3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
D500-82-00
1
I56-2536-003
Specifications
Operating Voltage:
18-35VDC, 18-35VAC, 115VAC, 230VAC
Operating Current (R-10E/R14E):
23mA DC @ 18-35VDC, 59mA AC @ 18-35VAC;
150mA AC @ 120VAC, 180mA AC @ 240VAC
Operating Current (R-20E/R-24E):
40mA DC @ 18-35VDC, 92mA AC @ 18-35VAC;
220 mA AC @ 120VAC, 260mA AC @ 240VAC
Operating Temperature:
–40°F to 158°F (–40°C to 70°C)
Humidity Range:
10% – 93%RH non-condensing
Dimensions:
R-10E/R-20E: 3.7˝H × 5.3˝W × 2.7˝D (94 mm H × 135 mm W × 69 mm D)
R-14E/R-24E: 5.4˝H × 10.9˝W × 2.7˝D (137 mm H × 277 mm W × 69 mm D)
Accessories:
R-10E/R-20E – 2 mounting screws
R-14E/R-24E – 4 mounting screws
Contact Ratings:
24VDC 7A
120VAC 10A
120VAC 1/6 HP
230VAC 7A
Notice: This manual should be left with the owner/user of this equipment.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
R-10E/R-20E/R-14E/R-24E
Multi Voltage Relay
General Description
Models R-10E/R-20E and R-14E/R-24E are multi voltage re-
lays with terminal strip field wiring connections, mounting
track and hardware mounted in a steel enclosure. The clo-
sure has a removable front cover that provides easy access
and a LED viewing hole on the top of the cover.
C0567-01
NC
C
NO
18-35 V
115 V
230 V
Not used
0V
18-35 VDC, 18-35VAC, 115VAC, 230VAC
R-10E Relay
NC
C
NO
NC
C
NO
18-35 V
115 V
230 V
Not used
0V
18-35 VDC, 18-35VAC, 115VAC, 230VAC
R-20E Relay
C0527-01
Metal Enclosure
C0569-01
The R-10E is a single 1 FORM C (SPDT) relay with a red
LED and the R-14E is a 4-gang 1 FORM C (SPDT) relay with
4 red LEDs. The R-20E is a single 2 Form C (DPDT) relay
with a red LED and the R-24E is a 4-gang 2 Form C (DPDT)
relay with 4 red LEDs. The LEDs indicate the energization
of the Relay Coil.
–
+
–
+
Non-Power
Limited
Power
Limited
NC
C
NO
Not used
0V
18-35 VDC, 18-35VAC, 115VAC, 230VAC
C0900-00
I56-2536-00
3
firealarmresources.com