remove and...

Page 11: ...label The multi function display also announces system faults such as low voltage high voltage single phasing unbalance and reverse phasing errors Any time the MODE SELECT switch is in the RUN positio...

Page 12: ...img down RD2 before restarting Display alternates uc with RUN The overload relay has tripped on undercurrent and is timing down RD3 before restarting If undercurrent is not a normal condition for this...

Page 13: ...computer Control and monitoring is also possible from SymCom s RM 1000 and RM 2000 PLC and SCADA systems using the RS 485 standard and MODBUS protocol can also be used NOTE An RS 485MS 2W module is r...

Page 14: ...ust the Display Program adjustment until cLr appears on the display Release the Reset Program Button To verify the last fault was cleared place the Mode Select switch in the Run position Then press an...

Page 15: ...urrent 15 Timing 5 1 second Repeatability Voltage 0 5 of nominal voltage Current 1 of nominal current TRIP TIMES Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpo...

Page 16: ...Compliance to a Level of 6 KV Line to Line Hi Potential Test Meets UL508 2 x Rated Voltage 1000 Volts for 1 Minute Vibration IEC 68 2 6 10 55 Hz 1 mm Peak to Peak 2 Hours 3 Axis Shock IEC 68 2 27 30...

Page 17: ...h 0 315 Seconds RD2 Motor Cool Down Timer 2 500 Minutes x 0 5 if TC J00 OCTD Overcurrent Trip Delay Linear 2 250 x 0 158 0 315 Seconds RD3 Dry Well Recovery Timer 2 500 Minutes x 0 5 if TC J00 RU Numb...

Page 18: ...DISPLAY MESSAGE RESET PROGRAM 800 843 8848 SYMCOM INC RAPID CITY SD DIMENSIONS 07 25 03 18...

Page 19: ...sions 18 Fast Linear Trip Mode 5 Multi Function System Display 11 Operation 2 Programmable Operationg Points 17 Programming Examples 9 Programmable Parameters 5 Programming 4 Remote Reset 13 Specifica...

Page 20: ...2880 North Plaza Drive Rapid City SD 57702 Phone 800 843 8848 or 605 348 5580 FAX 605 348 5685 Visit our website at www symcom com for our complete catalog and new product listings...

Reviews: