background image

D900-37-00 

I56-2257-005R

For use with the following models:
Strobe - 12/24 volt: 

S1224MCK

Combo - 12/24 volt:  P1224MCK
Horn - 12/24 volt: 

H12/24K

“K” model series are outdoor rated when installed with System Sensor WBB.
The Products to which this manual applies may be covered by one or more of the following U.S. Patent numbers:  
5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,133,843; 6,522,261; 6,661,337; 6,793,375; 6,822,400; 5,931,569; 6,833,783; 6,838,997;

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

General Description

The  SpectrAlert  series  notification  appliances  are  designed  to 
meet the requirements of most agencies governing these devices, 
including:  NFPA,  ADA,  The  National  Fire  Alarm  Code,  UL,  and 
ULC.  Also,  check  with  your  local  Authority  Having  Jurisdiction 
for other codes or standards that may apply.
The SpectrAlert series can be installed in systems using 12- or 24-
volt panels having DC or full-wave rectified (FWR) power supplies. 
The series can also be installed in systems requiring synchroniza-
tion (module MDL or compatible equivalent required) or systems 
that do not require synchronization (no module required).

NOTICE:

 This manual shall be left with the owner/user of this equipment.

Fire Alarm System Considerations

Temporal and Non-Temporal Coded Signals:

The American National Standards Institute and the National Fire 
Alarm Code require that all horns used for building evacuation in-
stalled after July 1, 1996, must produce Temporal Coded Signals.
Signals other than those used for evacuation purposes do not have 
to produce the Temporal Coded Signal. Temporal coding is accom-
plished by interrupting a steady sound in the following manner:

Specifications

Automatic selection for 12 or 24 volt rated operation (DC or Full-Wave Rectified)

Electrical

Horns, Strobes, and
 

Horn/Strobes Voltages: 

Regulated 12 DC/FWR and Regulated 24 DC/FWR

Operational Voltage Ranges: 

12V=8-17.5 Volts; 24V=16-33 Volts

Synchronous Applications
 

with MDL Module: 

12V=9-17.5 Volts; 24V=17-33 Volts

NOTE: Horn units will operate on walk tests with on-time durations of .25 sec. or greater.

Flash Rate: 

1 flash per second 

K Series Operating Temperature: 

 Strobe,  horn  and  horn/strobe  models  are  indoor  and  outdoor  listed,  having  a  temperature 
range of –40° F to 150.8° F (–40° C to 66° C)

 

 All models are indoor/outdoor listed, strobes per UL 1971 and UL 1638, horns per UL 464.

Selectable Light Outputs: 

All candelas are selectable via a manual slide switch.

12/24 Volt Applications: 

15 or 15/75 candela

24 Volt Application: 

30, 75, 110 candela

 

 15/75 is listed at 15 candela per UL 1971 but will provide 75 candela on axis (straight ahead). 
15, 30, 75, or 110 are rated for that candela.

Sound Output: 

 Sound output levels are established at Underwriters Laboratories in their reverberant room. 
Always use the sound output specified as UL Reverberant Room when comparing products.

Listings: 

UL S3593/S5512 (Strobe); UL S4011 (Combo); UL 1638 and UL 1971 (Strobe); UL50 (Horn)

Note for Strobes: Do not exceed; 1) 8-17.5 or 16-33 voltage range limit; 2) maximum number of 70 strobe lights when connecting the MDL Sync module 

with a maximum line impedance of 4 ohms per loop and; 3) maximum line impedance as required by the fire alarm control manufacturer.

The models S1224MCK and P1224MCK incorporate a patented voltage booster design that has a more consistent flash bulb voltage over the range of candela 

selections. The benefit to the customer is a high quality strobe device.

Power Supply Considerations

Panels  typically  supply  DC  filtered  voltage  or  FWR  (full-wave 
rectified) voltage. The system design engineer must calculate the 
number of units used in a zone based on the type of panel supply. 
Be certain the sum of all the device currents do not exceed the 
current capability of the panel. Calculations are based on using 
the  device  current  found  in  the  subsequent  charts  and  must  be 
the current specified for the type of panel power supply used. 

Wire Sizes

The designer must be sure that the last device on the circuit has 
sufficient  voltage  to  operate  the  device  within  its  rated  voltage. 
When calculating the voltage available to the last device, it is nec-
essary to consider the voltage drop due to the resistance of the 
wire. The thicker the wire, the less the voltage drop. Generally, for 
purposes of determining the wire size necessary for the system, it 
is best to consider all of the devices as “lumped” on the end of the 
supply circuit (simulates “worst case”).

1

/

2

 Sec. 

On

1

/

2

 Sec. 

Off

1

/

2

 Sec. 

On

1

/

2

 Sec. 

Off

1

/

2

 Sec. 

On

1

1

/

2

 Sec. 

Off

Repeats

SpectrAlert Selectable Output
Outdoor Strobes, Horn and Horn/Strobes

firealarmresources.com

Reviews: