background image

Application:

The Taco Clock Timer/Temperature Aquastat combination is
designed to cycle the circulator during peak demand peri-
ods. The Analog Timer (No. 265-1) is adjustable to 15 minute
intervals within a 24 hour time frame. The Digital Timer
(No. 265-3) can be programmed for 7 day operation. The
Temperature Aquastat (No. 563-2) automatically switches
the circulator ON at 95ºF and OFF at 115ºF. The two can
be used in combination, or they can be used separately.
When the Clock Timer/Temperature Aquastat are used
together, the Timer switches ON sending power to the unit.
The Temperature Aquastat measures the temperature, and
cycles the circulator as long as the Timer is switched to the
ON mode.

If used separately, the Clock Timer operates the circulator
during the chosen number of ON/OFF intervals. When using
only the Temperature Aquastat, the circulator cycles inter-
mittently to maintain a temperature between 95ºF and 115ºF.

The Clock Timer and Temperature Aquastat are easy to
retrofit to any “00” Series Circulator. The user-friendly 24
hour analog clock has an hour hand, raised minute hand
for ease of adjustment, two directional arrows, and AM/PM
time settings. Our easy to program digital timer provides
maximum convenience, comfort and energy savings. The
Clock Timer can be mounted in any direction by just
attaching it to the capacitor box electrical connection hole.

Installation: FOLLOW ALL INSTRUCTIONS IN THE 

SEQUENCE THAT THEY APPEAR.

Analog Timer Installation Instructions:

1. Disconnect the electrical supply. Remove circulator

terminal box screw and cover.

2. Loosen Timer box cover screw and remove cover.

3. Assemble the back portion of the Timer to the “00” ter-

minal box as shown in the Timer installation diagram
(006 circulator pictured). Make sure that the protruding
tang on the back of the Timer box fits under the circu-
lator’s terminal box base. Adjust until the two terminal
box openings are aligned.

4. Secure the locknuts. Feed the yellow and white circu-

lator lead wires into the Timer through the bushing.
Reassemble circulator terminal box cover and secure
with the screw.

5. See electrical hook-up for Timer wiring.

Aquastat Installation Instructions:

1. Disconnect the electrical supply. Securely fasten the

Aquastat clip to 

3

4

" pipe or to the circulator casing for

1

2

" pipe applications. The Aquastat must be properly

fastened to insure a good reading.

2. See electrical hook-up for Aquastat wiring.

Electrical Hook-Up:

1. All electrical work must be performed by an electrician

in accordance with the latest edition of the National
Electrical Codes and Local Codes and Regulations.

2. Verify that the voltage, phase and frequency are correct

for the Circulator, Timer and Aquastat prior to connection.

3. Follow the appropriate wiring diagram

Analog 24 Hour Timer Programming:

1. Set clock to the exact time of day by turning the outer

black ring clockwise to move the hour/minute hands to
the correct position. Pay special attention to the white
arrow pointing to the correct 

AM/PM

time in the 24

hour outer ring.

2. Set the desired 

ON/OFF

times by pushing the trippers

away from the clock face for 

ON

operation. Leave the

trippers toward the clock face for 

OFF

operation. Each

tripper represents a 15 minute interval.

3. Set switch in the middle position for

automatic operation.

Analog Timer Manual Switch Settings:

1. Up = On, Constant Circulation    

I

2. Middle = Automatic operation

3. Down = Off    O

Instruction Sheet

Timer and Aquastat

102-067A

SUPERSEDES: May 1, 2010 

EFFECTIVE: October 1, 2010

Plant ID# 001-3969

Analog Timer Clock Face

TIME

ARROW

MANUAL

SWITCH

IN AUTO

POSITION

PROGRAM

TRIPPERS

NOTE:

To run Digital Timer in Manual 

ON

(

I

) mode,

press the (R) Reset key first.

A Taco resource – saving product

http://waterheatertimer.org/Water-heater-recirculation-system.html

Summary of Contents for 265-1

Page 1: ...g on the back of the Timer box fits under the circu lator s terminal box base Adjust until the two terminal box openings are aligned 4 Secure the locknuts Feed the yellow and white circu lator lead wires into the Timer through the bushing Reassemble circulator terminal box cover and secure with the screw 5 See electrical hook up for Timer wiring Aquastat Installation Instructions 1 Disconnect the ...

Page 2: ...inute Second reverse 1 unit at a time press hold to scroll rapidly G Skip key to change to next screen H R To RESET timer and erase all programs Programs The PNP digital timer will accept up to 16 programs A pro gram consists of 1 ON or OFF setting 1 Time of Day setting Hour Minute Second 1 Day s of Operation setting Note Each ON setting must be matched with a corre sponding OFF setting Programmin...

Page 3: ...e OFF time set ting For OFF settings no light bulb will appear on the clock face Repeat the above procedure to program each ON odd number and OFF even number desired time setting in sequential order Refer to Timer Schedule below To finish and set digital timer to AUTO operation 1 When all programs are completed move Programming Switch P to RUN position 2 Move Manual Operation switch to AUTO Timer ...

Page 4: ...dition of petroleum based fluids or certain chemical additives to the systems or other abuse will not be covered by this warranty If in doubt as to whether a particular substance is suitable for use with a Taco product or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products an...

Reviews: